Data sheet
6XV1860-3PH05
product type designation
PROFIBUS ECOFAST Hybrid Cable GP
product description
ECOFAST Hybrid cable (data and energy wires), preferred length,
assembled with ECOFAST connector and socket
PROFIBUS ECOFAST Hybrid Cable GP, 2x Cu 0.64 mm, 4x Cu 1.5 mm2,
Cable pre-assembled with ECOFAST connector and socket, trailable,
Length 0.5 m
suitability for use
Hybrid cable for connection of ECOFAST stations, UL approval
cable designation
02Y (ST)C 1x2x0.65/2.56 -150 LI LIY-Z Y 4x1x1.5 VI
wire length
0.5 m
electrical data
attenuation factor per length
● at 9.6 kHz / maximum
0.003 dB/m
● at 38.4 kHz / maximum
0.004 dB/m
● at 4 MHz / maximum
0.025 dB/m
● at 16 MHz / maximum
0.049 dB/m
impedance
● rated value
150 Ω
● at 9.6 kHz
270 Ω
● at 38.4 kHz
185 Ω
● at 3 MHz … 20 MHz
150 Ω
relative symmetrical tolerance
● of the characteristic impedance at 9.6 kHz
10 %
● of the characteristic impedance at 38.4 kHz
10 %
● of the characteristic impedance at 3 MHz … 20 MHz
10 %
loop resistance per length / maximum
138 Ω/km
shield resistance per length / maximum
15 Ω/km
insulation resistance coefficient
20 GΩ·m
operating voltage / maximum
80 V
capacity per length / at 1 kHz
30 pF/m
operating voltage / RMS value
600 V
conductor cross section / of the power line
1.5 mm²
continuous current / of the power lines
12 A
mechanical data
design of the shield
Overlapped aluminum-clad foil, sheathed in a braided screen of tinplated copper wires
number of electrical cores
6
type of electrical connection / FastConnect
No
outer diameter
● of inner conductor
0.67 mm
● of the wire insulation
2.56 mm
● of cable sheath
11 mm
6XV18603PH05
Page 1/2
12.19.2020
Subject to change without notice
© Copyright Siemens
symmetrical tolerance of the outer diameter / of cable
sheath
0.3 mm
material
● of the wire insulation
polyethylene (PE)
● of cable sheath
PVC
color
● of the insulation of data wires
red / green
● of the power line insulation
Black
● of cable sheath
Violet
bending radius
● with multiple bends / minimum permissible
110 mm
number of bending cycles
1000000; For use in cable carriers, for 1 million bending cycles with a
bending radius of 166 mm (15x D) and an acceleration of 4.0 m/s²
tensile load / maximum
300 N
weight per length
154 kg/km
ambient conditions
ambient temperature
● during operation
-30 ... +80 °C
● during storage
-30 ... +80 °C
● during transport
-30 ... +80 °C
● during installation
-30 ... +80 °C
● note
Electrical properties measured at 20 Cel, verification according to DIN
47250 part 4 respectively DIN VDE 0490
fire behavior
flame-retardant according to IEC 60332-3-24 (Category C)
chemical resistance
● to mineral oil
Conditional resistance
● to grease
Conditional resistance
radiological resistance / to UV radiation
resistant
protection class IP
IP65
product features, product functions, product components / general
product feature
● halogen-free
Yes
● silicon-free
Yes
standards, specifications, approvals
UL/ETL listing / 300 V Rating
No
UL/ETL style / 600 V Rating
Yes; CM / CL3 / SunRes / OilRes
certificate of suitability
● EAC approval
Yes
● RoHS conformity
Yes
further information / internet-Links
Internet-Link
● to web page: selection aid TIA Selection Tool
http://www.siemens.com/snst
● to website: Industrial communication
http://www.siemens.com/simatic-net
● to website: Industry Mall
https://mall.industry.siemens.com
● to website: Information and Download Center
http://www.siemens.com/industry/infocenter
● to website: Image database
http://automation.siemens.com/bilddb
● to website: CAx-Download-Manager
http://www.siemens.com/cax
● to website: Industry Online Support
https://support.industry.siemens.com
last modified:
6XV18603PH05
Page 2/2
12/18/2020
12.19.2020
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6XV18603PH05”相匹配的价格&库存,您可以联系我们找货
免费人工找货