Data sheet
6ES7238-5XA32-0XB0
SIMATIC S7-1200, Analog input, SM 1238 Energy Meter 480 V AC, power
measurement module for data acquisition in 1- and 3-phase supply
systems (TN, TT) up to 480 V AC; Current range: 1 A, 5A; acquisition of
voltage, current, phase angles, power, energy values, frequencies; Channel
diagnostics
General information
Product type designation
SM 1238, AI energy meter 480 V AC
HW functional status
From FS02
Firmware version
V2.0.1
Product function
● Voltage measurement
— with voltage transformer
● Current measurement
Yes
Yes
Yes
— without current transformer
No
— with current transformer
Yes
● Energy measurement
Yes
● Frequency measurement
Yes
● Power measurement
Yes
● Active power measurement
Yes
● Reactive power measurement
Yes
● I&M data
Yes; I&M 0
● Isochronous mode
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
V13 SP1
Operating mode
● cyclic measurement
Yes
● acyclic measurement
Yes
● Acyclic measured value access
Yes
● Fixed measured value sets
Yes
● Freely definable measured value sets
No
CiR - Configuration in RUN
Reparameterization possible in RUN
Yes
Calibration possible in RUN
Yes
Installation type/mounting
Mounting position
Horizontal, vertical
Supply voltage
Design of the power supply
from CPU
Type of supply voltage
DC
Input current
Current consumption, max.
180 mA
Power loss
6ES72385XA320XB0
Page 1/2
1.20.2021
Subject to change without notice
© Copyright Siemens
Power loss, typ.
0.75 W
Address area
Address space per module
● Address space per module, max.
124 byte; 112 byte input / 12 byte output
Time of day
Operating hours counter
● present
Yes
Analog inputs
Cycle time (all channels), typ.
50 ms; Time for consistent update of all measured and calculated
values (cyclic und acyclic data)
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm
Yes
● Limit value alarm
Yes
● Hardware interrupt
No
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes
● Channel status display
Yes; green LED
● for channel diagnostics
Yes; red Fn LED
● for module diagnostics
Yes; green/red DIAG LED
Integrated Functions
Measuring functions
● Measuring procedure for voltage measurement
TRMS
● Measuring procedure for current measurement
TRMS
● Type of measured value acquisition
seamless
● Curve shape of voltage
Sinusoidal or distorted
● Buffering of measured variables
Yes
● Parameter length
74 byte
● Bandwidth of measured value acquisition
2 kHz
Measuring range
— Frequency measurement, min.
45 Hz
— Frequency measurement, max.
65 Hz
Measuring inputs for voltage
— Measurable line voltage between phase and
neutral conductor
277 V
— Measurable line voltage between the line
conductors
480 V
— Measurable line voltage between phase and
neutral conductor, min.
0V
— Measurable line voltage between phase and
neutral conductor, max.
293 V
— Measurable line voltage between the line
conductors, min.
0V
— Measurable line voltage between the line
conductors, max.
508 V
— Internal resistance line conductor and neutral
conductor
3.4 MΩ
— Power consumption per phase
20 mW
— Impulse voltage resistance 1,2/50µs
1 kV
— Measurement category for voltage
measurement in accordance with IEC 61010-2030
CAT II; CAT III in case of guaranteed protection level of 1.5 kV
Measuring inputs for current
— measurable relative current (AC), min.
1 %; Relative to the secondary rated current 5 A
— measurable relative current (AC), max.
100 %; Relative to the secondary rated current 5 A
— Continuous current with AC, maximum
permissible
5A
— Apparent power consumption per phase for
measuring range 5 A
0.6 V·A
— Rated value short-time withstand current
restricted to 1 s
100 A
6ES72385XA320XB0
Page 2/3
1.20.2021
Subject to change without notice
© Copyright Siemens
— Input resistance measuring range 0 to 5 A
25 mΩ
— Surge strength
10 A; for 1 minute
— Zero point suppression
Parameterizable: 2 ... 250 mA, default 50 mA
Accuracy class according to IEC 61557-12
— Measured variable apparent power
0.5
— Measured variable active power
0.5
— Measured variable power factor
0.5
— Measured variable active energy
0.5
— Measured variable neutral current
0.5; calculated
— Measured variable phase angle
±1 °; not covered by IEC 61557-12
— Measured variable frequency
0.05
Potential separation
Potential separation channels
● between the channels and backplane bus
Yes; 3 700V AC (type test) CAT III
Isolation
Isolation tested with
2 300V AC for 1 min. (type test)
Standards, approvals, certificates
CE mark
Yes
CSA approval
Yes
UL approval
Yes
cULus
Yes
FM approval
Yes
RCM (formerly C-TICK)
Yes
KC approval
Yes
Marine approval
Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-20 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-20 °C
● vertical installation, max.
50 °C
Dimensions
Width
45 mm
Height
100 mm
Depth
75 mm
Weights
Weight, approx.
165 g
Other
Data for selecting a current transformer
● Burden power current transformer x/1A, min.
As a function of cable length and cross section, see device manual
● Burden power current transformer x/5A, min.
As a function of cable length and cross section, see device manual
last modified:
6ES72385XA320XB0
Page 3/3
1/16/2021
1.20.2021
Subject to change without notice