Data sheet
3SU1130-2BL60-1NA0-Z Y11
Selector switch, illuminable, 22 mm, round, plastic with metal front ring,
white, selector switch, short, 3 switch positions I-O-II, latching, actuating
angle 2x45°, 10:30h/12h/13:30h, with holder, 1 NO, 1 NO, screw terminal,
with laser labeling, upper case
product brand name
SIRIUS ACT
product designation
Selector switches
design of the product
Complete unit
product type designation
3SU1
product line
Plastic with metal front ring, matt, 22 mm
manufacturer's article number
● of supplied contact module at position 1
3SU1400-1AA10-1BA0
● of supplied contact module at position 2
3SU1400-1AA10-1BA0
● of the supplied holder
3SU1500-0AA10-0AA0
● of the supplied actuator
3SU1032-2BL60-0AA0
Enclosure
number of command points
1
Actuator
design of the actuating element
Selector, short
principle of operation of the actuating element
latching, 2x45° (10:30 h/12 h/13:30 h)
product extension optional light source
Yes
color of the actuating element
white
material of the actuating element
plastic
shape of the actuating element
round
outer diameter of the actuating element
32.3 mm
marking of the actuating element
Any inscription, text in upper case
number of contact modules
2
number of switching positions
3
actuating angle
● clockwise
45°
● anticlockwise
45°
Front ring
product component front ring
Yes
design of the front ring
standard
material of the front ring
Metal, matt
color of the front ring
sand gray
Holder
material of the holder
Plastic
Display
number of LED modules
0
General technical data
product function positive opening
3SU11302BL601NA0-Z Y11
Page 1/2
No
2.6.2021
Subject to change without notice
© Copyright Siemens
product component light source
No
insulation voltage rated value
500 V
degree of pollution
3
type of voltage of the operating voltage
AC/DC
surge voltage resistance rated value
6 kV
protection class IP
IP66, IP67, IP69(IP69K)
● of the terminal
degree of protection NEMA rating
IP20
1, 2, 3, 3R, 4, 4X, 12, 13
shock resistance
● acc. to IEC 60068-2-27
Sinusoidal half-wave 50g / 11 ms
● for railway applications acc. to DIN EN 61373
Category 1, Class B
vibration resistance
● acc. to IEC 60068-2-6
10 ... 500 Hz: 5g
● for railway applications acc. to DIN EN 61373
Category 1, Class B
operating frequency maximum
1 800 1/h
mechanical service life (switching cycles) typical
1 000 000
electrical endurance (switching cycles) typical
10 000 000
thermal current
10 A
reference code acc. to IEC 81346-2
S
continuous current of the C characteristic MCB
10 A; for a short-circuit current smaller than 400 A
continuous current of the quick DIAZED fuse link
10 A
continuous current of the DIAZED fuse link gG
10 A
● operating voltage at AC
— at 50 Hz rated value
5 ... 500 V
— at 60 Hz rated value
5 ... 500 V
● operating voltage at DC rated value
5 ... 500 V
Power Electronics
contact reliability
One maloperation per 100 million (17 V, 5 mA), one maloperation per 10
million (5 V, 1 mA)
Auxiliary circuit
design of the contact of auxiliary contacts
Silver alloy
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
2
Connections/ Terminals
type of electrical connection of modules and accessories
Screw-type terminal
type of connectable conductor cross-sections
● solid with core end processing
2x (0.5 ... 0.75 mm²)
● solid without core end processing
2x (1.0 ... 1.5 mm²)
● finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
● finely stranded without core end processing
2x (1,0 ... 1,5 mm²)
● at AWG cables
2x (18 ... 14)
tightening torque of the screws in the bracket
● tightening torque with screw-type terminals
1 ... 1.2 N·m
0.8 ... 0.9 N·m
Safety related data
B10 value with high demand rate acc. to SN 31920
300 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920
20 %
● with high demand rate acc. to SN 31920
20 %
failure rate [FIT] with low demand rate acc. to SN 31920
100 FIT
T1 value for proof test interval or service life acc. to
IEC 61508
20 y
Ambient conditions
● ambient temperature during operation
-25 ... +70 °C
● ambient temperature during storage
-40 ... +80 °C
environmental category during operation acc. to IEC
60721
3M6, 3S2, 3B2, 3C3, 3K6 (with relative air humidity of 10 ... 95 %, no
condensation in operation permitted for all devices behind front panel)
Installation/ mounting/ dimensions
3SU11302BL601NA0-Z Y11
Page 2/3
2.6.2021
Subject to change without notice
© Copyright Siemens
fastening method
● of modules and accessories
Front plate mounting
height
40 mm
width
32.3 mm
shape of the installation opening
round
mounting diameter
22.3 mm
positive tolerance of installation diameter
0.4 mm
mounting height
28.8 mm
installation width
32.3 mm
installation depth
49.7 mm
Certificates/ approvals
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3SU1130-2BL60-1NA0-Z Y11
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3SU1130-2BL60-1NA0-Z Y11
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3SU1130-2BL60-1NA0-Z Y11
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3SU1130-2BL60-1NA0-Z Y11&lang=en
3SU11302BL601NA0-Z Y11
Page 3/4
2.6.2021
Subject to change without notice
© Copyright Siemens
last modified: