6SL32202YE280UB0

6SL32202YE280UB0

  • 厂商:

    SIEMENS(西门子)

  • 封装:

  • 描述:

    G120X IP20 380...480V 15KW FSC U

  • 详情介绍
  • 数据手册
  • 价格&库存
6SL32202YE280UB0 数据手册
Data sheet for SINAMICS G120X MLFB-Ordering data 6SL3220-2YE28-0UB0 Figure similar Client order no. : Item no. : Order no. : Consignment no. : Offer no. : Project : Remarks : Rated data General tech. specifications Input Number of phases 3 AC Line voltage 380 ... 480 V +10 % -20 % Line frequency 47 ... 63 Hz Rated voltage 400V IEC 480V NEC Rated current (LO) 29.50 A 29.50 A Rated current (HO) 23.97 A 24.50 A Output Number of phases 3 AC Rated voltage 400V IEC 480V NEC Rated power (LO) 15.00 kW 20.00 hp Rated power (HO) 11.00 kW 15.00 hp Rated current (LO) 32.00 A 27.00 A Rated current (HO) 26.00 A 21.00 A Rated current (IN) 33.00 A Max. output current 43.00 A Pulse frequency 4 kHz Output frequency for vector control 0 ... 200 Hz Output frequency for V/f control 0 ... 550 Hz Power factor λ 0.70 ... 0.85 Offset factor cos φ 0.96 Efficiency η 0.98 Sound pressure level (1m) 67 dB Power loss 0.396 kW Filter class (integrated) Unfiltered EMC category (with accessories) without Ambient conditions Standard board coating type Class 3C2, according to IEC 60721-33: 2002 Cooling Air cooling using an integrated fan Cooling air requirement 0.018 m³/s (0.653 ft³/s) Installation altitude 1000 m (3280.84 ft) Ambient temperature Operation -20 ... 45 °C (-4 ... 113 °F) Transport -40 ... 70 °C (-40 ... 158 °F) Storage -25 ... 55 °C (-13 ... 131 °F) Relative humidity Max. operation 95 % At 40 °C (104 °F), condensation and icing not permissible Overload capability Low Overload (LO) 110% base load current IL for 60 s in a 300 s cycle time High Overload (HO) 150% x base load current IH for 60 s within a 600 s cycle time Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 3 Generated Thu Jan 14 13:31:25 CET 2021 Data sheet for SINAMICS G120X MLFB-Ordering data 6SL3220-2YE28-0UB0 Figure similar Mechanical data Degree of protection IP20 / UL open type Size FSC Net weight 7 kg (15.74 lb) Width 140 mm (5.51 in) Height 295 mm (11.61 in) Depth 218 mm (8.58 in) Inputs / outputs Standard digital inputs Number 6 Switching level: 0→1 11 V Switching level: 1→0 5V Max. inrush current 15 mA Closed-loop control techniques V/f linear / square-law / parameterizable Yes V/f with flux current control (FCC) Yes V/f ECO linear / square-law Yes Sensorless vector control Yes Vector control, with sensor No Encoderless torque control Yes Torque control, with encoder No Communication Communication USS, Modbus RTU, BACnet MS/TP Connections Signal cable Fail-safe digital inputs Number 1 Digital outputs Conductor cross-section 0.15 ... 1.50 mm² (AWG 24 ... AWG 16) Line side Number as relay changeover contact 2 Version screw-type terminal Output (resistive load) DC 30 V, 5.0 A Conductor cross-section 1.50 ... 16.00 mm² (AWG 16 ... AWG 6) Number as transistor 0 Analog / digital inputs Number 2 (Differential input) Resolution 10 bit Motor end Version Screw-type terminals Conductor cross-section 1.50 ... 16.00 mm² (AWG 16 ... AWG 6) DC link (for braking resistor) Switching threshold as digital input PE connection 0→1 4V 1→0 1.6 V Analog outputs Number On housing with M4 screw Max. motor cable length Shielded 150 m (492.13 ft) Unshielded 300 m (984.25 ft) 1 (Non-isolated output) PTC/ KTY interface 1 motor temperature sensor input, sensors that can be connected: PTC, KTY and Thermo-Click, accuracy ±5 °C Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 3 Generated Thu Jan 14 13:31:25 CET 2021 Data sheet for SINAMICS G120X MLFB-Ordering data 6SL3220-2YE28-0UB0 Figure similar Converter losses to EN 50598-2* Efficiency class IE2 Comparison with the reference converter (90% / 100%) -35.40 % Standards I 100% 50% 25% 278.7 W (1.26 %) 324.6 W (1.46 %) 395.8 W (1.79 %) 173.9 W (0.78 %) 191.9 W (0.87 %) 216.3 W (0.98 %) 138.3 W (0.62 %) 146 W (0.66 %) 50% 90% Compliance with standards UL, cUL, CE, C-Tick (RCM), EAC, KCC, SEMI F47, REACH CE marking EMC Directive 2004/108/EC, Low-Voltage Directive 2006/95/EC f The percentage values show the losses in relation to the rated apparent power of the converter. The diagram shows the losses for the points (as per standard EN 50598) of the relative torque generating current (I) over the relative motor stator frequency(f). The values are valid for the basic version of the converter without options/components. *converted values Operator panel: Basic Operator Panel (BOP-2) Screen Display design Ambient conditions LCD, monochrome Mechanical data Degree of protection IP55 / UL type 12 Net weight 0.14 kg (0.31 lb) Width 70.0 mm (2.76 in) Ambient temperature during Operation 0 ... 50 °C (32 ... 122 °F) Storage -40 ... 70 °C (-40 ... 158 °F) Transport -40 ... 70 °C (-40 ... 158 °F) Relative humidity at 25°C during Max. operation Height 106.85 mm (4.21 in) Depth 19.60 mm (0.77 in) 95 % Approvals Certificate of suitability CE, cULus, EAC, KCC, RCM Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 3 of 3 Generated Thu Jan 14 13:31:25 CET 2021
6SL32202YE280UB0
物料型号:6SL3220-2YE28-0UB0

