Data sheet
3RW5214-1TC04
SIRIUS soft starter 200-480 V 18 A, 24 V AC/DC Screw terminals
Thermistor input
product brand name
SIRIUS
product category
Hybrid switching devices
product designation
Soft starter
product type designation
3RW52
manufacturer's article number
● of standard HMI module usable
3RW5980-0HS00
● of high feature HMI module usable
3RW5980-0HF00
● of communication module PROFINET standard
usable
3RW5980-0CS00
● of communication module PROFIBUS usable
3RW5980-0CP00
● of communication module Modbus TCP usable
3RW5980-0CT00
● of communication module Modbus RTU usable
3RW5980-0CR00
● of communication module Ethernet/IP
3RW5980-0CE00
● of circuit breaker usable at 400 V
3RV2032-4DA10; Type of coordination 1, Iq = 65 kA, CLASS 10
● of circuit breaker usable at 500 V
3RV2032-4DA10; Type of coordination 1, Iq = 15 kA, CLASS 10
● of circuit breaker usable at 400 V at inside-delta
circuit
3RV2032-4EA10; Type of coordination 1, Iq = 65 kA, CLASS 10
● of circuit breaker usable at 500 V at inside-delta
circuit
3RV2032-4EA10; Type of coordination 1, Iq = 15 kA, CLASS 10
● of the gG fuse usable up to 690 V
3NA3820-6; Type of coordination 1, Iq = 65 kA
● of the gG fuse usable at inside-delta circuit up to
500 V
3NA3820-6; Type of coordination 1, Iq = 65 kA
● of full range R fuse link for semiconductor protection
usable up to 690 V
3NE1802-0; Type of coordination 2, Iq = 65 kA
● of back-up R fuse link for semiconductor protection
usable up to 690 V
3NE8020-1; Type of coordination 2, Iq = 65 kA
General technical data
starting voltage [%]
30 ... 100 %
stopping voltage [%]
50 ... 50 %
start-up ramp time of soft starter
0 ... 20 s
current limiting value [%] adjustable
130 ... 700 %
certificate of suitability
● CE marking
Yes
● UL approval
Yes
● CSA approval
Yes
product component is supported
● HMI-Standard
Yes
● HMI-High Feature
Yes
product feature integrated bypass contact system
3RW52141TC04
Page 1/2
Yes
12.21.2020
Subject to change without notice
© Copyright Siemens
number of controlled phases
3
trip class
CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
buffering time in the event of power failure
● for main current circuit
100 ms
● for control circuit
100 ms
insulation voltage rated value
600 V
degree of pollution
3, acc. to IEC 60947-4-2
impulse voltage rated value
6 kV
blocking voltage of the thyristor maximum
1 600 V
service factor
1
surge voltage resistance rated value
6 kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
600 V
utilization category acc. to IEC 60947-4-2
AC 53a
shock resistance
15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
vibration resistance
15 mm to 6 Hz; 2g to 500 Hz
reference code acc. to IEC 81346-2
Q
product function
● ramp-up (soft starting)
Yes
● ramp-down (soft stop)
Yes
● Soft Torque
Yes
● adjustable current limitation
Yes
● pump ramp down
Yes
● intrinsic device protection
Yes
● motor overload protection
Yes; Full motor protection (thermistor motor protection and electronic
motor overload protection)
● evaluation of thermistor motor protection
Yes; Type A PTC or Klixon / Thermoclick
● inside-delta circuit
Yes
● auto-RESET
Yes
● manual RESET
Yes
● remote reset
Yes; By turning off the control supply voltage
● communication function
Yes
● operating measured value display
Yes; Only in conjunction with special accessories
● error logbook
Yes; Only in conjunction with special accessories
● via software parameterizable
No
● via software configurable
Yes
● PROFIenergy
Yes; in connection with the PROFINET Standard communication
module
● firmware update
Yes
● removable terminal for control circuit
Yes
● torque control
No
● analog output
No
Power Electronics
operational current
● at 40 °C rated value
18 A
● at 50 °C rated value
15.9 A
● at 60 °C rated value
13.8 A
operational current at inside-delta circuit
