Selectable Output Chimes and Chime/Strobes SpectrAlert® Advance selectable-output chimes and chime/strobes are rich with features guaranteed to cut installation times and maximize profits. SpectrAlert Advance selectable-output chimes and chime/ strobes are private mode notification appliances used to alert trained personnel to investigate possible emergency situations and to take appropriate action. Security guard and nurse workstations are ideal locations for chime products. SpectrAlert Advance chimes and chime/strobes are rich with features guaranteed to cut installation times and maximize profits. The SpectrAlert Advance Series of notification appliances is designed to simplify your installations, with features such as plug-in designs, instant feedback messages to ensure correct installation of individual devices, and seven field-selectable candela settings for chime/ strobes. More specifically, when installing SpectrAlert Advance products, first attach a universal mounting plate to a four-inch square, four-inch octagon, single-gang, or double-gang junction box. Then, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate. Finally, attach the chime or chime/strobe to the mounting plate by inserting the product’s tabs in the mounting plate’s grooves. The device is rotated into position, locking the product’s pins into the mounting plate’s terminals. The device will temporarily hold in place with a catch until it is secured with a captive mounting screw. SpectrAlert Advance products allow you to choose: • 12 or 24 volts • t 24 volts, 15, 15/75, 30, 75, 95, 110, or 115 candela by way of rearA mounted slide switch and front view window • Select chime tones and volume using a simple rotary switch Features • Plug-in design • Shorting spring on mounting plate for pre-installation continuity check • Captive mounting screw • Torx screw for tamper resistance • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Minimal intrusion into the back box • Rotary switch for tone selection • Two volume settings • Electrically compatible with existing SpectrAlert products • Listed for ceiling or wall mounting Agency Listings S4011 3023572 MEA452-05-E 7125-1653:188 (chime/strobes) 7125-1653:189 (chimes) SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance chimes and chime/strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, single-gang 2 × 4 × 17/8-inch back box, or double-gang back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full-wave rectified, unfiltered power supply. Chime/ strobes shall have field-selectable candela settings of 15, 15/75, 30, 75, 95, 110 and 115. Chime/Strobe Combination The chime/strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1638 and UL 464. The chime/strobe shall comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The chime shall have two audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. Synchronization Module The module shall be a System Sensor Sync•Circuit _______ listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1Hz and chimes at temporal three. Also, while operating the strobes, the module shall silence the chimes on chime/strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR1 Operating Voltage Range2 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal) Input terminal wire gauge 12 to 18 AWG Chime/strobe dimensions (including lens) 5.6 in L × 4.7 in W × 2.5 in D (142 mm L × 119 mm W × 64 mm D) Chime dimensions 5.6 in L × 4.7 in W × 1.3 in D (142 mm L × 119 mm W × 33 mm D) BBS-2 (red back box skirt) 5.9 in L × 5.0 in W × 2.2 in D (151 mm L × 128 mm W × 56 mm D) BBSW-2 (white back box skirt) 5.9 in L × 5.0 in W × 2.2 in D (151 mm L × 128 mm W × 56 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-filtered, time varying power source that is used on some power supply and panel outputs. 2. CHS products will operate at 12 V nominal only for 15 and 15/75 cd. A05-0396-003 UL Current Draw Data UL Max. Chime Current Draw (mA RMS) 8–17.5 Volts Sound Pattern dB DC FWR 1 Second Chime High 34 50 1 Second Chime Low 30 51 ¼ Second Chime High 34 51 ¼ Second Chime Low 31 51 Temporal Chime High 30 50 Temporal Chime Low 30 47 5 Second Whoop High 32 52 5 Second Whoop Low 30 40 Coded High 48 49 16–33 Volts DC FWR 58 51 51 54 50 50 50 52 48 54 50 51 34 54 34 52 50 50 * *This data represents coding at 3 chimes per second. Actual current draw will vary depending upon coding selected. UL Max. Chime/Strobe Current Draw (mA RMS) 8–17.5 Volts DC Input 15 15/75 1 Second Chime High 131 142 1 Second Chime Low 131 142 1/4 Second Chime High 129 142 1/4 Second Chime Low 129 142 Temporal Chime High 125 142 Temporal Chime Low 129 141 5 Second Whoop High 133 145 5 Second Whoop Low 130 143 One Time Chime * 127 141 8–17.5 Volts FWR Input 15 15/75 1 Second Chime High 128 150 1 Second Chime Low 127 150 1/4 Second Chime High 129 149 1/4 Second Chime Low 128 149 Temporal Chime High 128 148 Temporal Chime Low 125 147 5 Second Whoop High 136 152 5 Second Whoop Low 132 150 One Time Chime * 127 147 *Chime/Strobes cannot be powered with a coded supply. 16–33 Volts 15 65 64 66 64 64 65 70 66 64 16–33 Volts 15 72 71 72 71 71 71 84 77 72 15/75 76 75 75 74 74 75 81 77 76 15/75 82 81 82 81 81 81 93 86 82 30 94 92 95 91 91 92 99 95 93 30 98 97 99 97 97 97 110 102 97 75 160 157 159 155 156 155 165 160 156 75 158 157 160 154 157 156 170 161 157 95 185 183 184 181 181 180 189 186 182 95 183 182 183 179 179 180 193 184 181 110 207 203 205 204 205 200 210 206 203 110 202 202 203 196 199 200 212 203 200 115 213 212 212 211 211 209 217 214 210 115 210 210 211 205 206 206 220 214 210 Tone Selection Chime tone selection is accomplished by using the rotary switch on the back of the product. The current draw and sound measurements for various chime tone settings are listed below. Chime Patterns Setting 1 2 3 4 5 6 7 8 9 Chime and Chime/Strobe Output (dBA) Repetition Rate 1 Second Chime 1 Second Chime ¼ Second Chime ¼ Second Chime Temporal Chime Temporal Chime 5 Second Whoop 5 Second Whoop One Test Chime/coded dB Level High Low High Low High Low High Low High Switch Position 1 2 3 4 5 6 7 8 9 Sound Pattern 1 Second Chime 1 Second Chime ¼ Second Chime ¼ Second Chime Temporal Chime Temporal Chime 5 Second Whoop 5 Second Whoop One Test Chime/coded dB High Low High Low High Low High Low High 8–17.5 Volts DC FWR 58 59 53 54 63 64 58 59 62 64 55 57 68 71 62 64 57 55 16–33 Volts DC FWR 61 61 55 55 66 66 60 60 68 69 60 60 75 77 67 68 51 57 A05-0396-003 SpectrAlert Advance Dimensions 4.7˝ 1.3˝ 4.7˝ 2.5˝ 5.0˝ 2.2˝ Dia. 6.8˝ 5.9˝ 2.5˝ 5.6˝ 5.6˝ Chime Chime/Strobe BBS-2/BBSW-2 SpectrAlert Advance Ordering Information Model CHR CHW CHSR CHSW Accessories BBS-2 BBSW-2 Description Chime, Red Chime, White Chime/Strobe, Red Chime/Strobe, White Back Box Skirt, Wall, Red Back Box Skirt, Wall, White CHSR Red Chime Strobe CHSW White Chime Strobe CHR Red Chime CHW White Chime 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2007 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0396-003 • 12/07 • #1890
CHR
1. 物料型号: - CHR:红色报警器 - CHW:白色报警器 - CHSR:红色报警器/闪光灯 - CHSW:白色报警器/闪光灯 - BBS-2:红色后盒裙边(墙面) - BBSW-2:白色后盒裙边(墙面)

