Data sheet
6ES7142-5AF00-0BA0
SIMATIC ET 200AL, DQ 8x 24 V DC/2 A, 8x M12, Degree of protection
IP67
General information
Product type designation
DQ 8x24VDC/2A
HW functional status
FS03
Firmware version
V1.0.x
Product function
● I&M data
Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
STEP 7 V13 SP1 or higher
● STEP 7 configurable/integrated from version
V5.5 SP4 Hotfix 7 or higher
● PROFIBUS from GSD version/GSD revision
GSD as of Revision 5
● PROFINET from GSD version/GSD revision
GSDML V2.3.1
Supply voltage
power supply according to NEC Class 2 required
No
Load voltage 1L+
● Rated value (DC)
24 V
● permissible range, lower limit (DC)
20.4 V
● permissible range, upper limit (DC)
28.8 V
● Reverse polarity protection
Yes; against destruction; load increasing
Load voltage 2L+
● Rated value (DC)
24 V
● permissible range, lower limit (DC)
20.4 V
● permissible range, upper limit (DC)
28.8 V
● Reverse polarity protection
Yes; against destruction; load increasing
Input current
Current consumption (rated value)
40 mA; without load
from load voltage 1L+ (unswitched voltage)
4 A; Maximum value
from load voltage 2L+, max.
4 A; Maximum value
Power loss
Power loss, typ.
4W
Digital outputs
Number of digital outputs
● in groups of
Short-circuit protection
● Response threshold, typ.
Limitation of inductive shutdown voltage to
8
4; 2 load groups for 4 outputs each
Yes; per channel, electronic
2.8 A
2L+ (-47 V)
Switching capacity of the outputs
● on lamp load, max.
10 W
Load resistance range
6ES71425AF000BA0
Page 1/3
7/9/2022
Subject to change without notice
© Copyright Siemens
● lower limit
12 Ω
● upper limit
4 kΩ
Output voltage
● for signal "1", min.
L+ (-0.8 V)
Output current
● for signal "1" rated value
2A
● for signal "1" permissible range, max.
2 A; with inductive load to IEC 60947-5-1, DC-13 / AC-15
● for signal "0" residual current, max.
0.5 mA
Switching frequency
● with resistive load, max.
100 Hz
● with inductive load, max.
0.1 Hz; 0.25 Hz at 25 °C
● on lamp load, max.
1 Hz
Total current of the outputs
● Current per group, max.
4 A; For inductive load max. 2 channels per group
Cable length
● unshielded, max.
30 m
Interrupts/diagnostics/status information
Substitute values connectable
Yes; channel by channel, parameterizable
Alarms
● Diagnostic alarm
Yes; Parameterizable
Diagnoses
● Short-circuit
Yes; Outputs to ground; module by module
Diagnostics indication LED
● Channel status display
Yes; green LED
● for module diagnostics
Yes; green/red LED
● For load voltage monitoring
Yes; green LED
Potential separation
between the load voltages
Yes
Potential separation channels
● between the channels, in groups of
4
● between the channels and backplane bus
Yes
● between the channels and the power supply of the
electronics
No; 4 channels are non-isolated and 4 channels are isolated from
supply voltage 1L+
Isolation
Isolation tested with
707 V DC (type test)
Degree and class of protection
IP degree of protection
IP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules
Yes; From FS01
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SIL acc. to IEC 62061
SIL 2
Ambient conditions
Ambient temperature during operation
● min.
-30 °C
● max.
55 °C
connection method / header
Design of electrical connection for the inputs and outputs
M12, 5-pole
Design of electrical connection for supply voltage
M8, 4-pole
ET-Connection
● ET-Connection
M8, 4-pin, shielded
Dimensions
Width
45 mm
Height
159 mm
Depth
40 mm
Weights
Weight, approx.
192 g
last modified:
3/7/2022
6ES71425AF000BA0
Page 2/3
7/9/2022
Subject to change without notice
© Copyright Siemens
6ES71425AF000BA0
Page 3/3
7/9/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6ES71425AF000BA0”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+3224.094681+399.94745
- 10+2833.7490010+351.52525
- 25+2749.5906125+341.08544