● at 40 °C rated value
31.5 A
● at 50 °C rated value
28 A
● at 60 °C rated value
23.9 A
operating voltage
● rated value
200 ... 480 V
● at inside-delta circuit rated value
200 ... 480 V
relative negative tolerance of the operating voltage
-15 %
relative positive tolerance of the operating voltage
10 %
relative negative tolerance of the operating voltage at
inside-delta circuit
-15 %
relative positive tolerance of the operating voltage at
10 %
3RW52141TC04
Page 2/3
12.21.2020
Subject to change without notice
© Copyright Siemens
inside-delta circuit
operating power for 3-phase motors
● at 230 V at 40 °C rated value
4 kW
● at 230 V at inside-delta circuit at 40 °C rated value
7.5 kW
● at 400 V at 40 °C rated value
7.5 kW
● at 400 V at inside-delta circuit at 40 °C rated value
15 kW
Operating frequency 1 rated value
50 Hz
Operating frequency 2 rated value
60 Hz
relative negative tolerance of the operating frequency
-10 %
relative positive tolerance of the operating frequency
10 %
adjustable motor current
● at rotary coding switch on switch position 1
7.5 A
● at rotary coding switch on switch position 2
8.2 A
● at rotary coding switch on switch position 3
8.9 A
● at rotary coding switch on switch position 4
9.6 A
● at rotary coding switch on switch position 5
10.3 A
● at rotary coding switch on switch position 6
11 A
● at rotary coding switch on switch position 7
11.7 A
● at rotary coding switch on switch position 8
12.4 A
● at rotary coding switch on switch position 9
13.1 A
● at rotary coding switch on switch position 10
13.8 A
● at rotary coding switch on switch position 11
14.5 A
● at rotary coding switch on switch position 12
15.2 A
● at rotary coding switch on switch position 13
15.9 A
● at rotary coding switch on switch position 14
16.6 A
● at rotary coding switch on switch position 15
17.3 A
● at rotary coding switch on switch position 16
18 A
● minimum
7.5 A
adjustable motor current
● for inside-delta circuit at rotary coding switch on
switch position 1
13 A
● for inside-delta circuit at rotary coding switch on
switch position 2
14.2 A
● for inside-delta circuit at rotary coding switch on
switch position 3
15.4 A
● for inside-delta circuit at rotary coding switch on
switch position 4
16.6 A
● for inside-delta circuit at rotary coding switch on
switch position 5
17.8 A
● for inside-delta circuit at rotary coding switch on
switch position 6
19.1 A
● for inside-delta circuit at rotary coding switch on
switch position 7
20.3 A
● for inside-delta circuit at rotary coding switch on
switch position 8
21.5 A
● for inside-delta circuit at rotary coding switch on
switch position 9
22.7 A
● for inside-delta circuit at rotary coding switch on
switch position 10
23.9 A
● for inside-delta circuit at rotary coding switch on
switch position 11
25.1 A
● for inside-delta circuit at rotary coding switch on
switch position 12
26.3 A
● for inside-delta circuit at rotary coding switch on
switch position 13
27.5 A
● for inside-delta circuit at rotary coding switch on
switch position 14
28.8 A
● for inside-delta circuit at rotary coding switch on
switch position 15
30 A
● for inside-delta circuit at rotary coding switch on
switch position 16
31.2 A
● at inside-delta circuit minimum
13 A
3RW52141TC04
Page 3/4
12.21.2020
Subject to change without notice
© Copyright Siemens
minimum load [%]
15 %; Relative to smallest settable Ie
power loss [W] for rated value of the current at AC
● at 40 °C after startup
17 W
● at 50 °C after startup
17 W
● at 60 °C after startup
16 W
power loss [W] at AC at current limitation 350 %
● at 40 °C during startup
276 W
● at 50 °C during startup
241 W
● at 60 °C during startup
200 W
Control circuit/ Control
type of voltage of the control supply voltage
AC/DC
● control supply voltage at AC at 50 Hz rated value
