Data sheet
US2:CLM2F03277
Mechanically held lighting contactor, Contactor amp rating 200Amp 0NC _
3NO poles, 277VAC 60HZ coil, Non-combination type, Enclosure NEMA
type 12, Dust/drip proof for indoors
product brand name
Class CLM
design of the product
Magnetically latched lighting contactor
special product feature
Energy efficient; Quiet operation
General technical data
weight [lb]
Height x Width x Depth [in]
113 lb
touch protection against electrical shock
NA for enclosed products
installation altitude [ft] at height above sea level maximum
6560 ft
country of origin
USA
25 × 18 × 13 in
Contactor
size of contactor
200 Amp
number of NO contacts for main contacts
3
number of NC contacts for main contacts
0
operating voltage for main current circuit at AC at 60 Hz
maximum
600 V
mechanical service life (switching cycles) of the main
contacts typical
5000000
contact rating of the main contacts of lighting contactor
● at tungsten (1 pole per 1 phase) rated value
200A @277V 1p 1ph
● at tungsten (2 poles per 1 phase) rated value
200A @480V 2p 1ph
● at tungsten (3 poles per 3 phases) rated value
200A @480V 3p 3ph
● at ballast (1 pole per 1 phase) rated value
200A @347V 1p 1ph
● at ballast (2 poles per 1 phase) rated value
200A @600V 2p 1ph
● at ballast (3 poles per 3 phases) rated value
200A @600V 3p 3ph
● at resistive load (1 pole per 1 phase) rated value
200A @347V 1p 1ph
● at resistive load (2 poles per 1 phase) rated value
200A @600V 2p 1ph
● at resistive load (3 poles per 3 phases) rated value
200A @600V 3p 3ph
Auxiliary contact
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of total auxiliary contacts maximum
4
contact rating of auxiliary contacts of contactor according
to UL
NA
Coil
type of voltage of the control supply voltage
AC
control supply voltage
● at AC at 60 Hz rated value
US2:CLM2F03277
Page 1/2
277 V
1.21.2021
Subject to change without notice
© Copyright Siemens
apparent pick-up power of magnet coil at AC
900 V·A
apparent holding power of magnet coil at AC
200 V·A
operating range factor control supply voltage rated value
of magnet coil
0.85 ... 1.1
Enclosure
degree of protection NEMA rating of the enclosure
NEMA 12 enclosure
design of the housing
Dust tight and drip proof for indoors
Mounting/wiring
mounting position
Vertical
fastening method
Surface mounting and installation
type of electrical connection for supply voltage line-side
Box lug
tightening torque [lbf·in] for supply
275 ... 300 lbf·in
type of connectable conductor cross-sections at line-side
at AWG cables single or multi-stranded
1x (4 AWG ... 300 kcmil)
temperature of the conductor for supply maximum
permissible
75 °C
material of the conductor for supply
AL or CU
type of electrical connection for load-side outgoing feeder
Box lug
tightening torque [lbf·in] for load-side outgoing feeder
275 ... 300 lbf·in
type of connectable conductor cross-sections at AWG
cables for load-side outgoing feeder single or multistranded
1x (4 AWG ... 300 kcmil)
temperature of the conductor for load-side outgoing feeder
maximum permissible
75 °C
material of the conductor for load-side outgoing feeder
AL or CU
type of electrical connection of magnet coil
Screw-type terminals
tightening torque [lbf·in] at magnet coil
8 ... 12 lbf·in
type of connectable conductor cross-sections of magnet
coil at AWG cables single or multi-stranded
2x (16 ... 12 AWG)
temperature of the conductor at magnet coil maximum
permissible
75 °C
material of the conductor at magnet coil
CU
Short-circuit current rating
design of the fuse link for short-circuit protection of the
main circuit required
none
design of the short-circuit trip
Thermal magnetic circuit breaker
breaking capacity maximum short-circuit current (Icu)
● at 240 V
10 kA
● at 480 V
10 kA
● at 600 V
10 kA
certificate of suitability
NEMA ICS 2; UL 508; CSA 22.2, No. 14
Further information
Industrial Controls - Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:CLM2F03277
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/US/en/ps/US2:CLM2F03277
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:CLM2F03277&lang=en
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:CLM2F03277/certificate
US2:CLM2F03277
Page 2/3
1.21.2021
Subject to change without notice
© Copyright Siemens
US2:CLM2F03277
Page 3/4
1.21.2021
Subject to change without notice
© Copyright Siemens
last modified:
US2:CLM2F03277
Page 4/4
3/11/2020
1.21.2021
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“CLM2F03277”相匹配的价格&库存,您可以联系我们找货
免费人工找货