Data sheet
US2:LCE01C304240A
Electrically held lighting contactor, (convertible to mech. held), Amp rating
30A (tungsten 20A), 3 N.C. / 4 N.O. poles, 230-240V 60Hz/220V 50Hz coil,
Non-combination type, Enclosure NEMA type 1, Indoor general purpose
use
product brand name
Class LC
design of the product
Electrically held lighting contactor (convertible to mechanically held)
special product feature
Electrically held convertible to mechanically held; Power poles
convertible between NO and NC
General technical data
weight [lb]
Height x Width x Depth [in]
11 lb
touch protection against electrical shock
NA for enclosed products
installation altitude [ft] at height above sea level maximum
6560 ft
14 × 8 × 7 in
ambient temperature [°F]
● during storage
-22 ... +149 °F
● during operation
-13 ... +104 °F
ambient temperature
● during storage
-30 ... +65 °C
● during operation
-25 ... +40 °C
country of origin
USA
Contactor
size of contactor
30 Amp
number of NO contacts for main contacts
4
number of NC contacts for main contacts
3
operating voltage for main current circuit at AC at 60 Hz
maximum
600 V
mechanical service life (switching cycles) of the main
contacts typical
100000
contact rating of the main contacts of lighting contactor
● at tungsten (1 pole per 1 phase) rated value
20A @277V 1p 1ph
● at tungsten (2 poles per 1 phase) rated value
20A @480V 2p 1ph
● at tungsten (3 poles per 3 phases) rated value
20A @480V 3p 3ph
● at ballast (1 pole per 1 phase) rated value
30A @347V 1p 1ph
● at ballast (2 poles per 1 phase) rated value
30A @600V 2p 1ph
● at ballast (3 poles per 3 phases) rated value
30A @600V 3p 3ph
● at resistive load (1 pole per 1 phase) rated value
30A @600V 1p 1ph
● at resistive load (2 poles per 1 phase) rated value
30A @600V 2p 1ph
● at resistive load (3 poles per 3 phases) rated value
30A @600V 3p 3ph
Auxiliary contact
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
US2:LCE01C304240A
Page 1/2
1.22.2021
Subject to change without notice
© Copyright Siemens
number of total auxiliary contacts maximum
4
contact rating of auxiliary contacts of contactor according
to UL
NA
Coil
type of voltage of the control supply voltage
AC
control supply voltage
● at AC at 50 Hz rated value
220 V
● at AC at 60 Hz rated value
230 ... 240 V
apparent pick-up power of magnet coil at AC
248 V·A
apparent holding power of magnet coil at AC
28 V·A
operating range factor control supply voltage rated value
of magnet coil
0.85 ... 1.1
Enclosure
degree of protection NEMA rating of the enclosure
NEMA Type 1
design of the housing
Indoor general purpose use
Mounting/wiring
mounting position
Vertical
fastening method
Surface mounting and installation
type of electrical connection for supply voltage line-side
Screw-type terminals
tightening torque [lbf·in] for supply
35 ... 35 lbf·in
type of connectable conductor cross-sections at line-side
at AWG cables single or multi-stranded
2x (14 ... 8 AWG)
temperature of the conductor for supply maximum
permissible
75 °C
material of the conductor for supply
CU
type of electrical connection for load-side outgoing feeder
Screw-type terminals
tightening torque [lbf·in] for load-side outgoing feeder
35 ... 35 lbf·in
type of connectable conductor cross-sections at AWG
cables for load-side outgoing feeder single or multistranded
2x (14 ... 8 AWG)
temperature of the conductor for load-side outgoing feeder
maximum permissible
75 °C
material of the conductor for load-side outgoing feeder
CU
type of electrical connection of magnet coil
Screw-type terminals
tightening torque [lbf·in] at magnet coil
15 ... 15 lbf·in
type of connectable conductor cross-sections of magnet
coil at AWG cables single or multi-stranded
2x (18 ... 14 AWG)
temperature of the conductor at magnet coil maximum
permissible
75 °C
material of the conductor at magnet coil
CU
Short-circuit current rating
design of the fuse link for short-circuit protection of the
main circuit required
100kA@600V (Class R or J 40A max)
design of the short-circuit trip
Thermal magnetic circuit breaker
breaking capacity maximum short-circuit current (Icu)
● at 240 V
24 kA
● at 480 V
65 kA
● at 600 V
25 kA
certificate of suitability
NEMA ICS 2; UL 508
Further information
Industrial Controls - Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:LCE01C304240A
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/US/en/ps/US2:LCE01C304240A
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:LCE01C304240A&lang=en
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:LCE01C304240A/certificate
US2:LCE01C304240A
Page 2/3
1.22.2021
Subject to change without notice
© Copyright Siemens
US2:LCE01C304240A
Page 3/4
1.22.2021
Subject to change without notice
© Copyright Siemens
last modified:
US2:LCE01C304240A
Page 4/4
3/11/2020
1.22.2021
Subject to change without notice
© Copyright Siemens