Data sheet
6EP1436-2BA10
SITOP PSU300S/3AC/24VDC/20A
SITOP PSU300S 20 A stabilized power supply input: 400-500 V 3 AC output: 24 V
DC/20 A
input
type of the power supply network
3-phase AC
supply voltage at AC
● minimum rated value
400 V
● maximum rated value
500 V
● initial value
340 V
● full-scale value
550 V
wide range input
Yes
buffering time for rated value of the output current in the event of
power failure minimum
6 ms
operating condition of the mains buffering
at Vin = 400 V
line frequency
50/60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 400 V
1.2 A
● at rated input voltage 500 V
1A
current limitation of inrush current at 25 °C maximum
36 A
I2t value maximum
0.9 A²·s
fuse protection type
none
fuse protection type in the feeder
Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C
or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489listed, DIVQ)
output
voltage curve at output
Controlled, isolated DC voltage
output voltage at DC rated value
24 V
output voltage
● at output 1 at DC rated value
24 V
output voltage adjustable
Yes; via potentiometer
adjustable output voltage
24 ... 28 V; max. 480 W
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.5 %
● on slow fluctuation of ohm loading
1%
residual ripple
● maximum
150 mV
voltage peak
● maximum
240 mV
display version for normal operation
Green LED for 24 V OK
type of signal at output
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on
No overshoot of Vout (soft start)
response delay maximum
1.5 s
voltage increase time of the output voltage
6EP14362BA10
Page 1/5
5/18/2024
Subject to change without notice
© Copyright Siemens
● typical
30 ms
● maximum
500 ms
output current
● rated value
20 A
● rated range
0 ... 20 A
supplied active power typical
480 W
short-term overload current
● on short-circuiting during the start-up typical
35 A
● at short-circuit during operation typical
35 A
duration of overloading capability for excess current
● on short-circuiting during the start-up
100 ms
● at short-circuit during operation
100 ms
bridging of equipment
Yes
number of parallel-switched equipment resources for increasing
the power
2
efficiency
efficiency in percent
91 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
47 W
closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
3%
relative control precision of the output voltage load step of
resistive load 50/100/50 % typical
3%
setting time
● load step 50 to 100% typical
2 ms
● load step 100 to 50% typical
2 ms
relative control precision of the output voltage at load step of
resistive load 10/90/10 % typical
3%
setting time
● load step 10 to 90% typical
2 ms
● load step 90 to 10% typical
2 ms
● maximum
10 ms
protection and monitoring
design of the overvoltage protection
protection against overvoltage in case of internal fault Vout < 35 V
property of the output short-circuit proof
Yes
design of short-circuit protection
Electronic shutdown, automatic restart
● typical
25.5 A
overcurrent overload capability
● in normal operation
overload capability 150 % Iout rated up to 5 s/min
enduring short circuit current RMS value
● maximum
7A
safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra-low output voltage Vout acc. to EN 60950-1 and EN 50178,
transformer acc. to EN 61558-2-16
operating resource protection class
Class I
leakage current
● maximum
3.5 mA
● typical
1 mA
protection class IP
IP20
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
EN 61000-3-2
● for interference immunity
EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
6EP14362BA10
Page 2/5
5/18/2024
Subject to change without notice
© Copyright Siemens
(CSA C22.2 No. 60950-1, UL 60950-1)
● EAC approval
Yes
● NEC Class 2
No
● SEMI F47
Yes
type of certification
● BIS
Yes; R-41183539
● CB-certificate
Yes
MTBF at 40 °C
500 000 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx
No
● ATEX
No
● ULhazloc approval
No
● cCSAus, Class 1, Division 2
No
● FM registration
No
standards, specifications, approvals marine classification
shipbuilding approval
Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● French marine classification society (BV)
No
● Det Norske Veritas (DNV)
Yes
● Lloyds Register of Shipping (LRS)
No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration
Yes
Global Warming Potential [CO2 eq]
● total
1 500 kg
● during manufacturing
31.6 kg
● during operation
1 470 kg
● after end of life
0.48 kg
ambient conditions
ambient temperature
● during operation
-25 ... +60 °C; with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection
screw terminal
● at input
L1, L2, L3, PE: 1 screw terminal each for 0.5 ... 4 mm² single-core/finely
stranded
● at output
+, -: 2 screw terminals each for 0.2 ... 4 mm²
● for auxiliary contacts
13, 14 (alarm signal): 1 screw terminal each for 0.05 ... 2.5 mm²
mechanical data
width × height × depth of the enclosure
90 × 150
installation width × mounting height
90 mm
required spacing
● top
40 mm
● bottom
40 mm
● left
0 mm
● right
0 mm
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15
● standard rail mounting
Yes
● S7 rail mounting
No
● wall mounting
No
housing can be lined up
Yes
net weight
1.6 kg
accessories
electrical accessories
Redundancy module, buffer module, selectivity module, DC UPS
mechanical accessories
Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20
further information internet links
internet link
6EP14362BA10
Page 3/5
5/18/2024
Subject to change without notice
© Copyright Siemens
● to website: Industry Mall
https://mall.industry.siemens.com
● to web page: selection aid TIA Selection Tool
https://siemens.com/tst
● to website: Industrial communication
http://www.siemens.com/simatic-net
● to website: CAx-Download-Manager
http://www.siemens.com/cax
● to website: Industry Online Support
https://support.industry.siemens.com
additional information
other information
Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information
Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)
Classifications
Version
Classification
eClass
14
27-04-07-01
eClass
12
27-04-07-01
eClass
9.1
27-04-07-01
eClass
9
27-04-07-01
eClass
8
27-04-90-02
eClass
7.1
27-04-90-02
eClass
6
27-04-90-02
ETIM
9
EC002540
ETIM
8
EC002540
ETIM
7
EC002540
IDEA
4
4130
UNSPSC
15
39-12-10-04
Approvals Certificates
General Product Approval
Manufacturer Declaration
General Product Approval
Declaration of Conformity
For use in hazardous locations
Marine / Shipping
BIS CRS
Marine / Shipping
6EP14362BA10
Page 4/5
CCC-Ex
Environment
5/18/2024
Subject to change without notice
© Copyright Siemens
last modified:
6EP14362BA10
Page 5/5
5/18/2024
5/18/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP1436-2BA10”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+2154.85418
- 5+2097.73110