Data sheet
6ES7136-6AA00-0CA1
SIMATIC DP, electronic module ET 200SP, F-AI 4xI0(4)..20 mA HF fail-safe
analog inputs up to PL e (ISO 13849) up to SIL 3 (IEC 61508)
General information
Product type designation
F-AI 4xI 0(4)..20mA 2-/4-wire HF
Firmware version
● FW update possible
Yes
usable BaseUnits
BU type A0, A1
Color code for module-specific color identification plate
CC00
Product function
● I&M data
Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V15 with HSP 203
CiR - Configuration in RUN
Reparameterization possible in RUN
No
Calibration possible in RUN
No
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
power supply according to NEC Class 2 required
No
Input current
Current consumption (rated value)
0.38 A
Current consumption, max.
0.4 A
Encoder supply
24 V encoder supply
● 24 V
Yes; min. L+ (-1.5 V)
● Short-circuit protection
Yes
● Output current, max.
300 mA; total current of all encoders/channels
Power
Power available from the backplane bus
70 mW
Power loss
Power loss, typ.
2W
Address area
Address space per module
● Inputs
14 byte; S7-300/400F CPU, 13 byte
● Outputs
5 byte; S7-300/400F CPU, 4 byte
Hardware configuration
Automatic encoding
● Electronic coding element type F
Yes
Yes
Analog inputs
Number of analog inputs
6ES71366AA000CA1
Page 1/3
4
5/15/2024
Subject to change without notice
© Copyright Siemens
● For current measurement
permissible input current for current input (destruction limit),
max.
4
35 mA
Input ranges (rated values), currents
● 0 to 20 mA
— Input resistance (0 to 20 mA)
● 4 mA to 20 mA
— Input resistance (4 mA to 20 mA)
Yes
125 Ω
Yes
125 Ω
Cable length
● shielded, max.
1 000 m
Analog value generation for the inputs
Measurement principle
Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
16 bit
● Integration time, parameterizable
Yes
● Integration time (ms)
20 / 16,667
● Interference voltage suppression for interference
frequency f1 in Hz
50 / 60 Hz
Smoothing of measured values
● Number of smoothing levels
7
● parameterizable
Yes
● Step: None
Yes; 1x conversion cycle time
● Step: low
Yes; 2x / 4x conversion cycle time
● Step: Medium
Yes; 8x / 16x conversion cycle time
● Step: High
Yes; 32x / 64x conversion cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max.
● for current measurement as 4-wire transducer
Yes
650 Ω
Yes
Errors/accuracies
Linearity error (relative to input range), (+/-)
0.1 %
Temperature error (relative to input range), (+/-)
0.023 %/K
Repeat accuracy in steady state at 25 °C (relative to input
range), (+/-)
0.1 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-)
2%
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-)
0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference <
rated value of input range), min.
40 dB
● Common mode interference, min.
70 dB
Interrupts/diagnostics/status information
Diagnostics function
Yes
Alarms
● Diagnostic alarm
Yes
● Limit value alarm
No
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
Yes
● Short-circuit
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
● Channel status display
Yes; green LED
● for channel diagnostics
Yes; red LED
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
6ES71366AA000CA1
Page 2/3
No
5/15/2024
Subject to change without notice
© Copyright Siemens
● between the channels and backplane bus
Yes
● between the channels and the power supply of the
electronics
Yes
Permissible potential difference
between the inputs (UCM)
10 Vpp
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1
PLe
● Category according to ISO 13849-1
Cat. 4
● SIL acc. to IEC 61508
SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with
SIL3
< 5.00E-05
— High demand/continuous mode: PFH in accordance
with SIL3
< 1.00E-09 1/h
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
0 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
0 °C
● vertical installation, max.
50 °C
Dimensions
Width
15 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
48 g
last modified:
4/25/2024
6ES71366AA000CA1
Page 3/3
5/15/2024
Subject to change without notice
© Copyright Siemens
6ES7136-6AA00-0CA1. 价格&库存
很抱歉,暂时无法提供与“6ES7136-6AA00-0CA1.”相匹配的价格&库存,您可以联系我们找货
免费人工找货