Data sheet
6ES7214-1AG40-0XB0
SIMATIC S7-1200, CPU 1214C, compact CPU, DC/DC/DC, onboard I/O: 14 DI 24
V DC; 10 DO 24 V DC; 2 AI 0-10 V DC, power supply: DC 20.4-28.8 V DC,
program/data memory 150 KB
General information
Product type designation
CPU 1214C DC/DC/DC
Firmware version
V4.6
Engineering with
● Programming package
STEP 7 V18 or higher
Supply voltage
Rated value (DC)
● 24 V DC
Yes
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Load voltage L+
● Rated value (DC)
24 V
● permissible range, lower limit (DC)
20.4 V
● permissible range, upper limit (DC)
28.8 V
Input current
Current consumption (rated value)
500 mA; CPU only
Current consumption, max.
1 500 mA; CPU with all expansion modules
Inrush current, max.
12 A; at 28.8 V
I²t
0.5 A²·s
Output current
for backplane bus (5 V DC), max.
1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V
L+ minus 4 V DC min.
Power loss
Power loss, typ.
12 W
Memory
Work memory
● integrated
150 kbyte
Load memory
● integrated
4 Mbyte
● Plug-in (SIMATIC Memory Card), max.
with SIMATIC memory card
Backup
● present
Yes
● maintenance-free
Yes
● without battery
Yes
CPU processing times
for bit operations, typ.
6ES72141AG400XB0
Page 1/7
0.08 µs; / instruction
5/9/2024
Subject to change without notice
© Copyright Siemens
for word operations, typ.
1.7 µs; / instruction
for floating point arithmetic, typ.
2.3 µs; / instruction
CPU-blocks
Number of blocks (total)
DBs, FCs, FBs, counters and timers. The maximum number of addressable
blocks ranges from 1 to 65535. There is no restriction, the entire working
memory can be used
OB
● Number, max.
Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.
14 kbyte
Flag
● Size, max.
8 kbyte; Size of bit memory address area
Local data
● per priority class, max.
16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB
Address area
Process image
● Inputs, adjustable
1 kbyte
● Outputs, adjustable
1 kbyte
Hardware configuration
Number of modules per system, max.
3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time)
Yes
● Backup time
480 h; Typical
● Deviation per day, max.
±60 s/month at 25 °C
Digital inputs
Number of digital inputs
● of which inputs usable for technological functions
Source/sink input
14; Integrated
6; HSC (High Speed Counting)
Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.
14
Input voltage
● Rated value (DC)
24 V
● for signal "0"
5 V DC at 1 mA
● for signal "1"
15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in
groups of four
— at "0" to "1", min.
0.2 ms
— at "0" to "1", max.
12.8 ms
for interrupt inputs
— parameterizable
Yes
for technological functions
— parameterizable
Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30
kHz
Cable length
● shielded, max.
500 m; 50 m for technological functions
● unshielded, max.
300 m; for technological functions: No
Digital outputs
Number of digital outputs
● of which high-speed outputs
Limitation of inductive shutdown voltage to
10
4; 100 kHz Pulse Train Output
L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max.
0.5 A
● on lamp load, max.
5W
Output voltage
● for signal "0", max.
0.1 V; with 10 kOhm load
● for signal "1", min.
20 V
Output current
6ES72141AG400XB0
Page 2/7
5/9/2024
Subject to change without notice
© Copyright Siemens
● for signal "1" rated value
0.5 A
● for signal "0" residual current, max.
0.1 mA
Output delay with resistive load
● "0" to "1", max.
1 µs
● "1" to "0", max.
5 µs
Switching frequency
● of the pulse outputs, with resistive load, max.
100 kHz
Relay outputs
● Number of relay outputs
0
Cable length
● shielded, max.
500 m
● unshielded, max.
150 m
Analog inputs
Number of analog inputs
2
Input ranges
● Voltage
Yes
Input ranges (rated values), voltages
● 0 to +10 V
— Input resistance (0 to 10 V)
Yes
≥100k ohms
Cable length
● shielded, max.
100 m; twisted and shielded
Analog outputs
Number of analog outputs
0
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
10 bit
● Integration time, parameterizable
Yes
● Conversion time (per channel)
625 µs
Encoder
Connectable encoders
● 2-wire sensor
Yes
1. Interface
Interface type
PROFINET
Isolated
Yes
automatic detection of transmission rate
Yes
Autonegotiation
Yes
Autocrossing
Yes
Interface types
● RJ 45 (Ethernet)
Yes
● Number of ports
1
● integrated switch
No
Protocols
● PROFINET IO Controller
Yes
● PROFINET IO Device
Yes
● SIMATIC communication
Yes
● Open IE communication
Yes; Optionally also encrypted
● Web server
Yes
● Media redundancy
No
PROFINET IO Controller
● Transmission rate, max.
100 Mbit/s
Services
— PG/OP communication
Yes; encryption with TLS V1.3 pre-selected
— Isochronous mode
No
— IRT
No
— PROFIenergy
No
— Prioritized startup
Yes
— Number of IO devices with prioritized startup, max.
16
— Number of connectable IO Devices, max.
16
— Number of connectable IO Devices for RT, max.
16
— of which in line, max.
16
6ES72141AG400XB0
Page 3/7
5/9/2024
Subject to change without notice
© Copyright Siemens
— Activation/deactivation of IO Devices
Yes
— Number of IO Devices that can be simultaneously
activated/deactivated, max.
8
— Updating time
The minimum value of the update time also depends on the communication
component set for PROFINET IO, on the number of IO devices and the quantity
of configured user data.
