Data sheet
6ES7331-1KF02-0AB0
SIMATIC S7-300, Analog input SM 331, Isolated 8 AI, resolution 13 bits
U/I/resistor/Pt100, NI100, NI1000, LG-NI1000, PTC/KTY, 66 ms conversion time;
1x 40-pole
Input current
from backplane bus 5 V DC, max.
90 mA
Power loss
Power loss, typ.
0.4 W
Analog inputs
Number of analog inputs
● For resistance measurement
8
8
permissible input voltage for voltage input (destruction limit),
max.
30 V; 12 V continuous, 30 V for max. 1 s
permissible input current for current input (destruction limit),
max.
40 mA
Input ranges
● Voltage
Yes
● Current
Yes
● Thermocouple
No
● Resistance thermometer
Yes
● Resistance
Yes
Input ranges (rated values), voltages
● 0 to +10 V
— Input resistance (0 to 10 V)
● 1 V to 5 V
— Input resistance (1 V to 5 V)
Yes
100 kΩ
Yes
100 kΩ
● 1 V to 10 V
No
● -1 V to +1 V
Yes
— Input resistance (-1 V to +1 V)
● -10 V to +10 V
— Input resistance (-10 V to +10 V)
100 kΩ
Yes
100 kΩ
● -2.5 V to +2.5 V
No
● -250 mV to +250 mV
No
● -5 V to +5 V
Yes
— Input resistance (-5 V to +5 V)
● -50 mV to +50 mV
— Input resistance (-50 mV to +50 mV)
● -500 mV to +500 mV
— Input resistance (-500 mV to +500 mV)
● -80 mV to +80 mV
100 kΩ
Yes
100 kΩ
Yes
100 kΩ
No
Input ranges (rated values), currents
● 0 to 20 mA
— Input resistance (0 to 20 mA)
● -10 mA to +10 mA
6ES73311KF020AB0
Page 1/3
Yes
100 Ω
No
5/15/2024
Subject to change without notice
© Copyright Siemens
● -20 mA to +20 mA
— Input resistance (-20 mA to +20 mA)
Yes
100 Ω
● -3.2 mA to +3.2 mA
No
● 4 mA to 20 mA
Yes
— Input resistance (4 mA to 20 mA)
100 Ω
Input ranges (rated values), thermocouples
● Type B
No
● Type C
No
● Type E
No
● Type J
No
● Type K
No
● Type L
No
● Type N
No
● Type R
No
● Type S
No
● Type T
No
● Type U
No
● Type TXK/TXK(L) to GOST
No
Input ranges (rated values), resistance thermometer
● Cu 10
No
● Ni 100
Yes; Standard/climate
— Input resistance (Ni 100)
● Ni 1000
— Input resistance (Ni 1000)
● LG-Ni 1000
— Input resistance (LG-Ni 1000)
100 MΩ
Yes
100 MΩ
Yes; Standard/climate
100 MΩ
● Ni 120
No
● Ni 200
No
● Ni 500
No
● Pt 100
Yes; Standard/climate
— Input resistance (Pt 100)
100 MΩ
● Pt 1000
No
● Pt 200
No
● Pt 500
No
Input ranges (rated values), resistors
● 0 to 150 ohms
No
● 0 to 300 ohms
No
● 0 to 600 ohms
Yes
— Input resistance (0 to 600 ohms)
● 0 to 6000 ohms
— Input resistance (0 to 6000 ohms)
100 MΩ
Yes
100 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizable
No
— internal temperature compensation
No
— external temperature compensation with
compensations socket
No
Characteristic linearization
● parameterizable
Yes
— for thermocouples
No
— for resistance thermometer
yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.;
LG-Ni1000 standard/air con.
Cable length
● shielded, max.
200 m; max. 50 m at 50 mV
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
13 bit
● Integration time, parameterizable
Yes; 60 / 50 ms
● Basic conversion time (ms)
66 / 55 ms
● Interference voltage suppression for interference
frequency f1 in Hz
50 / 60 Hz
6ES73311KF020AB0
Page 2/3
5/15/2024
Subject to change without notice
© Copyright Siemens
Encoder
Connection of signal encoders
● for voltage measurement
Yes
● for current measurement as 2-wire transducer
Yes; with external supply
● for current measurement as 4-wire transducer
Yes
● for resistance measurement with two-wire connection
Yes
● for resistance measurement with three-wire connection
Yes
● for resistance measurement with four-wire connection
Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)
0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V)
● Current, relative to input range, (+/-)
0.5 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-)
0.5 %; 0 to 6 kohms, 0 to 600 kohms
● Resistance thermometer, relative to input range, (+/-)
1 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LGNi1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard)
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)
0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
● Current, relative to input range, (+/-)
0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-)
0.3 %; 0 to 6 kohms, 0 to 600 kohms
● Resistance thermometer, relative to input range, (+/-)
1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000,
LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
Interrupts/diagnostics/status information
Diagnostics function
No
Alarms
● Diagnostic alarm
No
● Limit value alarm
No
Diagnoses
● Diagnostic information readable
No
Diagnostics indication LED
● Group error SF (red)
No
Potential separation
Potential separation analog inputs
● between the channels
No
● between the channels and backplane bus
Yes
Isolation
Isolation tested with
500 V DC
connection method
required front connector
40-pin
Dimensions
Width
40 mm
Height
125 mm
Depth
117 mm
Weights
Weight, approx.
250 g