Data sheet for SINAMICS G120X
MLFB-Ordering data
6SL3220-1YE28-0UB0
Figure similar
Client order no. :
Item no. :
Order no. :
Consignment no. :
Offer no. :
Project :
Remarks :
Rated data
General tech. specifications
Input
Number of phases
3 AC
Line voltage
380 ... 480 V +10 % -20 %
Line frequency
47 ... 63 Hz
Rated voltage
400V IEC
480V NEC
Rated current (LO)
29.50 A
29.50 A
Rated current (HO)
23.97 A
24.50 A
Output
Number of phases
3 AC
Rated voltage
400V IEC
480V NEC
Rated power (LO)
15.00 kW
20.00 hp
Rated power (HO)
11.00 kW
15.00 hp
Rated current (LO)
32.00 A
27.00 A
Rated current (HO)
26.00 A
21.00 A
Rated current (IN)
33.00 A
Max. output current
43.00 A
Pulse frequency
4 kHz
Output frequency for vector control
0 ... 200 Hz
Output frequency for V/f control
0 ... 550 Hz
Power factor λ
0.70 ... 0.85
Offset factor cos φ
0.96
Efficiency η
0.98
Sound pressure level (1m)
67 dB
Power loss
0.396 kW
Filter class (integrated)
Unfiltered
EMC category (with accessories)
without
Ambient conditions
Standard board coating type
Class 3C2, according to IEC 60721-33: 2002
Cooling
Air cooling using an integrated fan
Cooling air requirement
0.018 m³/s (0.653 ft³/s)
Installation altitude
1000 m (3280.84 ft)
Ambient temperature
Operation
-20 ... 45 °C (-4 ... 113 °F)
Transport
-40 ... 70 °C (-40 ... 158 °F)
Storage
-25 ... 55 °C (-13 ... 131 °F)
Relative humidity
Max. operation
95 % At 40 °C (104 °F), condensation
and icing not permissible
Overload capability
Low Overload (LO)
110% base load current IL for 60 s in a 300 s cycle time
High Overload (HO)
150% x base load current IH for 60 s within a 600 s cycle time
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 1 of 3
Generated Thu Jan 14 13:26:36 CET 2021
Data sheet for SINAMICS G120X
MLFB-Ordering data
6SL3220-1YE28-0UB0
Figure similar
Mechanical data
Degree of protection
IP20 / UL open type
Size
FSC
Net weight
7 kg (15.74 lb)
Width
140 mm (5.51 in)
Height
295 mm (11.61 in)
Depth
218 mm (8.58 in)
Inputs / outputs
Standard digital inputs
Number
6
Switching level: 0→1
11 V
Switching level: 1→0
5V
Max. inrush current
15 mA
Closed-loop control techniques
V/f linear / square-law / parameterizable
Yes
V/f with flux current control (FCC)
Yes
V/f ECO linear / square-law
Yes
Sensorless vector control
Yes
Vector control, with sensor
No
Encoderless torque control
Yes
Torque control, with encoder
No
Communication
Communication
USS, Modbus RTU, BACnet MS/TP
Connections
Signal cable
Fail-safe digital inputs
Number
1
Digital outputs
Conductor cross-section
0.15 ... 1.50 mm²
(AWG 24 ... AWG 16)
Line side
Number as relay changeover contact
2
Version
screw-type terminal
Output (resistive load)
DC 30 V, 5.0 A
Conductor cross-section
1.50 ... 16.00 mm²
(AWG 16 ... AWG 6)
Number as transistor
0
Analog / digital inputs
Number
2 (Differential input)
Resolution
10 bit
Motor end
Version
Screw-type terminals
Conductor cross-section
1.50 ... 16.00 mm²
(AWG 16 ... AWG 6)
DC link (for braking resistor)
Switching threshold as digital input
PE connection
0→1
4V
1→0
1.6 V
Analog outputs
Number
On housing with M4 screw
Max. motor cable length
Shielded
150 m (492.13 ft)
Unshielded
300 m (984.25 ft)
1 (Non-isolated output)
PTC/ KTY interface
1 motor temperature sensor input, sensors that can be connected: PTC, KTY
and Thermo-Click, accuracy ±5 °C
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 2 of 3
Generated Thu Jan 14 13:26:36 CET 2021
Data sheet for SINAMICS G120X
MLFB-Ordering data
6SL3220-1YE28-0UB0
Figure similar
Converter losses to EN 50598-2*
Efficiency class
IE2
Comparison with the reference converter (90% /
100%)
-35.40 %
Standards
I
100%
50%
25%
278.7 W (1.26 %)
324.6 W (1.46 %)
395.8 W (1.79 %)
173.9 W (0.78 %)
191.9 W (0.87 %)
216.3 W (0.98 %)
138.3 W (0.62 %)
146 W (0.66 %)
50%
90%
Compliance with standards
UL, cUL, CE, C-Tick (RCM), EAC, KCC, SEMI
F47, REACH
CE marking
EMC Directive 2004/108/EC, Low-Voltage
Directive 2006/95/EC
f
The percentage values show the losses in relation to the rated apparent power of the converter.
The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
version of the converter without options/components.
*converted values
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 3 of 3
Generated Thu Jan 14 13:26:36 CET 2021