Data sheet
6ES7532-5HD00-0AB0
SIMATIC S7-1500, analog output module AQ 4xU/I ST, 16-bit resolution
accuracy 0.3%. 4 channels in groups of 4, diagnostics; substitute value; the
module supports the safety-oriented shutdown of load groups up to SIL2
according to EN IEC 62061:2021 and Category 2 / PL c according to EN
ISO 13849-1:2015. delivery including infeed element, shielding bracket and
shield terminal: front connector (screw terminals or push-in) to be ordered
separately
General information
Product type designation
AQ 4xU/I ST
HW functional status
from FS04
Firmware version
V2.2.0
● FW update possible
Yes
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
No
● Prioritized startup
No
● Output range scalable
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from
version
V12 / V12
● STEP 7 configurable/integrated from version
V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision
V1.0 / V5.1
● PROFINET from GSD version/GSD revision
V2.3 / -
Operating mode
● Oversampling
No
● MSO
Yes
CiR - Configuration in RUN
Reparameterization possible in RUN
Yes
Calibration possible in RUN
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption, max.
190 mA; with 24 V DC supply
Power
Power available from the backplane bus
0.6 W
Power loss
Power loss, typ.
4W
Analog outputs
Number of analog outputs
4
Voltage output, short-circuit protection
Yes
Voltage output, short-circuit current, max.
24 mA
Current output, no-load voltage, max.
22 V
Cycle time (all channels), min.
3.2 ms; independent of number of activated channels
6ES75325HD000AB0
Page 1/3
7/8/2022
Subject to change without notice
© Copyright Siemens
Output ranges, voltage
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -5 V to +5 V
No
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Connection of actuators
● for voltage output two-wire connection
Yes
● for voltage output four-wire connection
Yes
● for current output two-wire connection
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1 kΩ; 0.5 kOhm at 1 to 5 V
● with voltage outputs, capacitive load, max.
1 µF
● with current outputs, max.
750 Ω
● with current outputs, inductive load, max.
10 mH
Cable length
● shielded, max.
800 m; for current, 200 m for voltage
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
16 bit
● Conversion time (per channel)
0.5 ms
Settling time
● for resistive load
1.5 ms
● for capacitive load
2.5 ms
● for inductive load
2.5 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50
kHz), (+/-)
0.02 %
Linearity error (relative to output range), (+/-)
0.15 %
Temperature error (relative to output range), (+/-)
0.002 %/K
Crosstalk between the outputs, max.
-100 dB
Repeat accuracy in steady state at 25 °C (relative to
output range), (+/-)
0.05 %
note regarding accuracy
at temperatures below 0 °C, the figures for operating error and
temperature error are doubled
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-)
0.3 %
● Current, relative to output range, (+/-)
0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-)
0.2 %
● Current, relative to output range, (+/-)
0.2 %
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
Yes; Only for output type "current"
● Short-circuit
Yes; Only for output type "voltage"
● Overflow/underflow
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green LED
● Channel status display
Yes; green LED
● for channel diagnostics
Yes; red LED
6ES75325HD000AB0
Page 2/3
7/8/2022
Subject to change without notice
© Copyright Siemens
● for module diagnostics
Yes; red LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels, in groups of
4
● between the channels and backplane bus
Yes
● Between the channels and load voltage L+
Yes
Permissible potential difference
between S- and MANA (UCM)
8 V DC
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules
Yes; From FS05
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SIL acc. to IEC 62061
SIL 2
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C; From FS06
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C; From FS06
● vertical installation, max.
40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width
35 mm
Height
147 mm
Depth
129 mm
Weights
Weight, approx.
310 g
last modified:
3/3/2022
6ES75325HD000AB0
Page 3/3
7/8/2022
Subject to change without notice
© Copyright Siemens