Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YE52-0CB0
Client order no. :
Order no. :
Offer no. :
Remarks :
Figure similar
Item no. :
Consignment no. :
Project :
Rated data
Inputs / outputs
Input
Standard digital inputs
Number of phases
3 AC
Number
6
Line voltage
380 ... 480 V +10 % -20 %
Switching level: 0 → 1
11 V
Line frequency
47 ... 63 Hz
Switching level: 1 → 0
5V
Rated voltage
400V IEC
480V NEC
Max. inrush current
15 mA
Rated current (LO)
365.00 A
356.00 A
Fail-safe digital inputs
Rated current (HO)
330.00 A
327.00 A
Output
Number
1
Digital outputs
Number of phases
3 AC
Rated voltage
Number as relay changeover contact
2
Output (resistive load)
DC 30 V, 5.0 A
0
400V IEC
480V
Rated power (LO)
200.00 kW
300.00 hp
Number as transistor
Rated power (HO)
160.00 kW
250.00 hp
Analog / digital inputs
Rated current (LO)
370.00 A
361.00 A
Number
2 (Differential input)
Rated current (HO)
302.00 A
302.00 A
Resolution
10 bit
Rated current (IN)
379.00 A
Max. output current
500.00 A
Pulse frequency
2 kHz
Output frequency for vector control
0 ... 200 Hz
Output frequency for V/f control
0 ... 550 Hz
NEC 1)
Overload capability
Switching threshold as digital input
0→1
4V
1→0
1.6 V
Analog outputs
Number
1 (Non-isolated output)
PTC/ KTY interface
Low Overload (LO)
110% base load current IL for 60 s in a 300 s cycle time
1 motor temperature sensor input, sensors that can be connected PTC, KTY and
Thermo-Click, accuracy ±5 °C
Closed-loop control techniques
High Overload (HO)
150% x base load current IH for 60 s within a 600 s cycle time
General tech. specifications
V/f linear / square-law / parameterizable
Yes
V/f with flux current control (FCC)
Yes
Power factor λ
0.90 ... 0.95
V/f ECO linear / square-law
Yes
Offset factor cos φ
0.99
Sensorless vector control
Yes
Efficiency η
0.98
Vector control, with sensor
No
Sound pressure level (1m)
74 dB
Encoderless torque control
No
Power loss 3)
4.610 kW
Torque control, with encoder
No
Filter class (integrated)
RFI suppression filter for Category C3
EMC category (with accessories)
Category C3
Safety function "Safe Torque Off"
without
Communication
Communication
USS, Modbus RTU, BACnet MS/TP
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 1 of 3
Generated Sat Jul 9 09:59:08 CET 2022
Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YE52-0CB0
Ambient conditions
Standard board coating type
Class 3C2, according to IEC 60721-3-3:
2002
Cooling
Air cooling using an integrated fan
Cooling air requirement
0.210 m³/s (7.416 ft³/s)
Installation altitude
1,000 m (3,280.84 ft)
Ambient temperature
Operation
-20 ... 45 °C (-4 ... 113 °F)
Transport
-40 ... 70 °C (-40 ... 158 °F)
Storage
-25 ... 55 °C (-13 ... 131 °F)
Relative humidity
Max. operation
95 % At 40 °C (104 °F), condensation
and icing not permissible
Mechanical data
Degree of protection
IP20 / UL open type
Frame size
FSG
Net weight
113 kg (249.12 lb)
Dimensions
Width
305 mm (12.01 in)
Height
999 mm (39.33 in)
Depth
369 mm (14.53 in)
Standards
Compliance with standards
UL, cUL, CE, C-Tick (RCM), EAC, KCC,
SEMI F47, REACH
CE marking
EMC Directive 2004/108/EC, LowVoltage Directive 2006/95/EC
Connections
Signal cable
Conductor cross-section
0.15 ... 1.50 mm²
(AWG 24 ... AWG 16)
Converter losses to IEC61800-9-2*
Efficiency class
IE2
Comparison with the reference
converter (90% / 100%)
43.9 %
Line side
Version
M10 screw
Conductor cross-section
35.00 ... 2 x 185.00 mm²
(AWG 1 ... MCM 2 x 350)
I
100%
2,940.0 W (1.2 %)
3,550.0 W (1.4 %)
4,610.0 W (1.8 %)
1,470.0 W (0.6 %)
1,690.0 W (0.7 %)
2,020.0 W (0.8 %)
994.0 W (0.4 %)
1,080.0 W (0.4 %)
Motor end
Version
M10 screw
Conductor cross-section
35.00 ... 2 x 185.00 mm²
(AWG 1 ... MCM 2 x 350)
50%
DC link (for braking resistor)
PE connection
M10 screw
25%
Max. motor cable length
Shielded
200 m (656.17 ft)
50%
90%
f
The percentage values show the losses in relation to the rated apparent power of
the converter.
The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator frequency
(f). The values are valid for the basic version of the converter without
options/components.
*converted values
1)
The output current and HP ratings are valid for the voltage range 440V-480V
3)
Typical value. More information can be found in the element group "Converter losses to IEC 61800-9-2" in this datasheet.
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 2 of 3
Generated Sat Jul 9 09:59:08 CET 2022
Data sheet for SINAMICS G120X
Article No. :
6SL3220-3YE52-0CB0
Operator panel: Intelligent Operator Panel (IOP-2)
Screen
Display design
LCD color
Screen resolution
320 x 240 Pixel
Ambient conditions
Ambient temperature
Operation
0 ... 50 °C (32 ... 122 °F)
55 °C only with door installation kit
Mechanical data
Degree of protection
IP55 / UL type 12
Net weight
0.134 kg (0.30 lb)
Dimensions
Storage
-40 ... 70 °C (-40 ... 158 °F)
Transport
-40 ... 70 °C (-40 ... 158 °F)
Relative humidity at 25°C during
Max. operation
Width
70.00 mm (2.76 in)
Height
106.85 mm (4.21 in)
Depth
19.65 mm (0.77 in)
95 %
Approvals
Certificate of suitability
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 3 of 3
CE, cULus, EAC, KCC, RCM
Generated Sat Jul 9 09:59:08 CET 2022
很抱歉,暂时无法提供与“6SL32203YE520CB0”相匹配的价格&库存,您可以联系我们找货
免费人工找货