24 V
● control supply voltage at AC at 60 Hz rated value
24 V
relative negative tolerance of the control supply
voltage at AC at 50 Hz
-20 %
relative positive tolerance of the control supply
voltage at AC at 50 Hz
20 %
relative negative tolerance of the control supply
voltage at AC at 60 Hz
-20 %
relative positive tolerance of the control supply
voltage at AC at 60 Hz
20 %
control supply voltage frequency
50 ... 60 Hz
relative negative tolerance of the control supply
voltage frequency
-10 %
relative positive tolerance of the control supply
voltage frequency
10 %
● control supply voltage at DC rated value
24 V
relative negative tolerance of the control supply
voltage at DC
-20 %
relative positive tolerance of the control supply
voltage at DC
20 %
control supply current in standby mode rated value
160 mA
holding current in bypass operation rated value
360 mA
locked-rotor current at close of bypass contact
maximum
0.75 A
inrush current peak at application of control supply voltage
maximum
3.3 A
duration of inrush current peak at application of control
supply voltage
12.1 ms
design of the overvoltage protection
Varistor
design of short-circuit protection for control circuit
4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature
circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is
not part of scope of supply
Inputs/ Outputs
number of digital inputs
1
number of inputs for thermistor connection
1; Type A PTC or Klixon / Thermoclick
number of digital outputs
3
● not parameterizable
2
digital output version
2 normally-open contacts (NO) / 1 changeover contact (CO)
number of analog outputs
0
switching capacity current of the relay outputs
● at AC-15 at 250 V rated value
3A
● at DC-13 at 24 V rated value
1A
Installation/ mounting/ dimensions
mounting position
+/- 10° rotation possible and can be tilted forward or backward on
vertical mounting surface
fastening method
screw fixing
height
275 mm
width
170 mm
depth
152 mm
required spacing with side-by-side mounting
3RW52141TC04
Page 4/5
12.21.2020
Subject to change without notice
© Copyright Siemens
● forwards
10 mm
● backwards
0 mm
● upwards
100 mm
● downwards
75 mm
● at the side
5 mm
weight without packaging
2.1 kg
Connections/ Terminals
type of electrical connection
● for main current circuit
screw-type terminals
● for control circuit
screw-type terminals
wire length for thermistor connection
● with conductor cross-section = 0.5 mm² maximum
50 m
● with conductor cross-section = 1.5 mm² maximum
150 m
● with conductor cross-section = 2.5 mm² maximum
250 m
type of connectable conductor cross-sections
● for main contacts
— solid
2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— finely stranded with core end processing
2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²)
● at AWG cables for main current circuit solid
2x (16 ... 12), 2x (14 ... 8)
type of connectable conductor cross-sections
● for control circuit solid
1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● for control circuit finely stranded with core end
processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables for control circuit solid
1x (20 ... 12), 2x (20 ... 14)
wire length
● between soft starter and motor maximum
800 m
● at the digital inputs at AC maximum
100 m
● at the digital inputs at DC maximum
1 000 m
tightening torque
● for main contacts with screw-type terminals
2 ... 2.5 N·m
● for auxiliary and control contacts with screw-type
terminals
0.8 ... 1.2 N·m
tightening torque [lbf·in]
● for main contacts with screw-type terminals
18 ... 22 lbf·in
● for auxiliary and control contacts with screw-type
terminals
7 ... 10.3 lbf·in
Ambient conditions
installation altitude at height above sea level maximum
5 000 m; Derating as of 1000 m, see catalog
● ambient temperature during operation
