Data sheet
6EP3343-0SA00-0AY0
SITOP PSU3600 FLEXI/1AC/3-52VDC/10A/120W
SITOP PSU3600 flexi Stabilized
power supply Input: 120-230 V
AC Output: 3-52 V DC/10 A, 120
W
Input
Input
1-phase AC or DC
Rated voltage value Vin rated
120 ... 230 V
Voltage range AC
85 ... 264 V
● Note
Derating at < 110 V AC/DC: output power max. 100 W
supply voltage
● at DC
110 ... 220 V
input voltage
● at DC
88 ... 250 V
Wide-range input
Yes
Mains buffering
With Pa = 120 W and Ue = 230 V AC
Mains buffering at Iout rated, min.
80 ms; With Pa = 120 W and Ue = 230 V AC
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
input current
● at rated input voltage 120 V
2.6 A
● at rated input voltage 230 V
1.3 A
● at rated input voltage 110 V
1.3 A
● at rated input voltage 220 V
0.7 A
Switch-on current limiting (+25 °C), max.
35 A
I²t, max.
1 A²·s
Built-in incoming fuse
T 3.15 A (not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: 6-10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24 V
● Output voltage
3-52 V DC
Total tolerance, static ±
1%
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
1%
Sense line connection max. voltage control per line
0.5 V
Residual ripple peak-peak, max.
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
100 mV
6EP33430SA000AY0
Page 1/2
12.17.2020
Subject to change without notice
© Copyright Siemens
Adjustment range
0 ... 52 V
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer (setting range 3 to 52 V) or analog control voltage
signal 0 to 2.5 V (setting range 0 to 52 V)
Status display
Two-color LED: green for 24 V o.k., red for overload
Signaling
DC OK via relay contact, current monitor signal (0 to 2.5 V correspond
to 0 to 10 A)
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
0.5 s
Voltage rise, typ.
20 ms
Rated current value Iout rated
10 A
Current range
0 ... 10 A
● Note
supplied active power typical
Output power max. 120 W
120 W
constant overload current
● on short-circuiting during the start-up typical
12 A
● at short-circuit during operation typical
12 A
Parallel switching for enhanced performance
Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
88 %
Power loss at Vout rated, Iout rated, approx.
16 W
power loss [W] during no-load operation maximum
3W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.
0.3 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
5%
setting time maximum
0.2 ms
Protection and monitoring
Output overvoltage protection
≤ 60 V according to EN 60950-1
Current limitation
2 ... 10 A
Current limitation
Can be set with potentiometer or analog control voltage signal 0.5 ... 2.5
V
property of the output short-circuit proof
Yes
Short-circuit protection
Electronic current limiting (2 ... 10 A) in the range 3 ... 12 V or power
limiting (120 W) in the range 12 ... 52 V
enduring short circuit current RMS value
● maximum
12 A
Safety
Primary/secondary isolation
Yes
galvanic isolation
Safety extra low output voltage Vout according to EN 60950-1
Protection class
Class I
leakage current
● maximum
Degree of protection (EN 60529)
3.5 mA
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection
-
certificate of suitability NEC Class 2
No
FM approval
-
CB approval
Yes
Marine approval
-
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
environmental conditions
ambient temperature
6EP33430SA000AY0
Page 2/3
12.17.2020
Subject to change without notice
© Copyright Siemens
● during operation
— Note
-25 ... +70 °C
Derating > 60°C: 2%/°K
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technology
screw-type terminals
Connections
● Supply input
L1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely
stranded
● Output
+, -: 2 screw terminals each for 0.5 ... 2.5 mm² single-core/finely
stranded
● Auxiliary
Alarm signals, control inputs: screw-type terminals for 0.14 ... 1.5 mm²
single-core/finely stranded
width of the enclosure
42 mm
height of the enclosure
125 mm
depth of the enclosure
135 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
Weight, approx.
0.55 kg
product feature of the enclosure housing can be lined up
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C
1 200 000 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP33430SA000AY0
Page 3/3
12.17.2020
Subject to change without notice
© Copyright Siemens