Data sheet
6ES7132-6HD01-0BB1
SIMATIC ET 200SP, Relay module, RQ NO 4x 120V DC..230VAC/5A ST. 4
normally open contacts, isolated contacts, packing unit: 1 piece, fits to BU-type B0
and B1, Colour Code CC40, substitute value output, module diagnostics for: supply
voltage
General information
Product type designation
RQ 4x120 VDC ... 230 VAC/5 A NO ST
HW functional status
From FS02
Firmware version
V0.0
● FW update possible
No
usable BaseUnits
BU type B0, B1
Color code for module-specific color identification plate
CC40
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V14
● STEP 7 configurable/integrated from version
V5.5 SP3
● PCS 7 configurable/integrated from version
V8.1 SP1
● PROFIBUS from GSD version/GSD revision
One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision
GSDML V2.3
Operating mode
● DQ
Yes
● DQ with energy-saving function
No
● PWM
No
● Oversampling
No
● MSO
No
Redundancy
● Redundancy capability
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption (rated value)
55 mA; without load
output voltage / header
Rated value (AC)
230 V
Power loss
Power loss, typ.
1.5 W
Address area
Address space per module
● Inputs
+ 1 byte for QI information
● Outputs
1 byte
Hardware configuration
6ES71326HD010BB1
Page 1/3
5/22/2024
Subject to change without notice
© Copyright Siemens
Automatic encoding
Yes
● Mechanical coding element
Yes
● Type of mechanical coding element
type C
Selection of BaseUnit for connection variants
● 2-wire connection
BU type B1
● 3-wire connection
BU type B0
Digital outputs
Type of digital output
Relays
Number of digital outputs
4
Current-sinking
Yes
Current-sourcing
Yes
Digital outputs, parameterizable
Yes
Short-circuit protection
No
Parallel switching of two outputs
● for logic links
Yes
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
2 Hz
● with inductive load (acc. to IEC 60947-5-1, DC13), max.
0.5 Hz
● with inductive load (acc. to IEC 60947-5-1, AC15), max.
0.5 Hz
● on lamp load, max.
2 Hz
Total current of the outputs
● Current per channel, max.
5A
● Current per module, max.
20 A
Total current of the outputs (per module)
horizontal installation
— up to 50 °C, max.
20 A
— up to 60 °C, max.
16 A
vertical installation
— up to 40 °C, max.
20 A
— up to 50 °C, max.
16 A
Relay outputs
● Number of relay outputs
4
● Rated supply voltage of relay coil L+ (DC)
24 V
● Current consumption of relays (coil current of all relays),
max.
40 mA
● external protection for relay outputs
Yes, with miniature fuse max. 6 A tripping current and quick-response tripping
characteristic
● Number of operating cycles, max.
7 000 000; see additional description in the manual
Switching capacity of contacts
— with inductive load, max.
2 A; see additional description in the manual
— with resistive load, max.
5 A; see additional description in the manual
— Thermal continuous current, max.
5 A; Max. 1 385 VA, 150 W
— Switching current, min.
100 mA; 5 V DC
— Rated switching voltage (DC)
24 V DC to 120 V DC
— Rated switching voltage (AC)
24V AC to 230V AC
Cable length
● shielded, max.
1 000 m
● unshielded, max.
200 m
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
No
● Short-circuit
No
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
6ES71326HD010BB1
Page 2/3
Yes; green PWR LED
5/22/2024
Subject to change without notice
© Copyright Siemens
● Channel status display
Yes; green LED
● for channel diagnostics
No
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
Yes
● between the channels and backplane bus
Yes
● between the channels and the power supply of the
electronics
Yes
Permissible potential difference
between channels and backplane bus/supply voltage
240 V AC
Isolation
Isolation tested with
2 500 V DC (type test)
tested with
● between channels and backplane bus/supply voltage
2 500 V DC
● between backplane bus and supply voltage
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions
No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C
● vertical installation, max.
50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
2 000 m; On request: Installation altitudes greater than 2 000 m
Dimensions
Width
20 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
40 g
last modified:
5/22/2024
6ES71326HD010BB1
Page 3/3
5/22/2024
Subject to change without notice
© Copyright Siemens