Data sheet
5SV3344-4
residual current operated circuit breaker, 4-pole, type B, short-time-delayed, In: 40
A, 30 mA, Un AC: 400 V SIGRES: harsh ambient conditions, extended test interval
Model
product brand name
SENTRON
product designation
RCCB
design of the product
Short-time delayed
product type designation
5SV3
product variations
SIGRES
General technical data
number of poles
4
size of installation devices according to DIN 43880
1
mechanical service life (operating cycles) typical
10 000
short-circuit current of series fuse maximum permissible
100 A
short-circuit current rating
10 kA
switching function short-term delayed
Yes
overvoltage category
III
insulation voltage (Ui) rated value
2 000 V
tripping fault current rated value
30 mA
Supply voltage
supply voltage for testing equipment minimum
70 V
value range of the supply voltage frequency
50/60 Hz
value range of the operating frequency
50/60 Hz
value range of the supply voltage at AC
70-440 V
Protection class
protection class IP
IP20, if the distribution board is installed, with connected conductors
Breaking Capacity
switching capacity current
● according to IEC 61008-1 rated value
grid spacing
0.8 kA
60 mm
Dissipation
power loss [W]
● for rated value of the current at AC in hot operating state
per pole
2.5 W
● maximum
7.5 W
Product details
product feature silicon-free
Yes
product extension installable supplementary devices
Yes
Connections
connectable conductor cross-section solid
● minimum
0.75 mm²
● maximum
35 mm²
5SV33444
Page 1/5
5/16/2024
Subject to change without notice
© Copyright Siemens
connectable conductor cross-section stranded
● minimum
0.75 mm²
● maximum
35 mm²
tightening torque with screw-type terminals
● minimum
2.5 N·m
● maximum
3 N·m
position of power supply cord
top or bottom (top for SIGRES function also in switched-off state)
Mechanical Design
height
90 mm
width
72 mm
depth
70 mm
installation depth
70 mm
number of modular width units
4
fastening method
DIN rail (REG)
mounting position
any
net weight
544 g
Environmental conditions
ambient temperature during operation
● minimum
-25 °C
● maximum
45 °C
ambient temperature during storage minimum
-40 °C
number of test cycles for environmental testing according to IEC
60068-2-30
28
Environmental footprint
Environmental Product Declaration(EPD)
Yes
Global Warming Potential [CO2 eq] total
39.9 kg
Global Warming Potential [CO2 eq] during manufacturing
5.06 kg
Global Warming Potential [CO2 eq] during operation
36.7 kg
Global Warming Potential [CO2 eq] after end of life
-1.89 kg
Approvals Certificates
General Product Approval
Confirmation
General Product Approval
Test Certificates
Miscellaneous
Railway
Confirmation
Dangerous Good
Miscellaneous
other
Miscellaneous
Railway
Confirmation
Miscellaneous
Special Test Certificate
Environmental Confirmations
Environmental Confirmations
Environment
Transport Information
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=5SV3344-4
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/5SV3344-4
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=5SV3344-4
CAx-Online-Generator
5SV33444
Page 2/5
5/16/2024
Subject to change without notice
© Copyright Siemens
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
6,2
69,8
3
5
4
6
N
1
2
89,8
71,8
5SV33444
Page 3/5
5/16/2024
N
-Q
Subject to change without notice
© Copyright Siemens
last modified:
5SV33444
Page 4/5
5/1/2024
5/16/2024
Subject to change without notice
© Copyright Siemens
5SV33444
Page 5/5
5/16/2024
Subject to change without notice
© Copyright Siemens