Data sheet
5SV3314-6
Residual current operated circuit breaker, 2-pole, type A, In: 40 A, 30 mA, Un AC:
230 V
Model
product brand name
SENTRON
product designation
RCCB
design of the product
Instantaneous
product type designation
5SV3
General technical data
number of poles
2
size of installation devices according to DIN 43880
1
mechanical service life (operating cycles) typical
10 000
short-circuit current of series fuse maximum permissible
63 A
short-circuit current rating
10 kA
switching function short-term delayed
No
overvoltage category
III
insulation voltage (Ui) rated value
2 000 V
tripping fault current rated value
30 mA
Supply voltage
supply voltage for testing equipment minimum
195 V
value range of the supply voltage frequency
50 Hz
value range of the operating frequency
50 Hz
value range of the supply voltage at AC
230 V
Protection class
protection class IP
IP20, if the distribution board is installed, with connected conductors
Breaking Capacity
switching capacity current
● according to IEC 61008-1 rated value
grid spacing
0.5 kA
60 mm
Dissipation
power loss [W]
● for rated value of the current at AC in hot operating state
per pole
2.6 W
● maximum
5.2 W
Product details
product feature silicon-free
Yes
product extension installable supplementary devices
Yes
Connections
connectable conductor cross-section solid
● minimum
0.75 mm²
● maximum
35 mm²
connectable conductor cross-section stranded
5SV33146
Page 1/5
5/10/2024
Subject to change without notice
© Copyright Siemens
● minimum
0.75 mm²
● maximum
35 mm²
tightening torque with screw-type terminals
● minimum
2.5 N·m
● maximum
3 N·m
position of power supply cord
top or bottom
Mechanical Design
height
90 mm
width
36 mm
depth
70 mm
installation depth
70 mm
number of modular width units
2
fastening method
DIN rail (REG)
mounting position
any
net weight
208 g
Environmental conditions
ambient temperature during operation
● minimum
-25 °C
● maximum
45 °C
ambient temperature during storage minimum
-40 °C
number of test cycles for environmental testing according to IEC
60068-2-30
28
Environmental footprint
Environmental Product Declaration(EPD)
Yes
Global Warming Potential [CO2 eq] total
8.73 kg
Global Warming Potential [CO2 eq] during manufacturing
1.32 kg
Global Warming Potential [CO2 eq] during operation
7.39 kg
Global Warming Potential [CO2 eq] after end of life
0.017 kg
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
EMV
Miscellaneous
other
Miscellaneous
Miscellaneous
Railway
Special Test Certificate
Test Certificates
Dangerous Good
Confirmation
Transport Information
other
Confirmation
Environment
Environmental Confirmations
Environment
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
5SV33146
Page 2/5
5/10/2024
Subject to change without notice
© Copyright Siemens
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=5SV3314-6
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/5SV3314-6
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=5SV3314-6
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
5SV33146
Page 3/5
5/10/2024
Subject to change without notice
© Copyright Siemens
I
-CB
last modified:
5SV33146
Page 4/5
1
2
N
N.
5/1/2024
5/10/2024
Subject to change without notice
© Copyright Siemens
5SV33146
Page 5/5
5/10/2024
Subject to change without notice
© Copyright Siemens