0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
TSP-WR

TSP-WR

  • 厂商:

    TRACOPOWER

  • 封装:

  • 描述:

    TSP-WR - Industrial Power Supplies (TSP-WR Series, 180-600 Watt) - TRACO Electronic AG

  • 数据手册
  • 价格&库存
TSP-WR 数据手册
Industrial Power Supplies TSP-WR Series, 180–600 Watt Innovative and Powerful Features! ◆ For worldwide Operation – with ultrawide Input Range from 100 to 550VAC CB EN 60950 IEC 60950 Scheme UL 60950 UL 508 II3G ATEX 95 ◆ For Single- and 3 Phase Networks ◆ Robust Design- qualified for harsh Industrial Environments ◆ Industrial Operating Temperature Range: –25°C to +70°C ◆ Power Good Signal ◆ Indefinite Short Circuit, Overvoltage and Overtemperature Protection ◆ Wall Mounting Option ◆ Modular Design with Add-on Modules for: – Redundancy Operation – DC-UPS – Buffer for Power Back-up ◆ International Safety Approvals incl. ATEX and Class l, Div.2 Certification ◆ 3 Year Warranty The successful TSP series of high performance DIN-Rail Power Supplies has been expanded with 3 additional models which features an ultrawide input range of 85-132/230-550VAC.With this input voltages the power supplies can be used in almost all single- and 3 phase power networks worldwide. A high, continuously available power reserve guarantees reliable start-up of loads with high inrush currents. Excellent electrical specifications and high immunity against electrical disturbances makes these compact modules the best choice to power sensitive loads in industrial process control systems, machine tools or any other demanding industrial application. The power supplies complies also with the new EMC standard for Industrial environments, IEC/EN 61204-3. 3 Add-on Modules for extra functions offer a great flexibility in system applications. A module for redundant operation with true power sharing is available. With the Battery Controller module the power supplies can be extended to a perfect DC-UPS system. The Buffer module provides power back-up up to 4 seconds without the need of any batteries. Easy and vibration proof installation with pluggable screw terminal block and snap-on mounting on DIN-rails. Models Model No. TSP 180–124WR TSP 360–124WR TSP 600–124WR Output Voltage (Vnom) 24 VDC (adjustable 24 - 28 VDC) *Output Current (Imax) 7.5 A 15.0 A 25.0 A Output Power (Pmax) 180 W 360 W 600 W * Max. current at nominal output voltage and operating temperature up to 40°C max. http://www.tracopower.com Page 1 of 10 Industrial Power Supplies TSP-WR Series Input Specifications Applicable 3-Phase Networks – TN, TT: 500 VAC Star configuration (EN60950+UL508) 500 VAC Delta (UL508 only) – IT: 400 VAC Delta (IEC-62103) 230 VAC Delta (IEC-60950) 500 VAC UL508 only 85–132 / {187–264 / 323–550 autorange} selectable by manual slide switch EN 61000-3-2, Class A (for limited output power) 20 ms min. (full load 230 - 500 VAC) TSP 180-124WR TSP 360-124WR TSP 600-124WR Efficiency 115 VAC t.b.a t.b.a t.b.a 88% typ. 24 – 28 VDC – Input variation – Load variation (10–100 %) – Load variation (10–100 %) parallel mode 0.5 % max. 0.5 % max. 2.0% 100 mV pk-pk typ. (150 mV pk-pk max. at Imax) current limitation at 125% of Imax. constant current, automatic recovery 34 V electronic overload protection switch off at overtemperature, automatic restart dual color LED (green: DC ok, red: DC off) – trigger threshold: – relay output 18 - 22V DC OK = contact closed (rated: 30VDC / 1.0A) unlimited – 25°C...+70°C max. (–13°F...+158°F) (for derating see graph A on page 4) convection cooling, no internal fan –25 °C…+85 °C (– 13°F...