3VA6210-5HN41-0AA0
circuit breaker 3VA6 UL Frame 250 breaking capacity class M 35 kA @ 480 V 4pole, line protection ETU350, LSI, In=100 A overload protection Ir=40 A...100 A
short-circuit protection Isd=1.5...10 x Ir, Ii=12 x In neutral conductor protection
adjustable (OFF, 50%, 100%) without connection
Model
product brand name
SENTRON
product designation
Molded-case circuit breaker
product designation / according to UL file
MFAE
design of the product
System protection
design of the load switch / according to UL 489 / Heating, Air
Conditioning, and Refrigeration circuit breaker (HACR Type)
Yes
design of the overcurrent release
ETU350
protection function of the overcurrent release
LSI
number of poles
4
General technical data
insulation voltage / rated value
800 V
operating voltage / at AC / rated value
690 V
power loss [W] / maximum
6.7 W
power loss [W] / for rated value of the current / at AC / in hot
operating state / per pole
2.23 W
mechanical service life (operating cycles) / typical
25 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V
12 000
electrical endurance (operating cycles) / at AC-1 / at 690 V
8 400
electrical endurance (operating cycles) / at 480 V
12 000
electrical endurance (operating cycles) / at 600 V
8 400
product feature / for neutral conductors / upgradable/retrofittable
/ short-circuit and overload proof
No
ground-fault monitoring version
without
product function
● communication function
No
● other measurement function
No
Net Weight
3.2 kg
Current
marking / according to UL 489 / 100%-rated breaker
No
operational current
● at 40 °C
100 A
● at 45 °C
100 A
● at 50 °C
100 A
● at 55 °C
100 A
● at 60 °C
100 A
● at 65 °C
100 A
● at 70 °C
100 A
3VA62105HN410AA0
Page 1/6
6/2/2024
Subject to change without notice
© Copyright Siemens
Switching capacity according to IEC 60947
switching capacity class of the circuit breaker
M
maximum short-circuit current breaking capacity (Icu)
● at 240 V
85 kA
● at 415 V
55 kA
● at 690 V
3 kA
operating short-circuit current breaking capacity (Ics)
● at 240 V
85 kA
● at 415 V
55 kA
● at 690 V
3 kA
short-circuit current making capacity (Icm)
● at 240 V
187 kA
● at 415 V
121 kA
● at 690 V
4.5 kA
Switching capacity according to UL 489
current breaking capacity
● at 240 V
100 kA
● at 480 V
35 kA
● at 600 V
18 kA
Adjustable parameters
adjustable response value setting current (Ir) / of the L-trip / with
I2t characteristic
● minimum
40 A
● maximum
100 A
adjustable response value delay time (tr) / for L-tripping / with I2t
characteristic
● minimum
0.5 s
● maximum
17 s
adjustable response value setting current (Isd) / of S-trip / with
I0t characteristic
● minimum
150 A
● maximum
1 000 A
adjustable response value setting current (Isd) / of S-trip / with
I2t characteristic
● minimum
150 A
● maximum
1 000 A
adjustable response value delay time (tsd) / for S-tripping / with
I2t characteristic
● minimum
0.0001 s
● maximum
0.4 s
adjustable response value setting current (Ii) / for I-tripping
● minimum
1 200 A
● maximum
1 200 A
adjustable setting current (InN) / for N-tripping
● minimum
50 A
● maximum
100 A
design of the N-conductor protection
adjustable OFF; 50%; 100%
product function / grounding protection
No
Mechanical Design
product component
● undervoltage release
No
● voltage trigger
No
● trip indicator
No
height [in]
7.8 in
height
198 mm
width [in]
5.51 in
width
140 mm
depth [in]
3.39 in
depth
86 mm
Connections
arrangement of electrical connectors / for main current circuit
Without connection
type of electrical connection / for main current circuit
Without
3VA62105HN410AA0
Page 2/6
6/2/2024
Subject to change without notice
© Copyright Siemens
Auxiliary circuit
number of CO contacts / for auxiliary contacts
0
Accessories
product extension / optional / motor drive
Yes
Environmental conditions
protection class IP / on the front
IP40
ambient temperature
● during operation / minimum
-25 °C
● during operation / maximum
70 °C
● during storage / minimum
-40 °C
● during storage / maximum
80 °C
Environmental footprint
Siemens Eco Profile (SEP)
Siemens EcoTech
reference code / according to IEC 81346-2
Q
Approvals / Certificates
General Product Approval
Confirmation
General Product Approval
EMV
Marine / Shipping
Miscellaneous
Marine / Shipping
other
Confirmation
Dangerous Good
Transport Information
Miscellaneous
Miscellaneous
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA6210-5HN41-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VA6210-5HN41-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA6210-5HN41-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
3VA62105HN410AA0
Page 3/6
6/2/2024
Subject to change without notice
© Copyright Siemens
N 7
5
3
1
-Q
ETU350
L
I> S
I>
I>
I>
I>
I>>
I>>
I>>
I>>
I>> I
N N
3VA62105HN410AA0
Page 4/6
6/2/2024
-X2
8
6
4
2
N
EFB/
MMB
Subject to change without notice
© Copyright Siemens
CB
1
2
3
4
5
6
7 N
N 8
ETU350
EFB/
MMB
-X2
I> I>> N
L
last modified:
3VA62105HN410AA0
Page 5/6
S
I
N
3/11/2024
6/2/2024
Subject to change without notice
© Copyright Siemens
3VA62105HN410AA0
Page 6/6
6/2/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“3VA6210-5HN41-0AA0”相匹配的价格&库存,您可以联系我们找货