Data sheet
US2:LEN01F003120A
Electrically held lighting contactor, Contactor amp rating 200A, 0 N.C. / 3
N.O. Poles, 110VAC 50HZ/120VAC 60HZ coil, Non-combination type, (no
disconnect device), Enclosure NEMA type 1, Indoor general purpose use
product brand name
Class LE
design of the product
Electrically held lighting contactor
special product feature
Compact design; Finger safe control terminals
General technical data
weight [lb]
35 lb
Height x Width x Depth [in]
25 × 18 × 13 in
touch protection against electrical shock
NA for enclosed products
installation altitude [ft] at height above sea level maximum
6560 ft
ambient temperature [°F]
● during storage
-67 ... +176 °F
● during operation
32 ... 104 °F
ambient temperature
● during storage
-55 ... +80 °C
● during operation
0 ... 40 °C
country of origin
USA
Contactor
size of contactor
200 Amp
number of NO contacts for main contacts
3
number of NC contacts for main contacts
0
operating voltage for main current circuit at AC at 60 Hz
maximum
600 V
mechanical service life (switching cycles) of the main
contacts typical
10000000
contact rating of the main contacts of lighting contactor
● at tungsten (1 pole per 1 phase) rated value
200A @277V 1p 1ph
● at tungsten (2 poles per 1 phase) rated value
200A @480V 2p 1ph
● at tungsten (3 poles per 3 phases) rated value
200A @480V 3p 3ph
● at ballast (1 pole per 1 phase) rated value
200A @347V 1p 1ph
● at ballast (2 poles per 1 phase) rated value
200A @600V 2p 1ph
● at ballast (3 poles per 3 phases) rated value
200A @600V 3p 3ph
● at resistive load (1 pole per 1 phase) rated value
200A @600V 1p 1ph
● at resistive load (2 poles per 1 phase) rated value
200A @600V 2p 1ph
● at resistive load (3 poles per 3 phases) rated value
200A @600V 3p 3ph
Auxiliary contact
number of NC contacts at contactor for auxiliary contacts
2
number of NO contacts at contactor for auxiliary contacts
2
number of total auxiliary contacts maximum
4
contact rating of auxiliary contacts of contactor according
to UL
A300 / Q300
US2:LEN01F003120A
Page 1/2
7/6/2022
Subject to change without notice
© Copyright Siemens
Coil
type of voltage of the control supply voltage
AC/DC
control supply voltage
● at DC rated value
110 ... 127 V
● at AC at 50 Hz rated value
110 ... 127 V
● at AC at 60 Hz rated value
110 ... 127 V
apparent pick-up power of magnet coil at AC
300 VA
apparent holding power of magnet coil at AC
5.8 VA
operating range factor control supply voltage rated value
of magnet coil
0.85 ... 1.1
Enclosure
degree of protection NEMA rating of the enclosure
NEMA 1 enclosure
design of the housing
indoors, usable on a general basis
Mounting/wiring
mounting position
Vertical
fastening method
Surface mounting and installation
type of electrical connection for supply voltage line-side
Screw-type terminals
tightening torque [lbf·in] for supply
90 ... 110 lbf·in
type of connectable conductor cross-sections at line-side
at AWG cables single or multi-stranded
2x (6 ... 3/0 AWG)
temperature of the conductor for supply maximum
permissible
75 °C
material of the conductor for supply
CU
type of electrical connection for load-side outgoing feeder
Screw-type terminals
tightening torque [lbf·in] for load-side outgoing feeder
90 ... 110 lbf·in
type of connectable conductor cross-sections at AWG
cables for load-side outgoing feeder single or multistranded
2x (6 ... 3/0 AWG)
temperature of the conductor for load-side outgoing feeder
maximum permissible
75 °C
material of the conductor for load-side outgoing feeder
CU
type of electrical connection of magnet coil
Screw-type terminals
tightening torque [lbf·in] at magnet coil
7 ... 10 lbf·in
type of connectable conductor cross-sections of magnet
coil at AWG cables single or multi-stranded
2x (18 ... 14 AWG)
temperature of the conductor at magnet coil maximum
permissible
75 °C
material of the conductor at magnet coil
CU
Short-circuit current rating
design of the fuse link for short-circuit protection of the
main circuit required
none
design of the short-circuit trip
Thermal magnetic circuit breaker
breaking capacity maximum short-circuit current (Icu)
● at 240 V
100 kA
● at 480 V
100 kA
● at 600 V
25 kA
certificate of suitability
NEMA ICS 2; UL 508
Further information
Industrial Controls - Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:LEN01F003120A
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/US/en/ps/US2:LEN01F003120A
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:LEN01F003120A&lang=en
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:LEN01F003120A/certificate
last modified:
US2:LEN01F003120A
Page 2/2
1/25/2022
7/6/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“LEN01F003120A”相匹配的价格&库存,您可以联系我们找货
免费人工找货