Data sheet
6EP3330-6SB00-0AY0
LOGO!Power/1AC/24VDC/0.6A
LOGO!POWER 24 V / 0.6 A stabilized power supply input: 100-240 V AC output:
24 V DC/ 0.6 A
input
type of the power supply network
1-phase AC or DC
supply voltage at AC
● minimum rated value
100 V
● maximum rated value
240 V
● initial value
85 V
● full-scale value
264 V
input voltage at DC
110 ... 300 V
wide range input
Yes
overvoltage overload capability
300 V AC for 1 s
buffering time for rated value of the output current in the event of
power failure minimum
40 ms
operating condition of the mains buffering
at Vin = 187 V
line frequency
50/60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 120 V
0.3 A
● at rated input voltage 230 V
0.2 A
current limitation of inrush current at 25 °C maximum
20 A
I2t value maximum
0.8 A²·s
fuse protection type
internal
fuse protection type in the feeder
Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A
characteristic C
output
voltage curve at output
Controlled, isolated DC voltage
output voltage at DC rated value
24 V
output voltage
● at output 1 at DC rated value
output voltage adjustable
24 V
No
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
residual ripple
● maximum
200 mV
● typical
30 mV
voltage peak
● maximum
300 mV
● typical
50 mV
display version for normal operation
Green LED for output voltage OK
behavior of the output voltage when switching on
No overshoot of Vout (soft start)
6EP33306SB000AY0
Page 1/4
5/18/2024
Subject to change without notice
© Copyright Siemens
response delay maximum
0.5 s
voltage increase time of the output voltage
● typical
100 ms
output current
● rated value
0.6 A
● rated range
0 ... 0.6 A; +55 ... +70 °C: Derating 2%/K
supplied active power typical
14.4 W
bridging of equipment
No
efficiency
efficiency in percent
81 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
3.4 W
● during no-load operation maximum
0.3 W
closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
0.2 %
relative control precision of the output voltage at load step of
resistive load 10/90/10 % typical
2%
setting time
● load step 10 to 90% typical
1 ms
● load step 90 to 10% typical
1 ms
protection and monitoring
design of the overvoltage protection
Yes, according to EN 60950-1
property of the output short-circuit proof
Yes
design of short-circuit protection
Constant current characteristic
● typical
0.8 A
overcurrent overload capability
● when switching on
150% Iout rated typ. 200 ms
● in normal operation
overload capability 150% Iout rated typ. 200 ms
enduring short circuit current RMS value
● maximum
measuring point for output current
0.8 A
No
safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class
Class II (without protective conductor)
protection class IP
IP20
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
not applicable
● for interference immunity
EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURusRecognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURusRecognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
● EAC approval
Yes
● NEC Class 2
Yes; according to UL1310, File E151273
● SEMI F47
Yes
type of certification
● CB-certificate
MTBF at 40 °C
Yes
4 415 040 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx
No
● ATEX
No
● ULhazloc approval
No
6EP33306SB000AY0
Page 2/4
5/18/2024
Subject to change without notice
© Copyright Siemens
● cCSAus, Class 1, Division 2
No
● FM registration
No
standards, specifications, approvals marine classification
shipbuilding approval
Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● French marine classification society (BV)
Yes
● Det Norske Veritas (DNV)
Yes
● Lloyds Register of Shipping (LRS)
Yes
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration
Yes
Global Warming Potential [CO2 eq]
● total
107.9 kg
● during manufacturing
1.4 kg
● during operation
106.5 kg
● after end of life
0.04 kg
ambient conditions
ambient temperature
● during operation
-25 ... +70 °C; with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection
screw terminal
● at input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
● at output
+, -: 1 screw terminal each for 0.5 ... 2.5 mm²
● for auxiliary contacts
-
mechanical data
width × height × depth of the enclosure
18 × 53
installation width × mounting height
18 mm
required spacing
● top
20 mm
● bottom
20 mm
● left
0 mm
● right
0 mm
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting
positions
● standard rail mounting
Yes
● S7 rail mounting
No
● wall mounting
Yes
housing can be lined up
Yes
net weight
0.07 kg
further information internet links
internet link
● to website: Industry Mall
https://mall.industry.siemens.com
additional information
other information
Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information
6EP33306SB000AY0
Page 3/4
Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
5/18/2024
Subject to change without notice
© Copyright Siemens
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)
Classifications
Version
Classification
eClass
14
27-04-07-01
eClass
12
27-04-07-01
eClass
9.1
27-04-07-01
eClass
9
27-04-07-01
eClass
8
27-04-90-02
eClass
7.1
27-04-90-02
eClass
6
27-04-90-02
ETIM
9
EC002540
ETIM
8
EC002540
ETIM
7
EC002540
IDEA
4
4130
UNSPSC
15
39-12-10-04
Approvals Certificates
General Product Approval
Manufacturer Declaration
General Product Approval
For use in hazardous locations
Marine / Shipping
FM
Marine / Shipping
last modified:
6EP33306SB000AY0
Page 4/4
Declaration of Conformity
CCC-Ex
Environment
5/18/2024
5/18/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP3330-6SB00-0AY0”相匹配的价格&库存,您可以联系我们找货