Data sheet
6ES7132-6FD00-0CU0
SIMATIC ET 200SP, digital output module DQ 4x 24..230V AC/2A HF
packaging unit: 1 piece, two alternative modes: DQ and power control, fits
to BU-Type U0, color code CC20, channel diagnosis
General information
Product type designation
DQ 4x24 ... 230 V AC/2 A HF, PU 1
HW functional status
From FS03
Firmware version
● FW update possible
usable BaseUnits
Yes
BU type U0
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
V14
● STEP 7 configurable/integrated from version
STEP 7 V5.5 or higher
● PROFIBUS from GSD version/GSD revision
GSD as of Revision 5
● PROFINET from GSD version/GSD revision
GSDML V2.3
Operating mode
● DQ
Yes
● DQ with energy-saving function
Yes
● PWM
No
● Oversampling
No
● MSO
No
● Phase control
Yes
● Trailing-edge phase
No
● Half-wave
Yes
● Full-wave
Yes
Supply voltage
Rated value (AC)
230 V
permissible range, lower limit (AC)
20.4 V
permissible range, upper limit (AC)
264 V
Input current
Current consumption (rated value)
8 mA
Output voltage
Rated value (AC)
230 V; 24V AC to 230V AC
Power loss
Power loss, typ.
9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50
Hz
Address area
Address space per module
6ES71326FD000CU0
Page 1/2
12.20.2020
Subject to change without notice
© Copyright Siemens
● Inputs
+ 1 byte for QI information
● Outputs
8 byte
Hardware configuration
Automatic encoding
● Mechanical coding element
Yes
Yes
Selection of BaseUnit for connection variants
● 1-wire connection
BU type U0
● 2-wire connection
BU type U0
● 3-wire connection
BU type U0 + Potential distributor module
Digital outputs
Number of digital outputs
4
Current-sinking
No
Current-sourcing
Yes
Digital outputs, parameterizable
Yes
Short-circuit protection
No; external fusing necessary
Open-circuit detection
Yes; channel by channel
● Response threshold, typ.
1 mA; 40 V AC or more
Overload protection
No; A miniature fuse with 10 tripping current and tripping characteristic
"quick response" must be provided in the module supply
Controlling a digital input
Yes
Switching capacity of the outputs
● with resistive load, max.
2 A; Max. 4 A, see additional description in manual
● with inductive load, max.
2A
● on lamp load, max.
100 W; Tungsten rating in accordance with UL; for thermistors with
higher power ratings, see the notes in the manual
Output voltage
● for signal "1", min.
20.4 V
Output current
● for signal "1" rated value
2A
● for signal "1" permissible range, min.
10 mA
● for signal "1" permissible range, max.
4 A; note derating data in the manual
● for signal "0" residual current, max.
3 mA
Output delay with resistive load
● "0" to "1", max.
40 ms; 2 AC cycles
● "1" to "0", max.
20 ms; 1 AC cycle
Parallel switching of two outputs
● for logic links
No
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
10 Hz; Applies to DQ mode; limited by line frequency in PC mode
● with inductive load (acc. to IEC 60947-5-1, AC15),
max.
10 Hz; Applies to DQ mode; limited by line frequency in PC mode
● on lamp load, max.
1 Hz; Applies to DQ mode; limited by line frequency in PC mode
Total current of the outputs
● Current per channel, max.
2 A; Max. 4 A, see additional description in manual
● Current per module, max.
8A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max.
8A
— up to 50 °C, max.
6A
— up to 60 °C, max.
4A
vertical installation
— up to 30 °C, max.
8A
— up to 40 °C, max.
6A
— up to 50 °C, max.
4A
Cable length
● shielded, max.
1 000 m
● unshielded, max.
600 m
6ES71326FD000CU0
Page 2/3
12.20.2020
Subject to change without notice
© Copyright Siemens
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Diagnostic information readable
Yes
● Monitoring the supply voltage
Yes
● Wire-break
Yes; channel by channel
● Short-circuit
No
● Group error
Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
● Channel status display
Yes; green LED
● for channel diagnostics
Yes; red Fn LED
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
● between the channels and the power supply of the
electronics
No
Isolation
Isolation tested with
2 545 V DC/2 s (routine test)
Standards, approvals, certificates
Suitable for safety functions
No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C
● vertical installation, max.
50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
2 000 m; On request: Installation altitudes greater than 2 000 m
Dimensions
Width
20 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
50 g