Data sheet
6ES7155-6AU01-0BN0
SIMATIC ET 200SP, PROFINET interface module IM 155-6PN Standard,
max. 32 I/O modules, and 16 ET 200AL modules, single hot swap, incl.
server module (6ES7193-6PA00-0AA0)
General information
Product type designation
IM 155-6 PN ST
HW functional status
From FS03
Product function
● I&M data
Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping)
Yes
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
V14
● STEP 7 configurable/integrated from version
V5.5 SP4 and higher
● PROFINET from GSD version/GSD revision
V2.3 / -
Configuration control
via dataset
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Short-circuit protection
Yes
Mains buffering
● Mains/voltage failure stored energy time
10 ms
Input current
Current consumption (rated value)
450 mA
Current consumption, max.
550 mA
Inrush current, max.
3.7 A
I²t
0.09 A²·s
Power
Infeed power to the backplane bus
4.5 W
Power loss
Power loss, typ.
1.9 W
Address area
Address space per module
● Address space per module, max.
256 byte; per input / output
Address space per station
● Address space per station, max.
512 byte; Dependent on configuration
Hardware configuration
6ES71556AU010BN0
Page 1/2
1.19.2021
Subject to change without notice
© Copyright Siemens
Rack
● Modules per rack, max.
32; + 16 ET 200AL modules
● Quantity of operable ET 200SP modules, max.
32
● Quantity of operable ET 200AL modules, max.
16
Submodules
● Number of submodules per station, max.
256
Interfaces
Number of PROFINET interfaces
1; 2 ports (switch)
1. Interface
Interface types
● Number of ports
2
● integrated switch
Yes
● BusAdapter (PROFINET)
Yes; compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x M12
Protocols
● PROFINET IO Device
Yes
● Open IE communication
Yes
● Media redundancy
Yes; PROFINET MRP
Interface types
RJ 45 (Ethernet)
● Transmission procedure
PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 10 Mbps
Yes; for Ethernet services
● 100 Mbps
Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● Autonegotiation
Yes
● Autocrossing
Yes
Protocols
PROFINET IO Device
Services
— IRT
Yes; with send cycles of between 250 µs and 4 ms in increments of 125
µs
— PROFIenergy
Yes
— Prioritized startup
Yes
— Shared device
Yes
— Number of IO Controllers with shared device,
max.
2
Redundancy mode
● PROFINET system redundancy (S2)
No
Media redundancy
— MRP
Yes
— MRPD
No
Open IE communication
● TCP/IP
Yes
● SNMP
Yes
● LLDP
Yes
Interrupts/diagnostics/status information
Status indicator
Yes
Alarms
Yes
Diagnostics function
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● MAINT LED
Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
● Connection display LINK TX/RX
Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics
No
between PROFINET and all other circuits
Yes
between supply and all other circuits
No
Permissible potential difference
6ES71556AU010BN0
Page 2/3
1.19.2021
Subject to change without notice
© Copyright Siemens
between different circuits
Safety extra low voltage SELV
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Security level
According to Security Level 1 Test Cases V1.1.1
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
0 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
0 °C
● vertical installation, max.
50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; On request: Installation altitudes greater than 2 000 m
Connection method
ET-Connection
● via BU/BA Send
Yes; + 16 ET 200AL modules
Dimensions
Width
50 mm
Height
117 mm
Depth
74 mm
Weights
Weight, approx.
147 g
last modified:
1/17/2021
6ES71556AU010BN0
Page 3/3
1.19.2021
Subject to change without notice
© Copyright Siemens