Data sheet
6EP3324-7SB00-3AX0
SITOP PSU6200/1AC/12VDC/12A
SITOP PSU6200 12 V/12 A Stabilized power supply Input: 120 - 230 V AC,
(120 - 240 V DC) Output: 12 V DC/12 A with diagnostics interface
Input
type of the power supply network
1-phase AC or DC
supply voltage at AC
● minimum rated value
120 V
● maximum rated value
230 V
● initial value
85 V
● full-scale value
264 V
supply voltage
● at DC
110 ... 240 V
input voltage
● at DC
85 ... 275 V
design of input wide range input
Yes
overvoltage overload capability
300 V AC for 30 s
operating condition of the mains buffering
at Vin = 230 V
buffering time for rated value of the output current in the
event of power failure minimum
70 ms
operating condition of the mains buffering
at Vin = 230 V
line frequency
● 1 rated value
50 Hz
● 2 rated value
60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 120 V
1.4 A
● at rated input voltage 230 V
0.8 A
current limitation of inrush current at 25 °C maximum
6A
fuse protection type
5A
● in the feeder
Circuit breaker from 4 A characteristic C/6 A characteristic B to 10 A
characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or
3RV2711-1ED10 (UL 489)
Output
voltage curve at output
Controlled, isolated DC voltage
number of outputs
1
output voltage at DC rated value
12 V
output voltage
● at output 1 at DC rated value
12 V
relative overall tolerance of the voltage
3%
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
residual ripple
6EP33247SB003AX0
Page 1/3
7/5/2022
Subject to change without notice
© Copyright Siemens
● maximum
30 mV
● typical
20 mV
voltage peak
● maximum
30 mV
● typical
20 mV
adjustable output voltage
12 ... 15.5 V
product function output voltage adjustable
Yes
type of output voltage setting
via potentiometer; max. 144 W (173 W up to 45°C)
display version for normal operation
Green LED for 24 V OK
type of signal at output
Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC
O.K. or diagnostic interface
behavior of the output voltage when switching on
Overshoot of Vout < 2 %
response delay maximum
0.5 s
voltage increase time of the output voltage
● typical
100 ms
output current
● rated value
12 A
● rated range
0 ... 12 A; 14.4 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical
144 W
short-term overload current
● on short-circuiting during the start-up typical
14.4 A
● at short-circuit during operation typical
14.4 A
product feature
● bridging of equipment
number of parallel-switched equipment resources for
increasing the power
Yes; switchable characteristic
2
Efficiency
efficiency in percent
89.3 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
17 W
● during no-load operation maximum
3W
Closed-loop control
relative control precision of the output voltage at load step
of resistive load 10/90/10 % typical
3%
setting time
● load step 10 to 90% typical
2 ms
● load step 90 to 10% typical
2 ms
● maximum
3 ms
Protection and monitoring
design of the overvoltage protection
< 20 V
response value current limitation typical
14.4 A
property of the output short-circuit proof
Yes
design of short-circuit protection
Shutdown and periodic restart attempts
overcurrent overload capability in normal operation
overload capability 150 % Iout rated up to 5 s/min
Safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra low output voltage Vout according to EN 60950-1
operating resource protection class
Class I
leakage current
● maximum
protection class IP
3.5 mA
IP20
Approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● cCSAus, Class 1, Division 2
No
● ATEX
No
6EP33247SB003AX0
Page 2/3
7/5/2022
Subject to change without notice
© Copyright Siemens
certificate of suitability
● IECEx
No
● NEC Class 2
No
● ULhazloc approval
No
● FM registration
No
type of certification CB-certificate
Yes
certificate of suitability
● EAC approval
Yes
● C-Tick
No
● Regulatory Compliance Mark (RCM)
No
certificate of suitability shipbuilding approval
Yes
shipbuilding approval
in process: DNV GL, ABS
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
No
● French marine classification society (BV)
No
● DNV GL
No
● Lloyds Register of Shipping (LRS)
No
● Nippon Kaiji Kyokai (NK)
No
EMC
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
EN 61000-3-2
● for interference immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
-30 ... +70 °C; with natural convection a monotonically increasing startup from -25 °C, safe start-up from -40 °C
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection
Push-in terminals
● at input
L1/+, L2/N/-, PE:PushIn for 0.5 ... 4 mm² single-core/finely stranded
● at output
+1, +2, -1, -2, -3: PushIn for 0.5 ... 2.5 mm²
● for auxiliary contacts
13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm²
width of the enclosure
45 mm
height of the enclosure
135 mm
depth of the enclosure
125 mm
required spacing
● top
45 mm
● bottom
45 mm
● left
0 mm
● right
0 mm
net weight
0.9 kg
product feature of the enclosure housing can be lined up
Yes
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15
electrical accessories
Redundancy module
mechanical accessories
Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0
other information
Specifications at rated input voltage and ambient temperature +25 °C