Data sheet
6ES7522-1BL01-0AB0
SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in
groups of 8; 4 A per group; single-channel diagnostics; substitute value, switching
cycle counter for connected actuators. the module supports the safety-oriented
shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and
Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw
terminals or push-in) to be ordered separately
General information
Product type designation
DQ 32x24VDC/0.5A HF
HW functional status
From FS02
Firmware version
V1.1.0
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
Yes
● Prioritized startup
Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V13 SP1 / -
● STEP 7 configurable/integrated from version
V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision
V1.0 / V5.1
● PROFINET from GSD version/GSD revision
V2.3 / -
Operating mode
● DQ
Yes
● DQ with energy-saving function
No
● PWM
No
● Cam control (switching at comparison values)
No
● Oversampling
No
● MSO
Yes
● Integrated operating cycle counter
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes; through internal protection with 7 A per group
Input current
Current consumption, max.
60 mA
output voltage / header
Rated value (DC)
24 V
Power
Power available from the backplane bus
1.1 W
Power loss
Power loss, typ.
3.5 W
Digital outputs
Type of digital output
Transistor
Number of digital outputs
32
Current-sourcing
Yes
Digital outputs, parameterizable
Yes
6ES75221BL010AB0
Page 1/3
5/6/2024
Subject to change without notice
© Copyright Siemens
Short-circuit protection
● Response threshold, typ.
Yes; Clocked electronically
1A
Limitation of inductive shutdown voltage to
L+ (-53 V)
Controlling a digital input
Yes
Switching capacity of the outputs
● with resistive load, max.
0.5 A
● on lamp load, max.
5W
Load resistance range
● lower limit
48 Ω
● upper limit
12 kΩ
Output voltage
● for signal "1", min.
L+ (-0.8 V)
Output current
● for signal "1" rated value
0.5 A
● for signal "1" permissible range, max.
0.5 A
● for signal "0" residual current, max.
0.5 mA
Output delay with resistive load
● "0" to "1", max.
100 µs
● "1" to "0", max.
500 µs
Parallel switching of two outputs
● for logic links
Yes
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
100 Hz
● with inductive load, max.
0.5 Hz; According to IEC 60947-5-1, DC-13
● on lamp load, max.
10 Hz
Total current of the outputs
● Current per channel, max.
0.5 A; see additional description in the manual
● Current per group, max.
4 A; see additional description in the manual
● Current per module, max.
16 A; see additional description in the manual
Cable length
● shielded, max.
1 000 m
● unshielded, max.
600 m
Isochronous mode
Execution and activation time (TCO), min.
70 µs
Bus cycle time (TDP), min.
250 µs
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
● Maintenance interrupt
Yes
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
Yes
● Short-circuit
Yes
● Group error
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● MAINT LED
Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green LED
● Channel status display
Yes; green LED
● for channel diagnostics
Yes; red LED
● for module diagnostics
Yes; red LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels, in groups of
8
6ES75221BL010AB0
Page 2/3
5/6/2024
Subject to change without notice
© Copyright Siemens
● between the channels and backplane bus
Yes
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions
No
Suitable for safety-related tripping of standard modules
Yes; From FS02
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SIL acc. to IEC 62061
SIL 2
● remark on safety-oriented shutdown
https://support.industry.siemens.com/cs/de/en/view/39198632
product functions / security / header
signed firmware update
No
data integrity
No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C; From FS03
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C; From FS03
● vertical installation, max.
40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width
35 mm
Height
147 mm
Depth
129 mm
Weights
Weight, approx.
280 g
last modified:
3/12/2024
6ES75221BL010AB0
Page 3/3
5/6/2024
Subject to change without notice
© Copyright Siemens