Data sheet
6EP1437-3BA00-8AA0
SITOP MODULAR/3AC/24VDC/40A/CO
SITOP modular plus 40 A
Stabilized power supply input: 3
AC 400-500 V output: 24 V
DC/40 A Option for with
protective varnish
Input
Input
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
Voltage range AC
320 ... 550 V
● Note
Starting from Vin > 340 V
Wide-range input
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
Mains buffering
at Vin = 400 V
Mains buffering at Iout rated, min.
6 ms; at Vin = 400 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
input current
● at rated input voltage 400 V
2.2 A
Switch-on current limiting (+25 °C), max.
70 A
I²t, max.
2.8 A²·s
Built-in incoming fuse
none
Protection in the mains power input (IEC 898)
Required: 3-pole connected miniature circuit breaker 10 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
200 mV
Adjustment range
24 ... 28.8 V
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer; max. 960 W
Status display
Green LED for 24 V OK
Signaling
via signaling module (6EP1961-3BA10)
6EP14373BA008AA0
Page 1/2
1.14.2021
Subject to change without notice
© Copyright Siemens
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
voltage increase time of the output voltage maximum
500 ms
Rated current value Iout rated
40 A
Current range
0 ... 40 A
● Note
supplied active power typical
+60 ... +70 °C: Derating 2%/K
960 W
short-term overload current
● at short-circuit during operation typical
120 A
duration of overloading capability for excess current
● at short-circuit during operation
25 ms
constant overload current
● on short-circuiting during the start-up typical
46 A
Parallel switching for enhanced performance
Yes; switchable characteristic
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
90 %
Power loss at Vout rated, Iout rated, approx.
106 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.
1%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
2%
Load step setting time 50 to 100%, typ.
4 ms
Load step setting time 100 to 50%, typ.
4 ms
setting time maximum
10 ms
Protection and monitoring
Output overvoltage protection
< 35 V
Current limitation, typ.
46 A
property of the output short-circuit proof
Yes
Short-circuit protection
Alternatively, constant current characteristic approx. 46 A or latching
shutdown
enduring short circuit current RMS value
● typical
Overload/short-circuit indicator
46 A
LED yellow for "overload", LED red for "latching shutdown"
Safety
Primary/secondary isolation
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class
Class I
leakage current
● maximum
Degree of protection (EN 60529)
3.5 mA
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
UL-Listed (UL 508), File E197259, CSA (CSA C22.2 No. 14, CSA C22.2
No. 107.1)
Explosion protection
-
certificate of suitability NEC Class 2
No
FM approval
-
CB approval
No
Marine approval
-
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
— Note
6EP14373BA008AA0
Page 2/3
0 ... 70 °C
with natural convection
1.14.2021
Subject to change without notice
© Copyright Siemens
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technology
screw-type terminals
Connections
● Supply input
L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely
stranded
● Output
+, -: 2 screw terminals each for 0.33 ... 10 mm²
● Auxiliary
-
width of the enclosure
240 mm
height of the enclosure
125 mm
depth of the enclosure
125 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
Weight, approx.
3.2 kg
product feature of the enclosure housing can be lined up
Yes
Installation
Snaps onto DIN rail EN 60715 35x15
electrical accessories
Buffer module, signaling module
MTBF at 40 °C
485 437 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP14373BA008AA0
Page 3/3
1.14.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP14373BA008AA0”相匹配的价格&库存,您可以联系我们找货