Data sheet
6EP1935-6MD31
SITOP BATTERY MODULE/24V/2.5AH
SITOP pure lead battery module 24 V/2.5 Ah with maintenance-free sealed
lead batteries for SITOP DC UPS module 6 A and 15 A *Ex approval no
longer available*
Charging current charging voltage
end-of-charge voltage at DC
● at -10 °C recommended
29 V
● at 0 °C recommended
28.6 V
● at 10 °C recommended
28.3 V
● at 20 °C recommended
27.9 V
● at 30 °C recommended
27.5 V
● at 40 °C recommended
27.2 V
● at 50 °C recommended
26.8 V
● at 60 °C recommended
26.4 V
Output
charging current maximum
5A
output voltage at DC rated value
24 V
Safety
design of short-circuit protection
Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support)
design of the overload protection
Valve control
Safety
operating resource protection class
Class III
protection class IP
IP00
Approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes
● as approval for USA
cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
● cCSAus, Class 1, Division 2
No
● ATEX
No
certificate of suitability
● EAC approval
Yes
● shipbuilding approval
Yes
shipbuilding approval
ABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● DNV GL
Yes
environmental conditions
Operating data note
For storage, mounting and operation of lead-acid batteries, the relevant
DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part
2/EN 50272-2) must be observed. You must ensure that the battery site
is sufficiently ventilated. Possible sources of ignition must be at least 50
cm away.
ambient temperature
6EP19356MD31
Page 1/2
7/8/2022
Subject to change without notice
© Copyright Siemens
● during operation
-40 ... +60 °C
● during transport
-40 ... +60 °C
● during storage
-40 ... +60 °C
relative temporary capacity loss at 20 °C in a month
typical
3%
Service life
service life of energy storage
● typical
capacity falls to 80 % of original capacity (according to EUROBAT)
● at 20 °C typical
10 y
● at 30 °C typical
7y
● at 40 °C typical
3y
● at 50 °C typical
1.5 y
● at 60 °C typical
1y
ambient temperature during storage
Along with the storage and operating temperature, other factors such as
the duration of the storage period and the charge status during storage
have a decisive influence on the possible useful life. Batteries should
therefore be stored as briefly as possible, always fully charged, and
within the temperature range 0 to +20 °C.
Mechanics
type of electrical connection
● for power supply unit
spring-loaded terminals
1 screw terminal each for 0.08 ... 2.5 mm² for + BAT and - BAT
product component included
Accessories pack with solid-state circuitry fuse 15 A
width of the enclosure
265 mm
height of the enclosure
151 mm
depth of the enclosure
91 mm
installation width
285 mm
mounting height
171 mm
fastening method
● wall mounting
Yes
● standard rail mounting
Yes
● S7 rail mounting
No
fastening method
snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in
to M4 screws
net weight
3.8 kg
number of cells
12
battery capacity
2.5 A·h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP19356MD31
Page 2/2
7/8/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP19356MD31”相匹配的价格&库存,您可以联系我们找货