Data sheet
6EP3436-8MB00-2CY0
SITOP PSU8600/3AC/24VDC/20A/4X5A PN
SITOP PSU8600 3AC 20A/4x5A
PN Stabilized power supply
Input: 400-500 V 3 AC output: 24
V DC/20 A/4x 5 A with PN/IE
connection Integrated web server
OPC UA server integrated
Input
Input
3-phase AC
Rated voltage value Vin rated
400 ... 500 V
Voltage range AC
320 ... 575 V
● Note
Derating 320 … 360 and 530 … 575 V
Wide-range input
Yes
Mains buffering
at Vin = 400 V; Prioritized supply Output 1 at power failure can be
selected via DIP switch
Mains buffering at Iout rated, min.
15 ms; at Vin = 400 V; Prioritized supply Output 1 at power failure can
be selected via DIP switch
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
input current
● at rated input voltage 400 V
1.4 A
● at rated input voltage 500 V
1.1 A
Switch-on current limiting (+25 °C), max.
14 A
I²t, max.
1.2 A²·s
Built-in incoming fuse
none
Protection in the mains power input (IEC 898)
Required: 3-pole connected miniature circuit breaker 6 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Output
Controlled, isolated DC voltage
number of outputs
4
Rated voltage Vout DC
24 V
● output voltage at output 1 at DC rated value
24 V
● output voltage at output 2 at DC rated value
24 V
● output voltage at output 3 at DC rated value
24 V
● output voltage at output 4 at DC rated value
24 V
Total tolerance, static ±
3%
Static mains compensation, approx.
0.2 %
Static load balancing, approx.
0.1 %
6EP34368MB002CY0
Page 1/2
1.14.2021
Subject to change without notice
© Copyright Siemens
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
200 mV
Adjustment range
4 ... 28 V
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer or IE/PN interface; Derating > 24 V: 4%/V; max. 120
W per output, max. 480 W overall system
Status display
3-color LED for operating state device; LED for operating mode
manual/remote; 4 LEDs for communication PROFINET; 3-color LED per
output for operating state output; LED green for parallel operation
Output 1 and 2 / 3 and 4
Signaling
Relay contact (changeover contact, contact current capacity DC 60
V/0.3 A) for "Operating state OK"
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
1 s; Without on-delay of the outputs
connection of outputs operating
Simultaneous connecting-in of all outputs after device booting or delay
time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the
outputs via DIP switches can be set
voltage increase time of the output voltage maximum
500 ms
Rated current value Iout rated
20 A
output current
● per output
5A
● at output 1 rated value
5A
● at output 2 rated value
5A
● at output 3 rated value
5A
● at output 4 rated value
5A
Current range
● Note
0 ... 20 A
+50 ... +60 °C: Derating 2.5%/K; no derating in connection with
expansion module CNX8600 and total load of the outputs at the basic
device max. 240 W
supplied active power typical
480 W
product feature parallel switching of outputs
Yes; Parallel circuit Output 1 with 2 or Output 3 with 4 can be selected
via DIP switch
Parallel switching for enhanced performance
No
Efficiency
Efficiency at Vout rated, Iout rated, approx.
93 %
Power loss at Vout rated, Iout rated, approx.
34 W
power loss [W] during no-load operation maximum
12 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.
0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
0.4 %
setting time maximum
10 ms
Protection and monitoring
Output overvoltage protection
< 35 V
property of the output short-circuit proof
Yes
Short-circuit protection
electronic overload cut-off; optionally constant current operation can be
selected for Output 4 via DIP switches
adjustable response value current of current-dependent
overload trip
0.5 ... 5 A
type of threshold value setting
via potentiometer or IE/PN interface
characteristics of electronic overload switch-off
Ia >1.0… 15 V)
overcurrent overload capability in normal operation
Total system overloadable 150% Ia rated to 5 s/min
Overload/short-circuit indicator
3-color LED for operating state device; 3-color LED per output for
operating state output
Interface
Specification interface
Ethernet/PROFINET
Safety
6EP34368MB002CY0
Page 2/3
1.14.2021
Subject to change without notice
© Copyright Siemens
Primary/secondary isolation
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class
Class I
leakage current
● maximum
Degree of protection (EN 60529)
3.5 mA
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc;
cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2,
Group ABCD, T4
certificate of suitability NEC Class 2
No
FM approval
-
CB approval
Yes
Marine approval
ABS, DNV GL
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
— Note
-25 ... +60 °C
with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
Connection technology
Plug-in terminals with screwed connection
Connections
● Supply input
L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.2
... 4 mm² single-wire / fine stranded
● Output
1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) with 2 screwed
connections each for 0.2 ... 2.5 mm²; 0 V: Plug-in terminal with 3
screwed connections for 0.2 ... 4 mm²
● Auxiliary
RST (Reset): Plug-in terminal (together with alarm signal) with 1
screwed connection for 0.2 ... 1.5 mm²
● signaling contact
11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1
screwed connection each for 0.2 ... 1.5 mm²
product function
● removable terminal at input
Yes
● removable terminal at output
Yes
design of the interface for communication
PROFINET/Ethernet: two RJ45 sockets (2-port switch)
suitability for interaction modular system
Yes
width of the enclosure
100 mm
height of the enclosure
125 mm
depth of the enclosure
150 mm
required spacing
● top
50 mm
● bottom
50 mm
● left
0 mm
● right
0 mm
Weight, approx.
2 kg
product feature of the enclosure housing can be lined up
Yes
Installation
Snaps onto DIN rail EN 60715 35x15
electrical accessories
Expansion modules CNX8600, buffer modules BUF8600, module
UPS8600
mechanical accessories
Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C
243 178 h
6EP34368MB002CY0
Page 3/4
1.14.2021
Subject to change without notice
© Copyright Siemens
other information
6EP34368MB002CY0
Page 4/4
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
1.14.2021
Subject to change without notice
© Copyright Siemens