PROFINET IO Device
Services
— PG/OP communication
Yes; encryption with TLS V1.3 pre-selected
— Isochronous mode
No
— IRT
No
— PROFIenergy
Yes
— Shared device
Yes
— Number of IO Controllers with shared device, max.
2
Protocols
Supports protocol for PROFINET IO
Yes
PROFIsafe
No
PROFIBUS
Yes; CM 1243-5 (master) or CM 1242-5 (slave) required
OPC UA
Yes; OPC UA Server
AS-Interface
Yes; CM 1243-2 required
Protocols (Ethernet)
● TCP/IP
Yes
● DHCP
No
● SNMP
Yes
● DCP
Yes
● LLDP
Yes
Redundancy mode
Media redundancy
— MRP
No
— MRPD
No
SIMATIC communication
● S7 routing
Yes
Open IE communication
● TCP/IP
— Data length, max.
● ISO-on-TCP (RFC1006)
— Data length, max.
● UDP
— Data length, max.
Yes
8 kbyte
Yes
8 kbyte
Yes
1 472 byte
Web server
● supported
Yes
● User-defined websites
Yes
OPC UA
● Runtime license required
Yes; "Basic" license required
● OPC UA Server
Yes; data access (read, write, subscribe), method call, runtime license required
— Application authentication
Available security policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256
— User authentication
"anonymous" or by user name & password
— Number of sessions, max.
10
— Number of subscriptions per session, max.
5
— Sampling interval, min.
100 ms
— Publishing interval, min.
200 ms
— Number of server methods, max.
20
— Number of monitored items, recommended max.
1 000
— Number of server interfaces, max.
2
— Number of nodes for user-defined server interfaces,
max.
2 000
Further protocols
● MODBUS
Yes
communication functions / header
S7 communication
● supported
6ES72141AG400XB0
Page 4/7
Yes
5/9/2024
Subject to change without notice
© Copyright Siemens
● as server
Yes
● as client
Yes
● User data per job, max.
See online help (S7 communication, user data size)
Number of connections
● overall
PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max;
S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14
max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved
/ 10 max; Total Connections: 34 reserved / 64 max
Test commissioning functions
Status/control
● Status/control variable
Yes
● Variables
Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
● Forcing
Yes
Diagnostic buffer
● present
Yes
Traces
● Number of configurable Traces
2
● Memory size per trace, max.
512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED
Yes
● ERROR LED
Yes
● MAINT LED
Yes
Integrated Functions
Frequency measurement
Yes
controlled positioning
Yes
Number of position-controlled positioning axes, max.
8
Number of positioning axes via pulse-direction interface
4; With integrated outputs
PID controller
Yes
Number of alarm inputs
4
Number of pulse outputs
4
Limit frequency (pulse)
100 kHz
Potential separation
Potential separation digital inputs
● Potential separation digital inputs
No
● between the channels, in groups of
1
Potential separation digital outputs
● Potential separation digital outputs
Yes
● between the channels
No
● between the channels, in groups of
1
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static
electricity acc. to IEC 61000-4-2
Yes
— Test voltage at air discharge
8 kV
— Test voltage at contact discharge
6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 610004-4
Yes
● Interference immunity on signal cables acc. to IEC 610004-4
Yes
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to IEC 610004-5
Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency radiation
acc. to IEC 61000-4-6
Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas
Yes; Group 1
● Limit class B, for use in residential areas
Yes; When appropriate measures are used to ensure compliance with the limits
for Class B according to EN 55011
Degree and class of protection
6ES72141AG400XB0
Page 5/7
5/9/2024
Subject to change without notice
© Copyright Siemens
IP degree of protection
IP20
Standards, approvals, certificates
CE mark
Yes
UL approval
Yes
cULus
Yes
FM approval
Yes
RCM (formerly C-TICK)
Yes
KC approval
Yes
Marine approval
Yes
Ambient conditions
Free fall
● Fall height, max.
0.3 m; five times, in product package
Ambient temperature during operation
● min.
-20 °C
● max.
60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent
points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45
°C vertical
● horizontal installation, min.
-20 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-20 °C
● vertical installation, max.
50 °C
Ambient temperature during storage/transportation
● min.
-40 °C
● max.
70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min.
795 hPa
● Operation, max.
1 080 hPa
● Storage/transport, min.
660 hPa
● Storage/transport, max.
1 080 hPa
Altitude during operation relating to sea level
● Installation altitude, min.
-1 000 m
● Installation altitude, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
● Operation, max.
95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to IEC 600682-6
2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
● Operation, tested according to IEC 60068-2-6
Yes
Shock testing
● tested according to IEC 60068-2-27
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value),
duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
configuration / header
configuration / programming / header
Programming language
— LAD
Yes
— FBD
Yes
— SCL
Yes
Know-how protection
● User program protection/password protection
Yes
● Copy protection
Yes
● Block protection
Yes
Access protection
● protection of confidential configuration data
Yes
● Protection level: Write protection
Yes
● Protection level: Read/write protection
Yes
● Protection level: Complete protection
Yes
programming / cycle time monitoring / header
● adjustable
Yes
Dimensions
Width
6ES72141AG400XB0
Page 6/7
110 mm
5/9/2024
Subject to change without notice
© Copyright Siemens
Height
100 mm
Depth
75 mm
Weights
Weight, approx.
415 g
last modified:
3/12/2024
6ES72141AG400XB0
Page 7/7
5/9/2024
Subject to change without notice
© Copyright Siemens