-25 ... +60 °C; Please observe derating at temperatures of 40 °C or
above
● ambient temperature during storage and transport
-40 ... +80 °C
environmental category
● during operation acc. to IEC 60721
3K6 (no ice formation, only occasional condensation), 3C3 (no salt
mist), 3S2 (sand must not get into the devices), 3M6
● during storage acc. to IEC 60721
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must
not get inside the devices), 1M4
● during transport acc. to IEC 60721
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
EMC emitted interference
acc. to IEC 60947-4-2: Class A
Communication/ Protocol
communication module is supported
● PROFINET standard
Yes
● EtherNet/IP
Yes
● Modbus RTU
Yes
● Modbus TCP
Yes
● PROFIBUS
Yes
UL/CSA ratings
manufacturer's article number
● of circuit breaker
— usable for Standard Faults at 460/480 V
3RW52141TC04
Page 5/6
Siemens type: 3RV2742, max. 60 A or 3VA51, max. 60 A; Iq = 5 kA
12.21.2020
Subject to change without notice
© Copyright Siemens
according to UL
— usable for High Faults at 460/480 V according
to UL
Siemens type: 3RV2742, max. 30 A or 3VA51, max. 35 A; Iq max = 65
kA
— usable for Standard Faults at 460/480 V at
inside-delta circuit according to UL
Siemens type: 3RV2742, max. 60 A or 3VA51, max. 60 A; Iq = 5 kA
— usable for High Faults at 460/480 V at insidedelta circuit according to UL
Siemens type: 3VA51, max. 35 A; Iq max = 65 kA
— usable for Standard Faults at 575/600 V
according to UL
Siemens type: 3RV2742, max. 60 A or 3VA51, max. 60 A; Iq = 5 kA
— usable for Standard Faults at 575/600 V at
inside-delta circuit according to UL
Siemens type: 3RV2742, max. 60 A or 3VA51, max. 60 A; Iq = 5 kA
● of the fuse
— usable for Standard Faults up to 575/600 V
according to UL
Type: Class RK5 / K5, max. 70 A; Iq = 5 kA
— usable for High Faults up to 575/600 V
according to UL
Type: Class J / L, max. 70 A; Iq = 100 kA
— usable for Standard Faults at inside-delta
circuit up to 575/600 V according to UL
Type: Class RK5 / K5, max. 70 A; Iq = 5 kA
— usable for High Faults at inside-delta circuit up
to 575/600 V according to UL
Type: Class J / L, max. 70 A; Iq = 100 kA
operating power [hp] for 3-phase motors
● at 200/208 V at 50 °C rated value
3 hp
● at 220/230 V at 50 °C rated value
5 hp
● at 460/480 V at 50 °C rated value
10 hp
● at 200/208 V at inside-delta circuit at 50 °C rated
value
7.5 hp
● at 220/230 V at inside-delta circuit at 50 °C rated
value
7.5 hp
● at 460/480 V at inside-delta circuit at 50 °C rated
value
20 hp
contact rating of auxiliary contacts according to UL
R300-B300
Safety related data
protection class IP on the front acc. to IEC 60529
IP20
touch protection on the front acc. to IEC 60529
finger-safe, for vertical contact from the front
electromagnetic compatibility
in accordance with IEC 60947-4-2
Certificates/ approvals
General Product Approval
Declaration of Conformity
Miscellaneous
Marine / Shipping
EMC
Test Certificates
Marine / Shipping
Type Test
Certificates/Test
Report
other
Confirmation
Confirmation
Further information
3RW52141TC04
Page 6/7
12.21.2020
Subject to change without notice
© Copyright Siemens
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW5214-1TC04
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW5214-1TC04
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW5214-1TC04
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW5214-1TC04&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RW5214-1TC04/char
Characteristic: Installation altitude
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RW5214-1TC04&objecttype=14&gridview=view1
Simulation Tool for Soft Starters (STS)
https://support.industry.siemens.com/cs/ww/en/view/101494917
3RW52141TC04
Page 7/8
12.21.2020
Subject to change without notice
© Copyright Siemens
last modified:
3RW52141TC04