Industrial Power Supplies
TCL Series, 24–120 Watt Features ◆ For Industrial, Office and Residential
Application
UL 60950 UL 508C
◆ Ultracompact Plastic Housing ◆ Connection by Cage Clamps Terminals
or plugable Screw Terminals
◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ NEW◆ ◆
Reliable snap-on Mounting on DIN-Rails Adaptor for Wall Mounting Universal Input 85-264 VAC, 50/60 Hz Models with 5, 12, 24 and 48 VDC Output Output Voltage adjustable Power Good Signal Low Ripple and Noise Overload and Short-Circuit Protection Parallel Operation possible Worldwide Safety Approvals Redundancy Module 3 Year Product Warranty
The TRACOPOWER TCL series are a family of DIN-Rail power supplies with an excellent price/performance ratio. With tightly regulated output voltage and high immunity against electrical disturbances on the mains they provide a reliable power source for sensitive loads in industrial process controls, machine tools and other equipment exposed to a difficult industrial environment. Compact size, light weight, easy snap-on mounting on DIN-rails and the choice of two connection terminal versions are other features of these power supplies. The TCL series complies with all mayor safety standards for Europe (EN60950, EN50178), North America (UL/ cUL60950, UL508C listed) or elsewhere in the world (with CB-Report IEC60950).
Models
Ordercode TCL 024-105 TCL 024-112 TCL 024–124 TCL 060–112 TCL 060–124 TCL 060–148 TCL 120–112 TCL 120–124 TCL 024–124C TCL 060–112C TCL 060–124C TCL 060–148C TCL 120–112C TCL 120–124C 120 W 60 W 85 –264 VAC Universal Input 50 / 60 Hz 120 W 24 W 60 W 24 W Input Voltage Range Output Power max. *Output Voltage nom. 5.1 VDC 12 VDC 24 VDC 12 VDC 24 VDC 48 VDC 12 VDC 24 VDC 24 VDC 12 VDC 24 VDC 48 VDC 12 VDC 24 VDC *Output adjustable http://www.tracopower.com Page 1 of 5 Output Current max. 4.0 A 2.0 A 1.0 A 4.0 A 2.5 A 1.25 A 8.0 A 5.0 A 1.0 A 4.0 A 2.5 A 1.25 A 8.0 A 5.0 A Cage-Clamps Detachable Screw Terminal Block Connection
Industrial Power Supplies
TCL Series Input Specifications
Input voltage range output derating at operation between 85...93VAC/85...130VDC: 85...264 VAC / 85...375 VDC 15% for TCL 060 & TCL 120 models 20% for TCL 024-112 & TCL 024-124 30% for TCL 024-105 47 – 63 Hz EN610000-3-2 Class A 115 VAC TCL 24 models: 0.35 A TCL 60 models: 1.2 A TCL 120 models: 2.0 A 5.0 A 5.1 VDC model: 12 VDC models: 24 VDC models: 48 VDC models: 5.0 – 5.25 VDC 12 – 15 VDC (12 - 16 VDC for TCL 024-112) 24 – 28 VDC 48 – 56 VDC 2.5% (1% for TCL 60-112) < 50 mV pk-pk current limitation at 120 % typ (constant current, automatic recovery TCL 24 models: foldback, automatic recovery) output current characteristic suitable for parallel operation of max. 5 units 5.1 VDC model: < 6.5 VDC 12 / 24 VDC models: < 40 VDC 48 VDC models: < 60 VDC 115 VAC min. 15 ms trigger point 12 VDC models: >11V 24 VDC models: >22V 48 VDC models: >44V 230 VAC min. 125 ms output signal (reference to – Vout) 11.0 V ±1.0V / 60 mA max. 22.0 V ±2.0V / 30 mA max. 44.0 V ±4.0V / 15 mA max. 230 VAC 0.2 A 0.6 A 1.0 A
24–120 Watt
Input frequency Harmonic limits Input current at full load (typ.)
