Data sheet
6ES7155-6AA01-0BN0
SIMATIC ET 200SP, PROFINET bundle IM, IM 155-6PN ST, max. 32 I/O modules
and 16 ET 200AL modules, single hot swap, bundle consists of: Interface module
(6ES7155-6AU01-0BN0), Server module (6ES7193-6PA00-0AA0), BusAdapter BA
2xRJ45 (6ES7193-6AR00-0AA0)
General information
Product type designation
IM155-6PN ST, including BusAdapter BA 2x RJ45
HW functional status
From FS03
Firmware version
V4.2
● FW update possible
Yes
Product function
● I&M data
Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping)
Yes; Single hot swapping
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V14
● STEP 7 configurable/integrated from version
V5.5 SP4
● PROFINET from GSD version/GSD revision
GSDML V2.35
Configuration control
via dataset
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Short-circuit protection
Yes
Mains buffering
● Mains/voltage failure stored energy time
10 ms
Input current
Current consumption (rated value)
450 mA
Current consumption, max.
550 mA
Inrush current, max.
3.7 A
I²t
0.09 A²·s
Power loss
Power loss, typ.
1.9 W
Address area
Address space per module
● Address space per module, max.
256 byte; For input and output data respectively
Address space per station
● Address space per station, max.
512 byte
Hardware configuration
Rack
● Quantity of operable ET 200SP modules, max.
32
● Quantity of operable ET 200AL modules, max.
16
6ES71556AA010BN0
Page 1/3
5/22/2024
Subject to change without notice
© Copyright Siemens
Submodules
● Number of submodules per station, max.
256
Interfaces
Number of PROFINET interfaces
1; 2 ports (switch)
1. Interface
Interface types
● RJ 45 (Ethernet)
Yes; with BusAdapter
● Number of ports
2; with BusAdapter
● integrated switch
Yes
● BusAdapter (PROFINET)
Yes
Protocols
● PROFINET IO Device
Yes
● Open IE communication
Yes
● Media redundancy
Yes; PROFINET MRP client
PROFINET IO Device
Services
— IRT
Yes; 250 µs to 4 ms in 125 µs frame
— PROFIenergy
Yes
— Prioritized startup
Yes
— Shared device
Yes
— Number of IO Controllers with shared device, max.
2
Interface types
RJ 45 (Ethernet)
● Transmission procedure
PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 100 Mbps
Yes
● Autonegotiation
Yes
● Autocrossing
Yes
Protocols
Modbus TCP
No
Redundancy mode
● PROFINET system redundancy (S2)
No
Media redundancy
— MRP
Yes
— MRPD
No
Open IE communication
● TCP/IP
Yes
● SNMP
Yes
● LLDP
Yes
Interrupts/diagnostics/status information
Status indicator
Yes
Alarms
Yes
Diagnostics function
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● MAINT LED
Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
● Connection display LINK TX/RX
Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics
No
between PROFINET and all other circuits
Yes; 1500 V AC (type test)
between supply and all other circuits
No
Permissible potential difference
between different circuits
Safety extra low voltage SELV
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Network loading class
2
Ambient conditions
Ambient temperature during operation
6ES71556AA010BN0
Page 2/3
5/22/2024
Subject to change without notice
© Copyright Siemens
● horizontal installation, min.
-30 °C; No condensation
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C; No condensation
● vertical installation, max.
50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
connection method
ET-Connection
● via BU/BA Send
Yes; + 16 ET 200AL modules
Dimensions
Width
50 mm
Height
117 mm
Depth
74 mm
Weights
Weight, approx.
147 g; without BusAdapter
last modified:
5/22/2024
6ES71556AA010BN0
Page 3/3
5/22/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6ES7155-6AA01-0BN0”相匹配的价格&库存,您可以联系我们找货