2. 器件简介: SpectrAlert Advance系列报警器和报警器/闪光灯是具有多种特性的私人模式通知设备,用于提醒训练有素的人员调查可能的紧急情况并采取适当的行动。它们适合安装在保安和护士工作站。

3. 引脚分配: 报警器电路接线应连接到通用安装板上的SEMS端子。

4. 参数特性: - 操作电压:12或24伏 - 闪光强度设置:15, 15/75, 30, 75, 95, 110, 115 - 工作温度:32°F至120°F(0°C至49°C) - 湿度范围:10至93%非凝结 - 闪光灯速率:每秒1次 - 电源:12DC/FWR或24DC/FWR - 操作电压范围:8至17.5V(12V标称)或16至33V(24V标称)

5. 功能详解: - 插入式设计 - 安装板上的短路弹簧,用于预安装连续性检查 - 防篡改的Torx螺钉 - 现场可调的坎德拉设置 - 自动选择12或24伏操作 - 旋转开关用于音调选择 - 两种音量设置 - 与现有的SpectrAlert产品电气兼容 - 适用于天花板或墙面安装

6. 应用信息: SpectrAlert Advance产品适用于需要快速安装和最大化利润的场合,如紧急情况警报。

7. 封装信息: - 报警器/闪光灯尺寸:5.6英寸L x 4.7英寸W x 2.5英寸D(142毫米L x 119毫米W x 64毫米D) - 报警器尺寸:5.6英寸L x 4.7英寸W x 1.3英寸D(142毫米L x 119毫米W x 33毫米D) - BBS-2/BBSW-2尺寸:5.9英寸L x 5.0英寸W x 2.2英寸D(151毫米L x 128毫米W x 56毫米D)

很抱歉,暂时无法提供与“CHR”相匹配的价格&库存,您可以联系我们找货