Recommended circuit breaker ( characteristic C or slow blow fuse)
Output Specifications
Output voltage adj. range (pot.meter on frontpanel)
Output regulation (10 to 90% load variation) Ripple and Noise (20MHz Bandwidth) Electronic short circuit protection
Parallel operation Overvoltage protection, triggerpoint
Hold-up time Power good signal (TCL 60 & TCL 120 only)
General Specifications
Temperature ranges Temperature derating – Operating – Storage (non operating) – at 187 ...264 VAC or 265...375 VDC operation – at 93...132 VAC or 130...187 VDC operation – at 85...130 VDC operation – 10 °C…+70 °C max. – 25 °C…+85 °C 1.7% /K above 50°C 1.1% /K above 40°C 1.3% /K above 30°C 95 % rel. H max. 0.02 % /K 55 – 180 kHz depending on load (frequency modulation) 88% typ. according to IEC/EN 60950, UL 60950, UL 508, EN 50178, EN 60204, EN 61558-2-8 TCL 24 models: >2.68 Mio h TCL 60 models: >2.94 Mio h TCL 120 models: >1.62 Mio h
Humidity (non condensing) Temperature coefficient Switching frequency Efficiency Isolation Reliability, calculated MTBF @ 25°C ( according to IEC-1709)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 2 of 5
Industrial Power Supplies
TCL Series General Specifications
Safety standards IEC 60950, EN 60950 (output SELV), UL 60950, UL 508, EN 50178, EN 60204, EN 61558-2-8. - NEC class 2 (TCL 60 models only) UL/cUL 60950 recognized, File E181381 UL 508C listed, File E210002 CB-Report per IEC 60950 EN 61000-6-3 EN 61000-6-2 degree of protection class 1 IP 20 ( IEC 60529) plastic FR2010-110C (UL 94V-0 rated) 35 mm DIN-rails as per EN 50022-35x15/7.5 (snap-on with self-locking spring) Adapter for Wall-/Chassi Mounting (included) output characteristic optimized for battery charging available on request
24–120 Watt
Safety approvals (TCL 24 models pending)
Electromagnetic compatibility (EMC), Emissions Electromagnetic compatibility (EMC), Immunity Safety class Case protection Enclosure material Mounting
Options
TCL–REM240 Redundancy Module
This module enables redundant operation of any two TCL models by decoupling the 2 power supplies. It can also be used to separate sensitive loads from the main power source.
Models
Order code TCL–REM240 Inputs Vin 2 x 5...60 VDC Max power per input 144 W Output voltage Vin – 0.9 VDC Output current max. 8A Connection detachable screw terminal block
Specifications
Operating temperature Electromagnetic compatibility Dimensions – 10°C...+70°C max. (14°F...+158°F) derating above 40°C (104°F): 1.5%/K in correspondence to connected units (no internal switching device) same as model TCL 24 (see page 4)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 3 of 5
Industrial Power Supplies
TCL Series Outline Dimensions mm (inches)
TCL 24 and TCL-REM240
100.0 (3.94) OUTPUT 12
24–120 Watt
Output 1 +Vout 2 –Vout
75.0 (2.95)
DC-ON LED Output voltage adjust
Innput 1 AC Ground 2 Neutral 3 Live
1
23 INPUT
Weight: 140g (4.9 oz)
27 (1.06)
TCL 60
OUTPUT 12345 100.0 (3.94)
2.2 (0.09)
Output voltage adjust
1
23 INPUT
75.0 (2.95)
DC-ON LED
Output 1 +Vout 2 +Vout 3 –Vout 4 –Vout 5 Power Good
Innput 1 AC Ground 2 Neutral 3 Live
Weight: 265g (9.4 oz)
3.2 (0.13)
Tolerances: ±0.5mm (±0.02)
45 (1.77)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 4 of 5
Industrial Power Supplies
TCL Series Outline Dimensions mm (inches) 24–120 Watt
TCL 120
OUTPUT 12345 100.0 (3.94)
DC-ON LED Output voltage adjust 75.0 (2.95)
Output 1 +Vout 2 +Vout 3 –Vout 4 –Vout 5 Power Good
Innput 1 AC Ground 2 Neutral 3 Live
1
23 INPUT
DIN rail mounting hooks 20mm (0.79) wide
Weight: 440g (15.5 oz)
Tolerances: ±0.5mm (±0.02)
85 (3.35)
3.2 (0.13)
Wall Mounting Bracket Instead on a DIN-rail, the module can be easily mounted on a chassis or wall with help of a mounting bracket which is supplied as standard with each Power Supply
Specifications can be changed without notice
Rev. 07/05
Jenatschstrasse 1 · CH-8002 Zurich · Switzerland Tel. +41 43311 4511 · Fax +41 43311 4545 · info@traco.ch · www.tracopower.com
Page 5 of 5