Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YC18-1UP0
Client order no. :
Order no. :
Offer no. :
Remarks :
Figure similar
Item no. :
Consignment no. :
Project :
Rated data
Inputs / outputs
Input
Standard digital inputs
Number of phases
3 AC
Number
6
Line voltage
200 ... 240 V +10 % -20 %
Switching level: 0 → 1
11 V
Line frequency
47 ... 63 Hz
Switching level: 1 → 0
5V
Rated voltage
200V IEC
240V NEC
Max. inrush current
15 mA
Rated current (LO)
12.70 A
12.70 A
Rated current (HO)
9.60 A
9.60 A
Fail-safe digital inputs
Number
Output
1
Digital outputs
Number of phases
3 AC
Rated voltage
200V IEC
240V NEC
Rated power (LO)
3.00 kW
Rated power (HO)
Rated current (LO)
Number as relay changeover contact
2
Output (resistive load)
DC 30 V, 5.0 A
4.00 hp
Number as transistor
0
2.20 kW
3.00 hp
Analog / digital inputs
13.60 A
13.60 A
Number
2 (Differential input)
Rated current (HO)
10.40 A
10.40 A
Resolution
10 bit
Rated current (IN)
14.10 A
Max. output current
18.40 A
Pulse frequency
4 kHz
Output frequency for vector control
0 ... 200 Hz
Output frequency for V/f control
0 ... 550 Hz
Overload capability
1)
Switching threshold as digital input
0→1
4V
1→0
1.6 V
Analog outputs
Number
1 (Non-isolated output)
PTC/ KTY interface
Low Overload (LO)
110% base load current IL for 60 s in a 300 s cycle time
1 motor temperature sensor input, sensors that can be connected PTC, KTY and
Thermo-Click, accuracy ±5 °C
Closed-loop control techniques
High Overload (HO)
150% x base load current IH for 60 s within a 600 s cycle time
General tech. specifications
V/f linear / square-law / parameterizable
Yes
V/f with flux current control (FCC)
Yes
Power factor λ
0.70 ... 0.85
V/f ECO linear / square-law
Yes
Offset factor cos φ
0.96
Sensorless vector control
Yes
Efficiency η
0.96
Vector control, with sensor
No
Sound pressure level (1m)
63 dB
Encoderless torque control
No
Power loss 3)
0.165 kW
Torque control, with encoder
No
Filter class (integrated)
Unfiltered
EMC category (with accessories)
without
Safety function "Safe Torque Off"
without
Communication
Communication
PROFIBUS DP
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 1 of 4
Generated Sat Jul 9 09:49:06 CET 2022
Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YC18-1UP0
Ambient conditions
Standard board coating type
Class 3C2, according to IEC 60721-3-3:
2002
Cooling
Air cooling using an integrated fan
Cooling air requirement
0.018 m³/s (0.653 ft³/s)
Installation altitude
1,000 m (3,280.84 ft)
Ambient temperature
Operation
-20 ... 45 °C (-4 ... 113 °F)
Transport
-40 ... 70 °C (-40 ... 158 °F)
Storage
-25 ... 55 °C (-13 ... 131 °F)
Relative humidity
Max. operation
95 % At 40 °C (104 °F), condensation
and icing not permissible
Mechanical data
Degree of protection
IP20 / UL open type
Frame size
FSB
Net weight
5.8 kg (12.79 lb)
Dimensions
Width
100 mm (3.94 in)
Height
275 mm (10.83 in)
Depth
218 mm (8.58 in)
Standards
Compliance with standards
UL, cUL, CE, C-Tick (RCM), EAC, KCC,
SEMI F47, REACH
CE marking
EMC Directive 2004/108/EC, LowVoltage Directive 2006/95/EC
Connections
Signal cable
Conductor cross-section
0.15 ... 1.50 mm²
(AWG 24 ... AWG 16)
Converter losses to IEC61800-9-2*
Efficiency class
IE2
Comparison with the reference
converter (90% / 100%)
45.6 %
Line side
Version
screw-type terminal
Conductor cross-section
1.50 ... 6.00 mm²
(AWG 16 ... AWG 10)
I
100%
122.0 W (2.2 %)
140.0 W (2.5 %)
165.0 W (2.9 %)
87.4 W (1.5 %)
95.4 W (1.7 %)
106.0 W (1.9 %)
73.5 W (1.3 %)
77.3 W (1.4 %)
Motor end
Version
Screw-type terminals
Conductor cross-section
1.50 ... 6.00 mm²
(AWG 16 ... AWG 10)
50%
DC link (for braking resistor)
PE connection
On housing with M4 screw
25%
Max. motor cable length
Shielded
150 m (492.13 ft)
Unshielded
300 m (984.25 ft)
50%
90%
f
The percentage values show the losses in relation to the rated apparent power of
the converter.
