Data sheet
US2:87LPU6MH
Pump control panel, Size 5, Three phase full voltage, Solid-state overload
relay, OLR amp range 55-250A, 440-480V 50-60Hz/DC coil, Standard type
contactor, 400A circuit breaker, HOA Sel Sw. & Start P.B., Enclosure
NEMA type 3/3R, Weather proof outdoor use
product brand name
Class 87
design of the product
Pump control panel with MCP
special product feature
Gravity dropout contacts; 45 degree, wedge action contacts; Self-rising
pressure type control terminals; Encapsulated coil
General technical data
weight [lb]
Height x Width x Depth [in]
205 lb
touch protection against electrical shock
NA for enclosed products
installation altitude [ft] at height above sea level maximum
6560 ft
72 × 20 × 11 in
ambient temperature [°F]
● during storage
-22 ... +149 °F
● during operation
-4 ... +104 °F
ambient temperature
● during storage
-30 ... +65 °C
● during operation
-20 ... +40 °C
country of origin
USA
Horsepower ratings
yielded mechanical performance [hp] for 3-phase AC
motor
● at 200/208 V rated value
75 hp
● at 220/230 V rated value
100 hp
● at 460/480 V rated value
200 hp
● at 575/600 V rated value
200 hp
Contactor
size of contactor
NEMA controller size 5
number of NO contacts for main contacts
3
operating voltage for main current circuit at AC at 60 Hz
maximum
600 V
operational current at AC at 600 V rated value
270 A
mechanical service life (switching cycles) of the main
contacts typical
10000000
Auxiliary contact
number of NC contacts at contactor for auxiliary contacts
2
number of NO contacts at contactor for auxiliary contacts
2
number of total auxiliary contacts maximum
8
contact rating of auxiliary contacts of contactor according
to UL
10A@240VAC (A300), 2.5A@250VDC (Q300)
US2:87LPU6MH
Page 1/2
12.19.2020
Subject to change without notice
© Copyright Siemens
Coil
type of voltage of the control supply voltage
AC/DC
control supply voltage
● at DC rated value
440 ... 480 V
● at AC at 50 Hz rated value
440 ... 480 V
● at AC at 60 Hz rated value
440 ... 480 V
holding power at AC minimum
7.4 W
apparent pick-up power of magnet coil at AC
590 V·A
apparent holding power of magnet coil at AC
6.7 V·A
operating range factor control supply voltage rated value
of magnet coil
0.85 ... 1.1
percental drop-out voltage of magnet coil related to the
input voltage
60 %
switch ON delay time
30 ... 95 ms
OFF delay time
40 ... 80 ms
Overload relay
product function
● overload protection
Yes
● phase failure detection
Yes
● asymmetry detection
Yes
● ground fault detection
No
● test function
Yes
● external reset
Yes
reset function
Manual and automatic
trip class
CLASS 10
adjustable current response value current of the currentdependent overload release
55 ... 250 A
product feature protective coating on printed-circuit board
No
number of NC contacts of auxiliary contacts of overload
relay
1
number of NO contacts of auxiliary contacts of overload
relay
1
operational current of auxiliary contacts of overload relay
● at AC at 600 V
5A
● at DC at 250 V
1A
contact rating of auxiliary contacts of overload relay
according to UL
5A@600VAC (B600), 1A@250VDC (R300)
insulation voltage
● with single-phase operation at AC rated value
600 V
● with multi-phase operation at AC rated value
300 V
Enclosure
degree of protection NEMA rating of the enclosure
NEMA 3/3R
design of the housing
Weather proof for outdoor use
Standard Control Devices
product component Hand-Off-Auto selector switch
Yes
type of Hand-Off-Auto selector switch
30mm metal housing with chrome finish
product component start push button
Yes
type of start push button
30mm metal housing with chrome finish
Circuit Breaker
type of the motor protection
Motor circuit protector (magnetic trip only)
operational current of motor circuit breaker rated value
400 A
adjustable current response value current of
instantaneous short-circuit trip unit
2000 ... 4000 A
Mounting/wiring
mounting position
Vertical
fastening method
Surface mounting and installation
type of electrical connection for supply voltage line-side
Box lug
type of connectable conductor cross-sections at line-side
at AWG cables single or multi-stranded
2x (3/0 ... 500 kcmil) or 2x (4/0 ... 500 kcmil)
US2:87LPU6MH
Page 2/3
12.19.2020
Subject to change without notice
© Copyright Siemens
temperature of the conductor for supply maximum
permissible
75 °C
material of the conductor for supply
AL or CU
type of electrical connection for load-side outgoing feeder
Box lug
tightening torque [lbf·in] for load-side outgoing feeder
180 ... 220 lbf·in
type of connectable conductor cross-sections at AWG
cables for load-side outgoing feeder single or multistranded
2x 2/0 AWG ... 500 MCM
temperature of the conductor for load-side outgoing feeder
maximum permissible
75 °C
material of the conductor for load-side outgoing feeder
CU
type of electrical connection of magnet coil
Screw-type terminals
tightening torque [lbf·in] at magnet coil
7 ... 10 lbf·in
type of connectable conductor cross-sections of magnet
coil at AWG cables single or multi-stranded
2x (18 ... 14 AWG)
temperature of the conductor at magnet coil maximum
permissible
75 °C
material of the conductor at magnet coil
CU
type of electrical connection at contactor for auxiliary
contacts
Screw-type terminals
tightening torque [lbf·in] at contactor for auxiliary contacts
7 ... 10 lbf·in
type of connectable conductor cross-sections at contactor
at AWG cables for auxiliary contacts single or multistranded
2x (20 ... 16 AWG), 2x (18 ... 14 AWG)
temperature of the conductor at contactor for auxiliary
contacts maximum permissible
75 °C
material of the conductor at contactor for auxiliary contacts
CU
type of electrical connection at overload relay for auxiliary
contacts
Screw-type terminals
tightening torque [lbf·in] at overload relay for auxiliary
contacts
7 ... 10 lbf·in
type of connectable conductor cross-sections at overload
relay at AWG cables for auxiliary contacts single or multistranded
2x (20 ... 14 AWG)
temperature of the conductor at overload relay for auxiliary
contacts maximum permissible
75 °C
material of the conductor at overload relay for auxiliary
contacts
CU
Short-circuit current rating
design of the short-circuit trip
Instantaneous trip circuit breaker
breaking capacity maximum short-circuit current (Icu)
● at 240 V
100 kA
● at 480 V
100 kA
● at 600 V
25 kA
certificate of suitability
NEMA ICS 2; UL 508
Further information
Industrial Controls - Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:87LPU6MH
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/US/en/ps/US2:87LPU6MH
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:87LPU6MH&lang=en
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:87LPU6MH/certificate
US2:87LPU6MH
Page 3/4
12.19.2020
Subject to change without notice
© Copyright Siemens
US2:87LPU6MH
Page 4/5
12.19.2020
Subject to change without notice
© Copyright Siemens
last modified:
3/11/2020
US2:87LPU6MH
Page 5/5
12.19.2020
Subject to change without notice
© Copyright Siemens