www.emea.tdk-lambda.com/hws-me
• Limited Lifetime Warranty
• Medical Approvals
• Universal Input (85 - 265VAC)
• High Efficiency
HWS-/ME Series
Single Output
Medical Power Supplies
HWS-/ME Features and Benefits
Features
• Limited Lifetime Warranty
• Medical Approvals
• Wide Range AC Input
Specifications
ITEM
Input Voltage
Input Current (Typ)
Inrush Current
Power Factor / Flicker
Temperature Coefficient
Overcurrent Protection
Overvoltage Protection
Hold Up Time (Typ)
Leakage Current (60Hz)
Remote Sense
Indicator
Remote On/Off
Parallel operation
DC Good
Voltage Programming
Operating Temperature
and Derating
Storage Temperature
Humidity (non condensing)
Cooling
Withstand Voltage
Isolation Resistance
Vibration (non operating)
Shock (in packaging)
Safety Agency Approvals
Line Dip
Conducted & Radiated EMI
Immunity
Weight (Typ)
Size (WxHxD)
(with cover except 30 & 50W)
MTBF (5)
Warranty
• Broad 30W to 1500W product range
• RoHS Compliant Design
Key Market Segments & Applications
Medical
Industrial
Test
Broadcast
Comm
LED
Cots
Benefits
• Lower Cost of Ownership
• Reduces System Approval Times
• Supports Global Use
MODELS
(4)
(1)
(1)
(2)
A
A
V
ms
mA
-
-
(3)
(2)
°C
g
mm
hrs
HWS30A
HWS100A
HWS300
HWS600
HWS1000
HWS1500
HWS50A
HWS150A
85-265VAC (47-63Hz) or 120-370VDC
85-265VAC (47-63Hz) or 120-330VDC
85-265VAC (47-63Hz)
0.65 / 0.4
1.3 / 0.65
0.65 / 0.35
1.9 / 0.95
4.1 / 2.1
8.1 / 3.9
13.5/7.0
19/10
14 / 28
20 / 40
Meets EN61000-3-2, EN61000-3-3
104%
Yes (See table on page 2)
20
100MΩ at 25°C & 70%RH, Output to Ground 500VDC, >10MΩ Output to remote on/off 100VDC
10 - 55Hz (1 min sweep), 19.6m/s2 constant, X, Y, Z axis, one hour each
< 196.1m/s2
ES60601-1, EN60601-1, CSA-C22.2 No6011-M90 (C-UL) (basic insulation), CE Mark
Complies with SEMI F47 (200VAC line only)
EN55011 / EN55022-B, FCC-B, VCCI-B (HWS600 & 1500 Class A)
IEC61000-4-2, -3, -4, -5, -6, -8, -11, IEC61000-6-2
220
450
280
500
1000
1600
3200
3800
26 x 82 x 95
33 x 82 x 160
26 x 82 x 120
42 x 82 x 160
61 x 82 x 165 100 x 82 x 165 126.5 x 82 x 240 280 x 82 x 126.5
8,169,868
2,963,512
2,145,809
1,998,996
1,087,031
1,152,309
3,726,622
2,676,081
Limited Lifetime Warranty (See TDK-Lambda terms & conditions)
HWS-/ME Series
1
Notes from page 1: (1) 100/200VAC input. (2) See clause 19.5DV.2 of UL60601 for equipment in proximity of patient.
(3) HWS300-600 2.5kVAC Input to ground. (4) Consult Sales Office for use under DC Input conditions
(5) According to Telcordia document SR-332, issue 3 "Reliability Prediction Procedure for Electronic Equipment"
Conditions: ambient temp. 25°C, 230Vac input, full load (figures shown for 24V models)
Model Selector
Model
HWS30A-5/ME
HWS50A-5/ME
HWS100A-5/ME
HWS150A-5/ME
HWS600-5/ME
HWS30A-12/ME
HWS50A-12/ME
HWS100A-12/ME
HWS150A-12/ME
HWS300-12/ME
HWS600-12/ME
HWS30A-15/ME
HWS50A-15/ME
HWS100A-15/ME
HWS150A-15/ME
HWS300-15/ME
HWS600-15/ME
HWS30A-24/ME
HWS50A-24/ME
HWS100A-24/ME
HWS150A-24/ME
HWS300-24/ME
HWS600-24/ME
HWS1000-24/ME
HWS1500-24/ME
HWS1000-36/ME
HWS1500-36/ME
HWS30A-48/ME
HWS50A-48/ME
HWS100A-48/ME
HWS150A-48/ME
HWS300-48/ME
HWS600-48/ME
HWS1000-48/ME
HWS1500-48/ME
Voltage
5V
5V
5V
5V
5V
12V
12V
12V
12V
12V
12V
15V
15V
15V
15V
15V
15V
24V
24V
24V
24V
24V
24V
24V
24V
36V
36V
48V
48V
48V
48V
48V
48V
48V
48V
Adjust
Range
4.0 - 6.0
4.0 - 6.0
4.0 - 6.0
4.0 - 6.0
4.0 - 6.0
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
9.6 - 14.4
12.0 - 18.0
12.0 - 18.0
12.0 - 18.0
12.0 - 18.0
12.0 - 18.0
12.0 - 18.0
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
19.2 - 28.8
4.8 - 28.8(7)
28.8 - 43.2
7.2 - 43.2(6)
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
38.4 - 52.8
38-4 - 52.8
9.6- 52.8(6)
Max
Curr(A)4
6
10
20
30
120
2.5
4.3
8.5
13
27
53
2
3.5
7
10
22
43
1.3
2.2
4.5
6.5
14 (16.5 pk)
27 (31 pk)
46 (58.5 pk)
65/70(1)
(105pk(5))
30.7 (39 pk)
42/46.5(1)
(70 pk)(5)
0.65
1.1
2.1
3.3
7
13
23
32
Max
Load
Line
Ripple
Power(W) Reg(mV) Reg(mV) Noise(mV)
30
50
100
150
600
30
51.6
102
156
324
636
30
52.5
105
150
330
645
31.2
52.8
108
156
336
648
1104
1560/1680(1)
(2520 pk(5))
1104
1512/1674(1)
(2520 pk(5))
31.2
52.8
100.8
158.4
336
624
1104
1536
40
40
40
40
30
96
96
96
96
72
72
120
120
120
120
90
90
192
192
192
192
144
144
150
144
150
150
384
384
384
384
288
288
300
288
(4) Peak load for 10s maximum on time, 35% duty cycle
(5)
200-265AC Input
(6) Using voltage programming input - see installation manual for details
Options
Suffix
Blank
/A
2
Description
No cover (except HWS300-1500 cover fitted) as standard
Cover fitted (egHWSA100-24/MEA)
HWS-/ME Series
20
20
20
20
20
48
48
48
48
48
48
60
60
60
60
60
60
96
96
96
96
96
96
96
96
120
120
120
120
120
150
150
150
150
150
150
150
150
150
150
150
150
200
150
150
150
150
150
150
200
192
192
192
192
192
192
192
192
200
200
200
200
350
350
200
200
144
144
200
200
Overvoltage Efficiency
(V)
(typ)%1
6.25-7.25
6.25-7.25
6.25-7.25
6.25-7.25
6.25-7.25
15-17.4
15-17.4
15-17.4
15-17.4
15-17.4
15-17.4
18.8-21.8
18.8-21.8
18.8-21.8
18.8-21.8
18.8-21.8
18.8-21.8
30-34.8
30-34.8
30-34.8
30-34.8
30-34.8
30-34.8
30-34.8
30-34.8
77/80
82/84
83/86
83/86
80/83
81/83
81/83
83/86
83/86
80/83
80/83
81/83
81/83
83/86
83/86
82/85
81/84
83/86
82/84
84/87
85/88
82/85
82/85
85/87
84/88
55.2-64.8
55.2-64.8
55.2-64.8
55.2-64.8
55.2-64.8
55.2-64.8
55.2-60
55.2-64.8
82/83
83/85
84/87
85/88
82/85
83/86
86/88
86/90
45-49.7
34-49.7
85/88
84/88
Outline Drawing HWS100A/MEA Series
,13879$&$
+]
2873879$
(+)3
5
,13879$&$+]
2873879$
,13879$&$+]
2873879$
Outline Drawing HWS300 Series
OUTPUT : 24V
14A
INPUT : 100-240VAC
4.7A MAX. 50/60Hz
OUTPUT : 24V 14A
CN1
CN2
2
1
+S +Vm
-S
-Vm
COM PC
EN60601-1
NC NC
TOG CNT
TOG PF
12
11
OUTPUT : 24V
14A
Outline Drawing HWS1500 Series
12
2
11
1
(+)
EN60601-1
INPUT : 100-240VAC 20 A MAX.
50 / 60Hz
2
1
12
11
(+)
EN60601-1
INPUT : 100-240VAC 20 A MAX.
50 / 60Hz
HWS-/ME Series
3
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +33 1 60 12 71 65
tlf.fr.powersolutions@tdk.com
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
tla.powersolutions@tdk.com
www.us.lambda.tdk.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
tlf.it.powersolutions@tdk.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
tlf.nl.powersolutions@tdk.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
tlg.powersolutions@tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
tlc.powersolutions@tdk.com
www.lambda.tdk.com.cn
Austria Sales Office
Tel: +43 2256 655 84
tlg.at.powersolutions@tdk.com
TDK-Lambda Singapore Pte Ltd.
Switzerland Sales Office
Tel: +65 6251 7211
tls.marketing@tdk.com
www.sg.lambda.tdk.com
Tel: +41 44 850 53 53
tlg.ch.powersolutions@tdk.com
TDK India Private Limited, Power Supply Division
www.emea.lambda.tdk.com/at
www.emea.lambda.tdk.com/ch
Tel: +91 80 4039-0660
mathew.philip@tdk.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
tlg.dk.powersolutions@tdk.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
tlu.powersolutions@tdk.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
tli.powersolutions@tdk.com
www.emea.lambda.tdk.com/il-en
HWS-/ME Oct16 v6
4
HWS-/ME Series
For Additional Information, please visit
https://product.tdk.com/en/power/
很抱歉,暂时无法提供与“HWS30A-15/ME”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+513.593631+61.38370
- 10+494.4948110+59.10105
- 25+470.8379425+56.27363
- 50+451.7309450+53.99000