Data sheet
3VA5145-4EC31-1AA0
circuit breaker 3VA5 UL Frame 125 breaking capacity class S 25 kA @ 480 V 3pole, line protection TM230, FTAM, In=45 A overload protection Ir=45 A
permanently set short-circuit protection Ii=5...10 x In UL 489 SB (naval), 50° C
without connection
Model
product brand name
SENTRON
product designation
Molded-case circuit breaker
product designation / according to UL file
SEAM
design of the product
System protection
design of the load switch / according to UL 489 / Heating, Air
Conditioning, and Refrigeration circuit breaker (HACR Type)
Yes
design of the load switch / according to UL 489 / High-IntensityDischarge circuit breaker (HID Type)
Yes
design of the load switch / according to UL 489 / Switching Duty
circuit breaker (SWD Type)
No
design of the overcurrent release
TM230
protection function of the overcurrent release
LI
number of poles
3
General technical data
operating voltage / at AC / rated value
690 V
power loss [W] / maximum
11.4 W
power loss [W] / for rated value of the current / at AC / in hot
operating state / per pole
3.8 W
mechanical service life (operating cycles) / typical
20 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V
8 000
electrical endurance (operating cycles) / at AC-1 / at 690 V
4 000
electrical endurance (operating cycles) / at 480 V
8 000
electrical endurance (operating cycles) / at 600 V
4 000
product feature / for neutral conductors / upgradable/retrofittable
/ short-circuit and overload proof
No
ground-fault monitoring version
without
product function
● communication function
No
● other measurement function
No
Net Weight
0.88 kg
Current
marking / according to UL 489 / 100%-rated breaker
No
operational current
● at 40 °C
45 A
● at 45 °C
44 A
● at 50 °C
44 A
● at 55 °C
43 A
● at 60 °C
42 A
● at 65 °C
42 A
● at 70 °C
41 A
3VA51454EC311AA0
Page 1/5
5/2/2024
Subject to change without notice
© Copyright Siemens
Switching capacity according to IEC 60947
switching capacity class of the circuit breaker
S
design of short-circuit protection
For switching power values in DC networks, see the 3VA molded case circuit
breaker device manual; link to be found under Service & Support in the last
chapter
Switching capacity according to UL 489
current breaking capacity
● at 240 V
65 kA
● at 480 V
25 kA
● at 600 Y/347 V
14 kA
Adjustable parameters
adjustable response value setting current (Ir) / of the L-trip / with
I2t characteristic
● minimum
45 A
● maximum
45 A
adjustable response value delay time (tr) / for L-tripping / with I2t
characteristic
● minimum
1s
● maximum
1s
adjustable response value setting current (Ii) / for I-tripping
● minimum
225 A
● maximum
450 A
adjustable setting current (InN) / for N-tripping
● minimum
0A
● maximum
0A
product function / grounding protection
No
Mechanical Design
product component
● undervoltage release
No
● voltage trigger
No
● trip indicator
No
height [in]
5.51 in
height
140 mm
width [in]
3 in
width
76.2 mm
depth [in]
3.01 in
depth
76.5 mm
Connections
arrangement of electrical connectors / for main current circuit
Without connection
type of electrical connection / for main current circuit
Without
Auxiliary circuit
number of CO contacts / for auxiliary contacts
0
Accessories
product extension / optional / motor drive
Yes
Environmental conditions
protection class IP / on the front
IP40
ambient temperature
● during operation / minimum
-25 °C
● during operation / maximum
70 °C
● during storage / minimum
-40 °C
● during storage / maximum
80 °C
Approvals / Certificates
General Product Approval
Confirmation
General Product Approval
3VA51454EC311AA0
Page 2/5
EMV
Test Certificates
5/2/2024
Marine / Shipping
Subject to change without notice
© Copyright Siemens
Miscellaneous
Type Test Certificates/Test Report
other
Miscellaneous
Environment
Confirmation
Miscellaneous
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA5145-4EC31-1AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VA5145-4EC31-1AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA5145-4EC31-1AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
3VA51454EC311AA0
Page 3/5
5/2/2024
Subject to change without notice
© Copyright Siemens
5
3
1
-Q
I>>
6
I>>
4
2
I>>
CB
last modified:
3VA51454EC311AA0
Page 4/5
1
2
3
4
5
6
3/11/2024
5/2/2024
Subject to change without notice
© Copyright Siemens
3VA51454EC311AA0
Page 5/5
5/2/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3VA5145-4EC31-1AA0”相匹配的价格&库存,您可以联系我们找货