Data sheet
6ES7144-4GF01-0AB0
SIMATIC DP, Electronic module for ET 200 PRO 4 AI I High Feature, +-20
mA; 0...20 mA; 4-20mA; Channel diagnostics; incl. bus module, Connection
module IO 6ES7194-4..00-0AA0 order separately
Supply voltage
Rated value (DC)
24 V
Reverse polarity protection
Yes; against destruction
Input current
from supply voltage 1L+, max.
40 mA; Typical
from backplane bus 3.3 V DC, max.
12 mA; Typical
Encoder supply
Number of outputs
4
Short-circuit protection
Yes; per module, electronic to frame
Output current
● up to 55 °C, max.
1A
Power loss
Power loss, typ.
1.1 W
Address area
Address space per module
● Address space per module, max.
8 byte
Analog inputs
Number of analog inputs
4
permissible input current for current input (destruction
limit), max.
40 mA
Cycle time (all channels) max.
10 ms
Input ranges (rated values), currents
● 0 to 20 mA
— Input resistance (0 to 20 mA)
● -20 mA to +20 mA
— Input resistance (-20 mA to +20 mA)
● 4 mA to 20 mA
— Input resistance (4 mA to 20 mA)
Yes
50 Ω
Yes
50 Ω
Yes
50 Ω
Cable length
● shielded, max.
30 m
Analog value generation for the inputs
Measurement principle
integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
15 bit; 15 bit + sign at ±10 V, at ±5 V; 15 bit at 0 V to 10 V, at 1 V to 5 V
● Integration time (ms)
0,3 / 16,7 / 20 / 60
● Interference voltage suppression for interference
frequency f1 in Hz
16,67 / 50 / 60 / 3 600
6ES71444GF010AB0
Page 1/2
1.19.2021
Subject to change without notice
© Copyright Siemens
● Conversion time (per channel)
1.1 ms
Smoothing of measured values
● parameterizable
Yes
● Step: None
Yes; 1x cycle time
● Step: low
Yes; 4x cycle time
● Step: Medium
Yes; 16x cycle time
● Step: High
Yes; 64x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
Yes
● for current measurement as 4-wire transducer
Yes
Errors/accuracies
Linearity error (relative to input range), (+/-)
0.0075 %
Temperature error (relative to input range), (+/-)
0.00075 %/K
Crosstalk between the inputs, min.
-70 dB
Repeat accuracy in steady state at 25 °C (relative to input
range), (+/-)
0.004 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-)
0.1 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-)
0.075 %
Interference voltage suppression for f = n x (f1 +/- 0.5 %), f1 = interference frequency
● Series mode interference (peak value of
interference < rated value of input range), min.
60 dB
● Common mode interference (USS < 2.5 V), min.
80 dB; Interference voltage < 5 V
Interrupts/diagnostics/status information
Diagnostics function
Yes
Alarms
● Diagnostic alarm
Yes; Parameterizable
● Hardware interrupt
Yes; (limit value alarm), can be parameterized for channel 0
Diagnoses
● Diagnostic information readable
Yes
● Wire-break
Yes; at 4 to 20 mA
● Short-circuit
Yes; at 4 to 20 mA
Diagnostics indication LED
● Group error SF (red)
Yes
Potential separation
Potential separation analog inputs
● between the channels
No
● between the channels and backplane bus
Yes
Permissible potential difference
Between the inputs and MANA (UCM)
5 Vpp AC
Isolation
Isolation tested with
707 V DC (type test)
Dimensions
Width
45 mm
Height
130 mm
Depth
35 mm
Weights
Weight, approx.
150 g