Data sheet
6ES7231-5PD32-0XB0
SIMATIC S7-1200, ANALOG INPUT, SM 1231 RTD, 4 X AI RTD
MODULE
Supply voltage
Rated value (DC)
● 24 V DC
Yes
Input current
Current consumption, typ.
40 mA
from backplane bus 5 V DC, typ.
80 mA
Power loss
Power loss, typ.
1.5 W
Analog inputs
Number of analog inputs
4; Resistance thermometer
permissible input voltage for current input
(destruction limit), max.
± 35 V
Technical unit for temperature measurement
adjustable
Degrees Celsius/degrees Fahrenheit
Input ranges
● Voltage
No
● Current
No
● Thermocouple
No
6ES7231-5PD32-0XB0
Page 1/4
25.01.2016
Changes preserved
© Copyright Siemens AG
● Resistance thermometer
Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200,
Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50,
Cu100, LG-Ni1000
● Resistance
Yes; 150 Ω, 300 Ω, 600 Ω
Input ranges (rated values), resistance thermometer
● Cu 10
Yes
● Input resistance (Cu 10)
10 Ω
● Ni 100
Yes
● Input resistance (Ni 100)
100 Ω
● Ni 1000
Yes
● Input resistance (Ni 1000)
1 000 Ω
● LG-Ni 1000
Yes
● Input resistance (LG-Ni 1000)
1 000 Ω
● Ni 120
Yes
● Input resistance (Ni 120)
120 Ω
● Ni 200
Yes
● Input resistance (Ni 200)
200 Ω
● Ni 500
Yes
● Input resistance (Ni 500)
500 Ω
● Pt 100
Yes
● Input resistance (Pt 100)
100 Ω
● Pt 1000
Yes
● Input resistance (Pt 1000)
1 000 Ω
● Pt 200
Yes
● Input resistance (Pt 200)
200 Ω
● Pt 500
Yes
● Input resistance (Pt 500)
500 Ω
Input ranges (rated values), resistors
● 0 to 150 ohms
Yes
● 0 to 300 ohms
Yes
● 0 to 600 ohms
Yes
Thermocouple (TC)
Temperature compensation
— parameterizable
No
Analog value generation
Measurement principle
integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
15 bit; + sign
● Integration time, parameterizable
No
● Interference voltage suppression for
interference frequency f1 in Hz
85 dB at 50 / 60 / 400 Hz
6ES7231-5PD32-0XB0
Page 2/4
25.01.2016
Changes preserved
© Copyright Siemens AG
Errors/accuracies
Temperature error (relative to input range), (+/-)
25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Repeat accuracy in steady state at 25 °C (relative to
output area), (+/-)
0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode interference, min.
120 dB
Interrupts/diagnostics/status information
Alarms
Yes
Diagnostic functions
Yes; Can be read out
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Monitoring the supply voltage
Yes
● Wire-break
Yes
Diagnostics indication LED
● for status of the inputs
Yes
● for maintenance
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
● IP20
Yes
Standards, approvals, certificates
CE mark
Yes
CSA approval
Yes
FM approval
Yes
RCM (formerly C-TICK)
Yes
Highest safety class achievable in safety mode
● SIL acc. to IEC 61508
none
Ambient conditions
Free fall
● Fall height, max.
0.3 m; five times, in dispatch package
Ambient temperature during operation
● permissible temperature range
-20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical
mounting, 95% humidity, non-condensing
● min.
-20 °C
● max.
60 °C
Ambient temperature during storage/transportation
● min.
-40 °C
● max.
70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min.
795 hPa
● Operation, max.
1 080 hPa
6ES7231-5PD32-0XB0
Page 3/4
25.01.2016
Changes preserved
© Copyright Siemens AG
● Storage/transport, min.
660 hPa
● Storage/transport, max.
1 080 hPa
Relative humidity
● permissible range (without condensation) at 25
°C
95 %
Extended ambient conditions
Pollutant concentrations
— SO2 at RH < 60% without condensation
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector
Yes
Mechanics/material
Enclosure material (front)
● Plastic
Yes
Dimensions
Width
45 mm
Height
100 mm
Depth
75 mm
Weights
Weight, approx.
220 g
last modified:
22.01.2016
6ES7231-5PD32-0XB0
Page 4/4
25.01.2016
Changes preserved
© Copyright Siemens AG