Data sheet
6EP4437-7EB00-3CX0
SITOP SEL1400/4X2-10A
SITOP SEL1400 10 A Selectivity module 4-channel with limiting
characteristic input: 24 V DC/40 A output: 24 V DC/4x 10 A threshold
adjustable 2-10 A with monitoring interface *Ex approval no longer
available*
Input
type of the power supply network
Controlled DC voltage
supply voltage at DC rated value
24 V
input voltage at DC
20.4 ... 30 V
overvoltage overload capability
35 V
input current at rated input voltage 24 V rated value
40 A
Output
voltage curve at output
controlled DC voltage
formula for output voltage
Vin - approx. 0.2 V
relative overall tolerance of the voltage note
In accordance with the supplying input voltage
number of outputs
4
output current up to 60 °C per output rated value
10 A
adjustable current response value current of the currentdependent overload release
2 ... 10 A
type of response value setting
via potentiometer
product feature parallel switching of outputs
Yes
type of outputs connection
Connection of all outputs after ramp-up of the supply voltage > 20 V;
delay time of 25 ms, 200 ms, 500 ms or "load-optimized" can be set via
DIP switch for sequential connection
Efficiency
efficiency in percent
98 %
power loss [W] at rated output voltage for rated value of
the output current typical
10 W
Switch-off characteristic per output
switching characteristic
● of the excess current
Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s
● of the current limitation
Iout = 1.5 x set value, switch-off after typ. 100 ms
● of the immediate switch-off
Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
design of the reset device/resetting mechanism
via sensor per output
remote reset function
Non-electrically isolated 24 V input (signal level "high" at > 15 V)
Protection and monitoring
fuse protection type at input
15 A per output (not accessible)
display version for normal operation
Three-color LED per output: green LED for "Output switched through";
yellow LED for "Output switched off manually"; red LED for "Output
switched off due to overcurrent"
design of the switching contact for signaling function
Floating common signal contact or status signal output (pulse/pause
signal that can be evaluated via SIMATIC function block)
Safety
galvanic isolation between input and output at switch-off
No
standard for safety
according to EN 60950-1 and EN 50178
6EP44377EB003CX0
Page 1/2
7/4/2022
Subject to change without notice
© Copyright Siemens
operating resource protection class
Class III
protection class IP
IP20
Approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508,
CSA C22.2 No. 107.1) File E197259
● CSA approval
Yes; CSA 22.2 60950-1
● ATEX
No
certificate of suitability
● IECEx
type of certification CB-certificate
No
Yes
certificate of suitability
● EAC approval
Yes
EMC
standard
● for emitted interference
EN 61000-6-3
● for interference immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
-25 ... +70 °C; with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection
Push-in
● at input
24V1, 24V2: push-in for 0.5 ... 16 mm²; 0V1, 0V2: push-in for 0.5 ... 4
mm²
● at output
1 - 4: push-in for 0.5 ... 4 mm²
● for signaling contact
13, 14: push-in for 0.2 ... 1.5 mm²
● for auxiliary contacts
RST: push-in for 0.2 ... 1.5 mm²
width of the enclosure
45 mm
height of the enclosure
135 mm
depth of the enclosure
125 mm
installation width
45 mm
mounting height
225 mm
required spacing
● top
45 mm
● bottom
45 mm
● left
0 mm
● right
0 mm
net weight
0.3 kg
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP44377EB003CX0
Page 2/2
7/4/2022
Subject to change without notice
© Copyright Siemens