0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
6ES7215-1HG40-0XB0

6ES7215-1HG40-0XB0

  • 厂商:

    SIEMENS

  • 封装:

  • 描述:

    SIEMENS - 6ES7215-1HG40-0XB0 - CPU, SIMATIC S7-1200 PLCs, 14 Digital Inputs, 2 Analogue Inputs, 10 R...

  • 数据手册
  • 价格&库存
6ES7215-1HG40-0XB0 数据手册
Data sheet 6ES7215-1HG40-0XB0 SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/RELAY, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 2A, 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4 28.8 V DC, PROGRAM/DATA MEMORY: 100 KB General information Engineering with ● Programming package STEP 7 V13 SP1 or higher Display with display No Supply voltage Rated value (DC) ● 24 V DC Yes permissible range, lower limit (DC) 20.4 V permissible range, upper limit (DC) 28.8 V Load voltage L+ ● Rated value (DC) 24 V ● permissible range, lower limit (DC) 5 V ● permissible range, upper limit (DC) 250 V Input current Current consumption (rated value) 500 mA Current consumption, max. 1 500 mA Inrush current, max. 12 A; at 28.8 V DC Encoder supply 24 V encoder supply ● 24 V L+ minus 4 V DC min. Power losses Power loss, typ. 6ES7215-1HG40-0XB0 Page 1/8 12 W 12.03.2015 Changes preserved © Copyright Siemens AG Memory Type of memory EEPROM Work memory ● Integrated 125 kbyte ● expandable No Load memory ● Integrated 4 Mbyte ● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card Backup ● present Yes; maintenance-free ● without battery Yes CPU processing times for bit operations, typ. 0.085 µs; / instruction for word operations, typ. 1.7 µs; / instruction for floating point arithmetic, typ. 2.5 µs; / instruction CPU-blocks Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used OB ● Number, max. Limited only by RAM for code Data areas and their retentivity retentive data area in total (incl. times, counters, flags), max. 10 kbyte Flag ● Number, max. 8 kbyte; Size of bit memory address area Process image ● Inputs, adjustable 1 kbyte ● Outputs, adjustable 1 kbyte Hardware configuration Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules Time of day Clock ● Hardware clock (real-time clock) Yes ● Deviation per day, max. +/- 60 s/month at 25 °C ● Backup time 480 h; Typical Digital inputs Number of digital inputs ● of which, inputs usable for technological functions 6ES7215-1HG40-0XB0 Page 2/8 14; Integrated 6; HSC (High Speed Counting) 12.03.2015 Changes preserved © Copyright Siemens AG integrated channels (DI) 14 m/p-reading Yes Number of simultaneously controllable inputs all mounting positions — up to 40 °C, max. 14 Input voltage ● Rated value (DC) 24 V ● for signal "0" 5 V DC at 1 mA ● for signal "1" 15 VDC at 2.5 mA Input current ● for signal "1", typ. 1 mA Input delay (for rated value of input voltage) for standard inputs — Parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four — at "0" to "1", min. 0.2 ms — at "0" to "1", max. 12.8 ms for interrupt inputs — Parameterizable Yes for counter/technological functions — Parameterizable Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz Cable length ● shielded, max. 500 m; 50 m for technological functions ● Unshielded, max. 300 m; For technological functions: No Digital outputs Number of digital outputs 10; Relays integrated channels (DO) 10 short-circuit protection No; to be provided externally Switching capacity of the outputs ● with resistive load, max. 2 A ● on lamp load, max. 30 W with DC, 200 W with AC Output delay with resistive load ● "0" to "1", max. 10 ms; max. ● "1" to "0", max. 10 ms; max. Switching frequency ● of the pulse outputs, with resistive load, max. 1 Hz Relay outputs ● Number of relay outputs, integrated 10 ● Number of relay outputs 10 ● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000 Cable length 6ES7215-1HG40-0XB0 Page 3/8 12.03.2015 Changes preserved © Copyright Siemens AG ● shielded, max. 500 m ● Unshielded, max. 150 m Analog inputs Number of analog inputs 2 Integrated channels (AI) 2; 0 to 10 V Input ranges ● Voltage Yes Input ranges (rated values), voltages ● 0 to +10 V Yes ● Input resistance (0 to 10 V) ≥100k ohms Cable length ● shielded, max. 100 m; twisted and shielded Analog outputs Number of analog outputs 2 Integrated channels (AO) 2; 0 to 20 mA Output ranges, current ● 0 to 20 mA Yes Cable length ● shielded, max. 100 m; shielded, twisted pair Analog value creation Integration and conversion time/resolution per channel ● Resolution with overrange (bit including sign), max. 10 bit ● Integration time, parameterizable Yes ● Conversion time (per channel) 625 µs Encoder Connectable encoders ● 2-wire sensor Yes 1st interface Interface type PROFINET Physics Ethernet Isolated Yes Automatic detection of transmission speed Yes Autonegotiation Yes Autocrossing Yes Functionality ● PROFINET IO Device Yes ● PROFINET IO Controller Yes PROFINET IO Controller ● Transmission rate, max. 6ES7215-1HG40-0XB0 Page 4/8 100 Mbit/s 12.03.2015 Changes preserved © Copyright Siemens AG ● Number of connectable IO devices, max. 16 ● Prioritized startup — Number of IO Devices, max. 16 PROFINET IO Device Services — Shared device Yes — Number of IO controllers with shared device, max. 2 Communication functions S7 communication ● supported Yes ● as server Yes ● As client Yes Open IE communication ● TCP/IP Yes ● ISO-on-TCP (RFC1006) Yes ● UDP Yes Web server ● supported Yes ● User-defined websites Yes Number of connections ● overall 16; dynamically Test commissioning functions Status/control ● Status/control variable Yes ● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters Forcing ● Forcing Yes Diagnostic buffer ● present Yes Traces ● Number of configurable Traces 2; Up to 512 KB of data per trace are possible Integrated Functions Number of counters 6 Counter frequency (counter) max. 100 kHz Frequency meter Yes controlled positioning Yes PID controller Yes Number of alarm inputs 4 Galvanic isolation 6ES7215-1HG40-0XB0 Page 5/8 12.03.2015 Changes preserved © Copyright Siemens AG Galvanic isolation digital inputs ● Galvanic isolation digital inputs 500V AC for 1 minute ● between the channels, in groups of 1 Galvanic isolation digital outputs ● Galvanic isolation digital outputs Relays ● between the channels No ● between the channels, in groups of 2 Permissible potential difference between different circuits 500 V DC between 24 V DC and 5 V DC EMC Interference immunity against discharge of static electricity ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes — Test voltage at air discharge 8 kV — Test voltage at contact discharge 6 kV Interference immunity to cable-borne interference ● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes ● Interference immunity on signal lines acc. to IEC 61000-4-4 Yes Surge immunity ● on the supply lines acc. to IEC 61000-4-5 Yes Immunity against conducted interference induced by high-frequency fields ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes Emission of radio interference acc. to EN 55 011 ● Limit class A, for use in industrial areas Yes; Group 1 ● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 Degree and class of protection Degree of protection to EN 60529 ● IP20 Yes Standards, approvals, certificates CE mark Yes UL approval Yes cULus Yes RCM (formerly C-TICK) Yes FM approval Yes Marine approval ● Marine approval Yes Ambient conditions 6ES7215-1HG40-0XB0 Page 6/8 12.03.2015 Changes preserved © Copyright Siemens AG Free fall ● Drop height, max. (in packaging) 0.3 m; five times, in dispatch package Ambient temperature in operation ● Min. -20 °C ● max. 60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical ● horizontal installation, min. -20 °C ● horizontal installation, max. 60 °C ● vertical installation, min. -20 °C ● vertical installation, max. 50 °C Storage/transport temperature ● Min. -40 °C ● max. 70 °C Air pressure acc. to IEC 60068-2-13 ● Storage/transport, min. 660 hPa ● Storage/transport, max. 1 080 hPa ● Permissible operating height -1000 to 2000 m Relative humidity ● Operation, max. 95 %; no condensation ● Permissible range (without condensation) at 25 °C 95 % Vibrations ● Vibrations 2G wall mounting, 1G DIN rail ● Operation, checked according to IEC 60068-26 Yes Shock test ● checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms Pollutant concentrations — SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free programming Programming language — LAD Yes — FBD Yes — SCL Yes Cycle time monitoring ● can be set Yes Dimensions Width 130 mm Height 100 mm Depth 75 mm 6ES7215-1HG40-0XB0 Page 7/8 12.03.2015 Changes preserved © Copyright Siemens AG Weights Weight, approx. 585 g last modified: 12.03.2015 6ES7215-1HG40-0XB0 Page 8/8 12.03.2015 Changes preserved © Copyright Siemens AG
6ES7215-1HG40-0XB0 价格&库存

很抱歉,暂时无法提供与“6ES7215-1HG40-0XB0”相匹配的价格&库存,您可以联系我们找货

免费人工找货
6ES7215-1HG40-0XB0
    •  国内价格
    • 1+8311.17366

    库存:1