Data sheet
6EP1334-2AA01-0AB0
SITOP SMART/1AC/24VDC/10A/WALL MOUNTING
SITOP smart 240 W Stabilized
power supply input: 120/230 V
AC, output: DC 24 V/10 A Option
for for wall mounting
Input
Input
● Note
1-phase AC
Set by means of selector switch on the device
supply voltage
● 1 at AC rated value
120 V
● 2 at AC rated value
230 V
input voltage
● 1 at AC
85 ... 132 V
● 2 at AC
170 ... 264 V
Wide-range input
No
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
Mains buffering
at Vin = 93/187 V
Mains buffering at Iout rated, min.
20 ms; at Vin = 93/187 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
input current
● at rated input voltage 120 V
4.1 A
● at rated input voltage 230 V
2.4 A
Switch-on current limiting (+25 °C), max.
65 A
duration of inrush current limiting at 25 °C
● typical
3 ms
I²t, max.
3.3 A²·s
Built-in incoming fuse
T 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.5 %
Residual ripple peak-peak, max.
150 mV
Residual ripple peak-peak, typ.
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
240 mV
6EP13342AA010AB0
Page 1/2
1.14.2021
Subject to change without notice
© Copyright Siemens
Spikes peak-peak, typ. (bandwidth: 20 MHz)
150 mV
Adjustment range
22.8 ... 28 V
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer
Status display
Green LED for 24 V OK
On/off behavior
Overshoot of Vout approx. 4 %
Startup delay, max.
0.1 s
Voltage rise, typ.
50 ms
Rated current value Iout rated
10 A
Current range
0 ... 12 A
● Note
supplied active power typical
12 A up to +45 °C
288 W
short-term overload current
● on short-circuiting during the start-up typical
30 A
● at short-circuit during operation typical
33 A
duration of overloading capability for excess current
● on short-circuiting during the start-up
100 ms
● at short-circuit during operation
200 ms
Parallel switching for enhanced performance
Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
90 %
Power loss at Vout rated, Iout rated, approx.
27 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.
0.3 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
1%
Load step setting time 50 to 100%, typ.
0.2 ms
Load step setting time 100 to 50%, typ.
0.2 ms
Protection and monitoring
Output overvoltage protection
< 33 V
Current limitation
12.5 ... 13.5 A
property of the output short-circuit proof
Yes
Short-circuit protection
Constant current characteristic
enduring short circuit current RMS value
● typical
Overload/short-circuit indicator
16 A
-
Safety
Primary/secondary isolation
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class
Class I
leakage current
● maximum
3.5 mA
● typical
0.8 mA
Degree of protection (EN 60529)
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection
-
certificate of suitability NEC Class 2
No
FM approval
-
CB approval
Yes
Marine approval
-
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
-
Noise immunity
EN 61000-6-2
environmental conditions
6EP13342AA010AB0
Page 2/3
1.14.2021
Subject to change without notice
© Copyright Siemens
ambient temperature
● during operation
— Note
0 ... 60 °C
with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technology
screw-type terminals
Connections
● Supply input
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely
stranded
● Output
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
● Auxiliary
-
width of the enclosure
70 mm
height of the enclosure
125 mm
depth of the enclosure
125 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
Weight, approx.
0.85 kg
product feature of the enclosure housing can be lined up
Yes
Installation
Wall mounting
MTBF at 40 °C
1 460 803 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP13342AA010AB0
Page 3/3
1.14.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP13342AA010AB0”相匹配的价格&库存,您可以联系我们找货