TDK-Lambda
RDS60-24
SPECIFICATIONS
B028-01-01E
MODEL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
ITEMS
Nominal Output Voltage
Maximum Output Current
Maximum Output Power
Efficiency (Typ)
Input Voltage Range
Input Current (Typ)
Inrush Current (Typ)
Output Voltage Range
Maximum Ripple
Maximum Ripple & Noise
Maximum Line Regulation
Maximum Load Regulation
Temperature Coefficient
Over Current Protection
Over Voltage Protection
Remote ON/OFF control
Parallel Operation
Series Operation
Operating Temperature
Operating Humidity
Storage Temperature
Storage Humidity
Cooling
Withstand Voltage
25
26
Isolation Resistance
Vibration
-
27
Shock
-
28
Safety
-
29
30
31
Conducted Emission
Radiated Emission
Immunity
-
(*1)
(*1)
(*1)
(*8)
(*2)
(*2)
(*3)
(*4)
(*5)
(*6)
(*7)
V
A
W
%
A
V
mV
mV
mV
mV
A
V
-
RDS60-24-5
RDS60-24-12
RDS60-24-15
RDS60-24-24
5
12
60
78
12
5
60
15
4
60
24
2.5
60
80
79
18 - 32VDC
3.3
4.7A at Cold Start
4.5 - 5.5
10.8 - 13.2
13.5 - 16.5
21.6 - 26.4
50
80
80
100
100
170
200
290
40
96
120
192
100
100
100
200
Less than 0.02 %/℃
12.3 - 13.8
5.2 - 6.0
4.2 - 4.9
2.6 - 3.1
6.0 - 7.5
15.0 - 18.0
17.6 - 22.5
28.0 - 36.0
Possible
Possible
-20 - +60°C (-20 - +50°C:100%, +60°C:70%)
20 - 95%RH (No Condensing)
-25 - +75°C
20 - 95%RH (No Condensing)
Convection Cooling
I/P - O/P, I/P - FG : 2kVAC (10mA) for 1min.,
O/P - CNT(RC) : 100VAC (100mA) for 1min.
O/P - FG : 500VDC 100Mohm, O/P - CNT(RC) : 100VDC 10Mohm
10 - 55Hz : 19.6m/s 2, X,Y,Z 1hour each.
Designed to meet JIS E 3014-2-B
294m/s2 (time : 6±3ms)
Designed to meet JIS E 3015-2-B
Approved by UL60950-1 & CSA60950-1,
Designed to meet EN60950-1
Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A
Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A
Designed to meet IEC61000-4-2(Level 2,3), -4(Level 3), -8(Level 4)
32 Weight (Typ)
g
550
33 Size (W x H x D)
mm
43 x 95 x 160 ( Refer to Outline Drawing )
*Read instruction manual carefully, before using the power supply unit.
=NOTES=
*1. At 24VDC, Ta=25°C, nominal output voltage and maximum output power.
*2. Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz.
*3. 18 - 32VDC, constant load.
*4. No load-Full load, constant input voltage.
*5. OCP TYPE : Constant current limit with automatic recovery.
*6. OVP circuit will shut the output down, manual reset (Re power on).
*7. Ratings
- Derating at standard mounting. Refer to output derating curve(B028-01-02_).
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
*8. At 24VDC Input.(Refer to instruction manual.)
TDK-Lambda
RDS60-24
OUTPUT DERATING
B028-01-02A
*COOLING : CONVECTION COOLING
LOAD (%)
Ta (°C)
-20 - +40
50
60
MOUNTING A
100
100
70
MOUNTING B
100
70
-
OUTPUT DERATING CURVE
120
LOAD (%)
100
80
MOUNTING A
60
MOUNTING B
40
20
0
-20
-10
0
10
20
30
40
50
60
70
80
Ta (°C)
DON'T USE
MOUNTING A
(STANDARD MOUNTING)
MOUNTING B
MOUNTING C
MOUNTING D
MOUNTING E