Data sheet
6ES7142-6BG00-0AB0
SIMATIC DP, ET 200ECO PN, 8 DO 24 V DC/1.3 A; 8xM12, Degree of
protection IP67
Supply voltage
Rated value (DC)
24 V
Reverse polarity protection
Yes
Load voltage 1L+
● Rated value (DC)
24 V
● permissible range, lower limit (DC)
20.4 V
● permissible range, upper limit (DC)
28.8 V
● Reverse polarity protection
Yes
Load voltage 2L+
● Rated value (DC)
24 V
● permissible range, lower limit (DC)
20.4 V
● permissible range, upper limit (DC)
28.8 V
● Reverse polarity protection
Yes
Input current
Current consumption, typ.
100 mA
from supply voltage 1L+, max.
4A
from load voltage 1L+ (unswitched voltage)
4A
from load voltage 2L+, max.
4A
Power loss
Power loss, typ.
5.5 W
Digital outputs
Number of digital outputs
● in groups of
Short-circuit protection
● Response threshold, typ.
8
4
Yes
1.8 A
Limitation of inductive shutdown voltage to
Typ. (L1+, L2+) -47 V
Controlling a digital input
Yes
Switching capacity of the outputs
● on lamp load, max.
5W
Output current
● for signal "1" rated value
1.3 A; Maximum
● for signal "0" residual current, max.
1.5 mA
Parallel switching of two outputs
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
6ES71426BG000AB0
Page 1/2
1.19.2021
Subject to change without notice
© Copyright Siemens
● with resistive load, max.
100 Hz
● with inductive load, max.
0.5 Hz
● on lamp load, max.
1 Hz
Total current of the outputs (per group)
all mounting positions
— up to 60 °C, max.
3.9 A
Cable length
● unshielded, max.
30 m
Interfaces
Transmission procedure
100BASE-TX
Number of PROFINET interfaces
1
1. Interface
Interface types
● integrated switch
Yes
Interface types
M12 port
● Autonegotiation
Yes
● Autocrossing
Yes
● Transmission rate, max.
100 Mbit/s
Protocols
Supports protocol for PROFINET IO
Yes
PROFINET CBA
No
PROFIsafe
No
PROFINET IO Device
Services
— IRT with the option "high flexibility"
Yes
— Prioritized startup
Yes
Redundancy mode
Media redundancy
— MRP
Yes
Open IE communication
● TCP/IP
No
● SNMP
Yes
● DCP
Yes
● LLDP
Yes
● ping
Yes
● ARP
Yes
Interrupts/diagnostics/status information
Diagnostics function
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Diagnostic information readable
Yes
● Monitoring the supply voltage
Yes; green "ON" LED
● Wire-break in actuator cable
Yes
● Short-circuit
Yes
● Group error
Yes; Red/yellow "SF/MT" LED
Potential separation
between the load voltages
Yes
between load voltage and all other switching components
No
between Ethernet and electronics
Yes
Potential separation channels
● between the channels
No
Isolation
tested with
● 24 V DC circuits
707 V DC (type test)
● Test voltage for interface, rms value [Vrms]
1 500 V; According to IEEE 802.3
6ES71426BG000AB0
Page 2/3
1.19.2021
Subject to change without notice
© Copyright Siemens
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules
Yes
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SILCL according to IEC 62061
SILCL 2
Connection method
Design of electrical connection
4/5-pin M12 circular connectors
Dimensions
Width
60 mm
Height
175 mm
Depth
49 mm
Weights
Weight, approx.
910 g
last modified:
12/19/2020
6ES71426BG000AB0
Page 3/3
1.19.2021
Subject to change without notice
© Copyright Siemens