Data sheet
6AV2123-2MB03-0AX0
SIMATIC HMI, KTP1200 Basic, Basic Panel, Key/touch operation, 12" TFT
display, 65536 colors, PROFINET interface, configurable from WinCC
Basic V13/ STEP 7 Basic V13, contains open-source software, which is
provided free of charge see enclosed CD
General information
Product type designation
KTP1200 Basic color PN
Display
Design of display
TFT widescreen display, LED backlighting
Screen diagonal
12 in
Display width
261.1 mm
Display height
163.2 mm
Number of colors
65 536
Resolution (pixels)
● Horizontal image resolution
1 280 pixel
● Vertical image resolution
800 pixel
Backlighting
● MTBF backlighting (at 25 °C)
20 000 h
● Backlight dimmable
Yes
Control elements
Keyboard fonts
● Function keys
— Number of function keys
10
— Number of function keys with LEDs
0
● Keys with LED
No
● System keys
No
● Numeric keyboard
Yes; Onscreen keyboard
● alphanumeric keyboard
Yes; Onscreen keyboard
Touch operation
● Design as touch screen
Yes; Analog-resistive
Installation type/mounting
Mounting position
vertical
Mounting in portrait format possible
Yes
Mounting in landscape format possible
Yes
maximum permissible angle of inclination without external
ventilation
35°
Supply voltage
Type of supply voltage
DC
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Input current
Current consumption (rated value)
510 mA
Starting current inrush I²t
0.2 A²·s
6AV21232MB030AX0
Page 1/6
7/7/2022
Subject to change without notice
© Copyright Siemens
Power
Active power input, typ.
12.2 W
Processor
Processor type
ARM
Memory
Flash
Yes
RAM
Yes
Memory available for user data
10 Mbyte
Type of output
Acoustics
● Buzzer
Yes
● Speaker
No
Time of day
Clock
● Hardware clock (real-time)
Yes
● Software clock
Yes
● retentive
Yes; Back-up duration typically 6 weeks
● synchronizable
Yes
Interfaces
Number of industrial Ethernet interfaces
1
Number of RS 485 interfaces
0
Number of RS 422 interfaces
0
Number of RS 232 interfaces
0
Number of USB interfaces
1; Up to 16 GB
Number of 20 mA interfaces (TTY)
0
Number of parallel interfaces
0
Number of other interfaces
0
Number of SD card slots
0
With software interfaces
No
Industrial Ethernet
● Industrial Ethernet status LED
2
Protocols
PROFINET
Yes
Supports protocol for PROFINET IO
No
IRT
No
PROFIBUS
No
EtherNet/IP
Yes
MPI
No
Protocols (Ethernet)
● TCP/IP
Yes
● DHCP
Yes
● SNMP
Yes
● DCP
Yes
● LLDP
Yes
WEB characteristics
● HTTP
No
● HTML
No
Redundancy mode
Media redundancy
— MRP
No
Further protocols
● CAN
No
● MODBUS
Yes; Modicon (MODBUS TCP/IP)
Interrupts/diagnostics/status information
Diagnoses
● Diagnostic information readable
No
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas
6AV21232MB030AX0
Page 2/6
Yes
7/7/2022
Subject to change without notice
© Copyright Siemens
● Limit class B, for use in residential areas
No
Degree and class of protection
IP (at the front)
IP65
IP (rear)
IP20
NEMA (front)
● Enclosure Type 4 at the front
Yes
● Enclosure Type 4x at the front
Yes
Standards, approvals, certificates
CE mark
Yes
cULus
Yes
RCM (formerly C-TICK)
Yes
KC approval
Yes
Use in hazardous areas
● ATEX Zone 2
No
● ATEX Zone 22
No
● IECEx Zone 2
No
● IECEx Zone 22
No
● cULus Class I Zone 1
No
● cULus Class I Zone 2, Division 2
No
● FM Class I Division 2
No
Marine approval
● Germanischer Lloyd (GL)
Yes
● American Bureau of Shipping (ABS)
Yes
● Bureau Veritas (BV)
Yes
● Det Norske Veritas (DNV)
Yes
● Lloyds Register of Shipping (LRS)
Yes
● Nippon Kaiji Kyokai (Class NK)
Yes
● Polski Rejestr Statkow (PRS)
No
● Chinese Classification Society (CCS)
No
Ambient conditions
Ambient temperature during operation
Operation (vertical installation)
— For vertical installation, min.
0 °C
— For vertical installation, max.
50 °C
Operation (max. tilt angle)
— At maximum tilt angle, min.
0 °C
— At maximum tilt angle, max.
40 °C
Operation (vertical installation, portrait format)
— For vertical installation, min.
0 °C
— For vertical installation, max.
40 °C
Operation (max. tilt angle, portrait format)
— At maximum tilt angle, min.
0 °C
— At maximum tilt angle, max.
35 °C
Ambient temperature during storage/transportation
● min.
-20 °C
● max.
60 °C
Relative humidity
● Operation, max.