The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator frequency
(f). The values are valid for the basic version of the converter without
options/components.
*converted values
1)
The output current and HP ratings are valid for the voltage range 220V-240V
3)
Typical value. More information can be found in the element group "Converter losses to IEC 61800-9-2" in this datasheet.
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 2 of 4
Generated Sat Jul 9 09:49:06 CET 2022
Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YC18-1UP0
Operator panel: Intelligent Operator Panel (IOP-2)
Screen
Display design
LCD color
Screen resolution
320 x 240 Pixel
Ambient conditions
Ambient temperature
Operation
0 ... 50 °C (32 ... 122 °F)
55 °C only with door installation kit
Mechanical data
Degree of protection
IP55 / UL type 12
Net weight
0.134 kg (0.30 lb)
Dimensions
Storage
-40 ... 70 °C (-40 ... 158 °F)
Transport
-40 ... 70 °C (-40 ... 158 °F)
Relative humidity at 25°C during
Max. operation
Width
70.00 mm (2.76 in)
Height
106.85 mm (4.21 in)
Depth
19.65 mm (0.77 in)
95 %
Approvals
Certificate of suitability
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 3 of 4
CE, cULus, EAC, KCC, RCM
Generated Sat Jul 9 09:49:06 CET 2022
Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YC18-1UP0
I/O Extension Module
Inputs / outputs
Mechanical data
Dimensions
Digital inputs
Number of digital inputs 1)
2
Width
71 mm (2.80 in)
Conductor cross-section
0.5 … 1.5 mm² (AWG 21 … AWG 16)
Height
117 mm (4.61 in)
Alternatively 2 x 0.5 mm²
Depth
27 mm (1.06 in)
Input voltage (0→1)
11 V
Input voltage (1→0)
5V
Input voltage, max.
30 V
Number of digital outputs
4
Conductor cross-section
1.5 mm² (AWG 16)
Output
6: digital input; DI 7: P or M switch; DI COM: Input for Control Unit interface (24 V out, max.
250 mA)
2) The
max. current depends on the temperature and the size of the connected converted. It
varies between 2 A and 3 A at 30 V DC.
analog inputs for the connection of Pt1000/Ni1000 temperature sensors. One of which can
be optionally used as analog input.
4) Switchable between voltage (0 ... 10 V) and current (0 ... 20 mA) using a parameter
3) 2
Digital outputs
current 2)
1) DI
2A
Analog inputs
Number of analog inputs 3)
2
Conductor cross-section
0.5 … 1.5 mm² (AWG 21 … AWG 16)
alternatively 2*0.5 mm²
Current
0 … 20 mA
Analog outputs
Number of analog outputs
2
Type of analog outputs 4)
Non-isolated output
Conductor cross-section
0.5 … 1.5 mm² (AWG 21 … AWG 16)
Alternatively 2 x 0.5 mm²
Output voltage
0 … 10 V
Output current
0 … 20 mA
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 4 of 4
Generated Sat Jul 9 09:49:06 CET 2022