器件简介: - 该变频器适用于空气冷却,内置风扇。 - 其冷却空气需求为0.018 m³/s,适用于最高1000米安装高度,温度范围为-25至55°C。

引脚分配: - 标准数字输入:1个15 mA 11 V和6个2 0 DC 30 V, 5.0 A。 - 故障安全数字输入:1.50 ... 16.00 mm²(AWG 16 ... AWG 6)螺钉式端子。 - 数字输出:线侧和电机端均有,具体导线截面积未详细说明。

参数特性: - 输入电压:3AC 380...480V+10%-20%,频率47...63Hz。 - 额定电流(低过载LO):29.50A,高过载HO:23.97A(400V IEC)或24.50A(480V NEC)。 - 额定功率(低过载LO):15.00kW,高过载HO:11.00kW。 - 最大输出电流:43.00A。 - 输出频率:矢量控制0...200Hz,V/f控制0...550Hz。

功能详解: - 支持V/f线性/平方律/参数化控制。 - 支持无传感器矢量控制。 - 标准数字输入和输出,模拟/数字输入,具有PTC/KTY接口。

应用信息: - 适用于需要闭环控制技术的场合。 - 具有机械数据和环境条件参数,如防护等级IP20/UL开放式,尺寸FSC,净重7kg。

封装信息: - 尺寸:宽140mm,高295mm,深218mm。 - 冷却方式:空气冷却,需要冷却空气。 - 安装高度和环境温度:标准板涂层类型未说明,但有操作、运输和存储的相关湿度和温度条件。
6SL32202YE280UB0 价格&库存

很抱歉,暂时无法提供与“6SL32202YE280UB0”相匹配的价格&库存,您可以联系我们找货

免费人工找货