90 %; no condensation
Operating systems
proprietary
Yes
pre-installed operating system
● Windows CE
No
configuration / header
Message indicator
Yes
Alarm system (incl. buffer and acknowledgment)
Yes
Process value display (output)
Yes
Process value default (input) possible
Yes
Recipe management
Yes
Configuration software
6AV21232MB030AX0
Page 3/6
7/7/2022
Subject to change without notice
© Copyright Siemens
● STEP 7 Basic (TIA Portal)
Yes; via integrated WinCC Basic (TIA Portal)
● STEP 7 Professional (TIA Portal)
Yes; via integrated WinCC Basic (TIA Portal)
● WinCC flexible Compact
No
● WinCC flexible Standard
No
● WinCC flexible Advanced
No
● WinCC Basic (TIA Portal)
Yes
● WinCC Comfort (TIA Portal)
Yes
● WinCC Advanced (TIA Portal)
Yes
● WinCC Professional (TIA Portal)
Yes
Languages
Online languages
● Number of online/runtime languages
10
Project languages
● Languages per project
32
Functionality under WinCC (TIA Portal)
Libraries
Yes
Applications/options
● Web browser
Yes
● SIMATIC WinCC Sm@rtServer
Yes; Available with WinCC (TIA Portal) V14 or higher
Number of Visual Basic Scripts
No
Task planner
Yes
● time-controlled
No
● task-controlled
Yes
Help system
● Number of characters per info text
Yes
500
Message system
● Number of alarm classes
32
● Bit messages
— Number of bit messages
1 000
● Analog messages
— Number of analog messages
25
● S7 alarm number procedure
No
● System messages HMI
Yes
● System event, more (SIMATIC S7, SINUMERIK,
SIMOTION, ... )
Yes; System message buffer of the SIMATIC S7-1200 and S7-1500
● Number of characters per message
80
● Number of process values per message
8
● Acknowledgment groups
Yes
● Message indicator
Yes
● Message buffer
— Number of entries
256
— Circulating buffer
Yes
— retentive
Yes
— maintenance-free
Yes
Recipe management
● Number of recipes
50
● Data records per recipe
100
● Entries per data record
100
● Size of internal recipe memory
256 kbyte
● Recipe memory expandable
No
Variables
● Number of variables per device
800
● Number of variables per screen
100
● Limit values
Yes
● Multiplexing
Yes
● Structures
No
● Arrays
Yes
Images
● Number of configurable images
250
● Permanent window/default
Yes
6AV21232MB030AX0
Page 4/6
7/7/2022
Subject to change without notice
© Copyright Siemens
● Global image
Yes
● Pop-up images
No
● Slide-in images
No
● Image selection by PLC
Yes
● Image number in the PLC
Yes
Image objects
● Number of objects per image
100
● Text fields
Yes
● I/O fields
Yes
● Graphic I/O fields (graphics list)
Yes
● Symbolic I/O fields (text list)
Yes
● Date/time fields
Yes
● Switches
Yes
● Buttons
Yes
● Graphic display
Yes
● Icons
Yes
● Geometric objects
Yes
Complex image objects
● Number of complex objects per screen
10
● Alarm view
Yes
● Trend view
Yes
● User view
Yes
● Status/control
No
● Sm@rtClient view
No
● Recipe view
Yes
● f(x) trend view
No
● System diagnostics view
Yes; System message buffer of the SIMATIC S7-1200 and S7-1500
● Media Player
No
● HTML browser
Yes
● PDF display
No
● IP camera display
No
● Bar graphs
Yes
● Sliders
No
● Pointer instruments
No
● Analog/digital clock
No
Lists
● Number of text lists per project
300
● Number of entries per text list
100
● Number of graphics lists per project
100
● Number of entries per graphics list
100
Archiving
● Number of archives per device
2; One message and one process value archive
● Number of entries per archive
10 000
● Message archive
Yes
● Process value archive
Yes
● Archiving methods
— Sequential archive
Yes
— Short-term archive
Yes
● Memory location
— Memory card
No
— USB memory
Yes
— Ethernet
No
● Data storage format
— CSV
No
— TXT
Yes
— RDB
No
Security
● Number of user groups
50
● Number of user rights
32
● Number of users
50
6AV21232MB030AX0
Page 5/6
7/7/2022
Subject to change without notice
© Copyright Siemens
● Password export/import
Yes
● SIMATIC Logon
No
Character sets
● Keyboard fonts
— US English
Yes
Transfer (upload/download)
● MPI/PROFIBUS DP
No
● USB
No
● Ethernet
Yes
● using external storage medium
Yes
Process coupling
● S7-1200
Yes
● S7-1500
Yes
● S7-200
Yes
● S7-300/400
Yes
● LOGO!
Yes
● WinAC
Yes
● SINUMERIK
Yes; No access to NCK data
● SIMOTION
Yes
● Allen Bradley (EtherNet/IP)
Yes
● Allen Bradley (DF1)
No
● Mitsubishi (MC TCP/IP)
Yes
● Mitsubishi (FX)
No
● OMRON (FINS TCP)
No
● OMRON (LINK/Multilink)
No
● Modicon (Modbus TCP/IP)
Yes
● Modicon (Modbus)
No
Service tools/configuration aids
● Backup/Restore manually
Yes
● Backup/Restore automatically
No
● Simulation
Yes
● Device switchover
Yes
Peripherals/Options
Printer
No
SIMATIC HMI MM memory card: Multi Media Card
No
SIMATIC HMI SD memory card: Secure Digital memory
card
No
SIMATIC HMI CF memory card Compact Flash Card
No
USB memory
Yes
SIMATIC IPC USB Flashdrive (USB stick)
Yes
SIMATIC HMI USB stick
Yes
Mechanics/material
Enclosure material (front)
● Plastic
Yes
● Aluminum
No
● Stainless steel
No
Dimensions
Width of the housing front
330 mm
Height of housing front
245 mm
Mounting cutout, width
310 mm
Mounting cutout, height
221 mm
Overall depth
60 mm
Weights
Weight (without packaging)
1 710 g
Weight (with packaging)
2.2 kg
last modified:
10/8/2021
6AV21232MB030AX0
Page 6/6
7/7/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6AV21232MB030AX0”相匹配的价格&库存,您可以联系我们找货