Data sheet
6ES7132-6BH01-0BA0
SIMATIC ET 200SP, Digital output module, DQ 16x 24V DC/0,5A
Standard, Source output (PNP,P-switching) Packing unit: 1 piece, fits to
BU-type A0, Colour Code CC00, substitute value output, module
diagnostics for: short-circuit to L+ and ground, wire break, supply voltage
General information
Product type designation
DQ 16x24VDC/0.5A ST
HW functional status
From FS03
Firmware version
V0.0
● FW update possible
No
usable BaseUnits
BU type A0
Color code for module-specific color identification plate
CC00
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
V14
● STEP 7 configurable/integrated from version
V5.5 SP3
● PCS 7 configurable/integrated from version
V8.1 SP1
● PROFIBUS from GSD version/GSD revision
One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision
GSDML V2.3
Operating mode
● DQ
Yes
● DQ with energy-saving function
No
● PWM
No
● Oversampling
No
● MSO
No
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption, max.
60 mA; without load
output voltage / header
Rated value (DC)
24 V
Power loss
Power loss, typ.
1W
Address area
Address space per module
● Address space per module, max.
2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding
6ES71326BH010BA0
Page 1/3
Yes
7/8/2022
Subject to change without notice
© Copyright Siemens
● Mechanical coding element
Yes
● Type of mechanical coding element
Type A
Selection of BaseUnit for connection variants
● 1-wire connection
BU type A0
● 2-wire connection
BU type A0 + Potential distributor module
● 3-wire connection
BU type A0 + Potential distributor module
● 4-wire connection
BU type A0 + Potential distributor module
Digital outputs
Type of digital output
Source output (PNP, current-sourcing)
Number of digital outputs
16
Current-sinking
No
Current-sourcing
Yes
Digital outputs, parameterizable
Yes
Short-circuit protection
Yes
● Response threshold, typ.
1 A; 0.7 to 1.3 A
Open-circuit detection
Yes
Limitation of inductive shutdown voltage to
Typ. L+ (-50 V)
Controlling a digital input
Yes
Switching capacity of the outputs
● with resistive load, max.
0.5 A
● on lamp load, max.
5W
Load resistance range
● lower limit
48 Ω
● upper limit
12 kΩ
Output current
● for signal "1" rated value
0.5 A
● for signal "0" residual current, max.
0.1 mA
Output delay with resistive load
● "0" to "1", typ.
50 µs
● "1" to "0", typ.
100 µs
Parallel switching of two outputs
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
100 Hz
● with inductive load, max.
2 Hz
● on lamp load, max.
10 Hz
Total current of the outputs
● Current per channel, max.
0.5 A
● Current per module, max.
8A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max.
8A
— up to 50 °C, max.
6A
— up to 60 °C, max.
4A
vertical installation
— up to 30 °C, max.
8A
— up to 40 °C, max.
6A
— up to 50 °C, max.
4A
Cable length
● shielded, max.
1 000 m
● unshielded, max.
600 m
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
Yes; Module-wise
6ES71326BH010BA0
Page 2/3
7/8/2022
Subject to change without notice
© Copyright Siemens
● Short-circuit to M
Yes; Module-wise
● Short-circuit to L+
Yes; Module-wise
● Group error
Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
● Channel status display
Yes; green LED
● for channel diagnostics
No
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions
No
Suitable for safety-related tripping of standard modules
Yes; see FAQ Entry ID: 39198632
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1
PL d
● SIL acc. to IEC 61508
SIL 2
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C; < 0 °C as of FS03
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C; < 0 °C as of FS03
● vertical installation, max.
50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width
15 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
30 g