Data sheet
6EP1334-3BA10
SITOP PSU200M/1-2AC/24VDC/10A
SITOP PSU200M 10 A stabilized power supply input: 120/230-500 V AC output: 24
V DC/10 A
input
type of the power supply network
1-phase and 2-phase AC
supply voltage at AC
Set by means of selector switch on the device
supply voltage 1 at AC
120 ... 230 V
supply voltage 2 at AC
230 ... 500 V
input voltage 1 at AC
85 ... 264 V
input voltage 2 at AC
176 ... 550 V
wide range input
Yes
overvoltage overload capability
1300 Vpeak, 1.3 ms
buffering time for rated value of the output current in the event of
power failure minimum
25 ms
operating condition of the mains buffering
at Vin = 120/230 V, typ. 150 ms at Vin = 400 V
line frequency
50/60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 120 V
4.4 A
● at rated input voltage 230 V
2.4 A
● at rated input voltage 500 V
1.1 A
current limitation of inrush current at 25 °C maximum
35 A
I2t value maximum
4 A²·s
fuse protection type
T 6.3 A (not accessible)
fuse protection type in the feeder
Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A)
characteristic C (B); required at 2-phase operation: circuit breaker 2-pole
connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV27111ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
output
voltage curve at output
Controlled, isolated DC voltage
output voltage at DC rated value
24 V
output voltage
● at output 1 at DC rated value
24 V
output voltage adjustable
Yes; via potentiometer
adjustable output voltage
24 ... 28.8 V
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
residual ripple
● maximum
50 mV
voltage peak
● maximum
display version for normal operation
6EP13343BA10
Page 1/4
200 mV
Green LED for 24 V OK
5/14/2024
Subject to change without notice
© Copyright Siemens
type of signal at output
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on
Overshoot of Vout approx. 3 %
response delay maximum
1s
voltage increase time of the output voltage
● typical
50 ms
output current
● rated value
10 A
● rated range
0 ... 10 A; +60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V)
supplied active power typical
240 W
short-term overload current
● at short-circuit during operation typical
30 A
duration of overloading capability for excess current
● at short-circuit during operation
25 ms
constant overload current
● on short-circuiting during the start-up typical
12 A
bridging of equipment
Yes; switchable characteristic
number of parallel-switched equipment resources for increasing
the power
2
efficiency
efficiency in percent
91 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
24 W
● during no-load operation maximum
6W
closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
0.1 %
relative control precision of the output voltage load step of
resistive load 50/100/50 % typical
3%
setting time
● load step 50 to 100% typical
2 ms
● load step 100 to 50% typical
2 ms
setting time
● maximum
5 ms
protection and monitoring
design of the overvoltage protection
< 35 V
property of the output short-circuit proof
Yes
design of short-circuit protection
Alternatively, constant current characteristic approx. 12 A or latching shutdown
● typical
12 A
enduring short circuit current RMS value
● typical
display version for overload and short circuit
12 A
LED yellow for "overload", LED red for "latching shutdown"
safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class
Class I
leakage current
● maximum
3.5 mA
● typical
0.32 mA
protection class IP
IP20
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
EN 61000-3-2
● for interference immunity
EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● EAC approval
Yes
6EP13343BA10
Page 2/4
5/14/2024
Subject to change without notice
© Copyright Siemens
● Regulatory Compliance Mark (RCM)
Yes
● NEC Class 2
No
● SEMI F47
Yes
type of certification
● CB-certificate
MTBF at 40 °C
Yes
1 055 408 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx
No
● ATEX
No
● ULhazloc approval
No
● cCSAus, Class 1, Division 2
No
● FM registration
No
standards, specifications, approvals marine classification
shipbuilding approval
Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● French marine classification society (BV)
No
● Det Norske Veritas (DNV)
Yes
● Lloyds Register of Shipping (LRS)
No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration
Yes
Global Warming Potential [CO2 eq]
● total
763.9 kg
● during manufacturing
12.6 kg
● during operation
751 kg
● after end of life
0.18 kg
ambient conditions
ambient temperature
● during operation
-25 ... +70 °C; With natural convection; startup tested starting from -40 °C
nominal voltage
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection
screw terminal
● at input
L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm² single-core/finely stranded
● at output
+, -: 2 screw terminals each for 0.2 ... 2.5 mm²
● for auxiliary contacts
13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²
mechanical data
width × height × depth of the enclosure
70 × 121
installation width × mounting height
70 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15
● standard rail mounting
Yes
● S7 rail mounting
No
● wall mounting
No
housing can be lined up
Yes
net weight
0.8 kg
accessories
electrical accessories
Buffer module
further information internet links
internet link
● to web page: selection aid TIA Selection Tool
https://siemens.com/tst
● to website: Industrial communication
http://www.siemens.com/simatic-net
● to website: CAx-Download-Manager
http://www.siemens.com/cax
6EP13343BA10
Page 3/4
5/14/2024
Subject to change without notice
© Copyright Siemens
additional information
other information
Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information
Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)
Classifications
Version
Classification
14
27-04-07-01
eClass
12
27-04-07-01
eClass
9.1
27-04-07-01
eClass
9
27-04-07-01
eClass
8
27-04-90-02
eClass
7.1
27-04-90-02
eClass
6
27-04-90-02
ETIM
9
EC002540
ETIM
8
EC002540
ETIM
7
EC002540
eClass
IDEA
4
4130
UNSPSC
15
39-12-10-04
Approvals Certificates
General Product Approval
Manufacturer Declaration
General Product Approval
Declaration of Conformity
For use in hazardous locations
Marine / Shipping
BIS CRS
Marine / Shipping
last modified:
6EP13343BA10
Page 4/4
CCC-Ex
Environment
5/7/2024
5/14/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP1334-3BA10”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+1987.06635
- 5+1934.36315
- 国内价格
- 1+2849.44793
- 5+2494.37654