+185°F) 95 % rel. H max. 2 0.02 %/K >350’000h in acc. to IEC 61709 by ext. contact. DC on: -S contact open DC off: -S connectetd via 1Kohm to -Vout 230 VAC < 23 A < 46 A < 50 A 180–600 Watt Input voltage ranges Harmonic limits Holdup time Inrush current Output Specifications Output voltage adj. range Regulation Ripple and Noise (20MHz Bandwidth) Electronic short circuit protection Output overvoltage protection Overload protection Overtemperature protection Status indicator Power-Good signal Max. capacitive load General Specifications Operating temperature range Cooling Storage temperature Humidity (non condensing) Pollution degree Temperature coefficient Reliability, calculated MTBF Remote On/Off All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 2 of 10 Industrial Power Supplies TSP-WR Series General Specifications Isolation Safety standards – – – – – Information technology equipment Industrial control equipment Electrical equipment of machines Electronic equipment for power installation Control equipment for hazardous location according to IEC/EN 60950, UL 60950, UL 508C IEC/EN 60950, UL 60950, CSA-C22.2 No. 60950-1-03 UL 508, CSA-C22.2 EN 60204 EN 50178 IEC/EN 60079-15 ( Class I, Zone 2, EEx nC II C T4 U), ANSI/UL60079-15 ( Class I, Division 2, Groups A,B,C,D AEx n C II C T4 U) EN 61558-2-4 EN 60950 sect. 2.5 and NEC Class 2 CB-Report as per IEC 60950, EN 60950-1:2003 CSA/UL 60950, CSA-C22.2 No.14-95, UL 508C CSA File no.: 219759 EN 60204, EN 61558-2-4 ATEX 94/9/EC, ANSI/UL 60079-15, FM 3611. Degree of electrical protection I ( IEC 536) IP 20 ( IEC 529) EN 61000-6-3, EN 61204-3 EN 55011 class B, EN 55022 class B, EN 55011 class B, EN 55022 class B, EN 61000-6-2, EN 61204-3 IEC / EN 61000-4-2 4 kV / 8 kV IEC / EN 61000-4-3 10 V / m IEC / EN 61000-4-4 2 kV IEC / EN 61000-4-5 1 kV / 2 kV IEC / EN 61000-4-6 10 V IEC / EN 61000-4-8 30 A / m IEC / EN 61000-4-11 3 axis, sine sweep, 10-55 Hz, 1g, 1oct/min 3 axis, 15 g half sine, 11 ms aluminium (chassis) / zinc plated steel (cover) – DIN-rail mounting – Wall mounting (option) Connection for DIN-rails as per EN 50022-35x15/7.5 (snap-on with self-locking spring) with wall mounting bracket - see page 10 detachable screw terminals (plugs included) 2 terminals per output A) Output Power Derating vs Ambient Temperature B) Output Power Derating vs Input Voltage 180–600 Watt – Safety transformers for SMPS – Limitet power source (model TSP 090-124N) Safety approvals / certifications Safety class Case protection Electromagnetic compatibility (EMC), Emissions – Conducted RI suppression on input – Radiated RI suppression Electromagnetic compatibility (EMC), Immunity – Electrostatic discharge (ESD) – Radiated RF field immunity – Electrical fast transient / burst immunity – Surge immunity – Immunity to conducted RF disturbances – Power frequency field immunity – Voltage dips Environment Enclosure material Mounting – Vibration acc. IEC 60068-2-6; – Shock acc. IEC 60068-2-27 Output Power Derating 100 90 TSP 600 100 90 TSP 600 TSP 180 TSP 360 Output Power [% Pmax] 70 60 50 40 30 20 10 0 -25 Output Power [% Pmax] 60 70 80 TSP 180 TSP 360 80 70 60 50 40 30 20 10 0 40 50 Temperature [˚C] 85 100 115 132 187 284 323 Input Voltage [VAC] 550 All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 3 of 10 Industrial Power Supplies TSP-WR Series TSP–REM360 Redundancy Module With this module and two power supplies of the TSP series (180 and 360W models) a highly reliable, true redundant power system can be configured without any additional components. This module enforces the equivalent sharing of the output current by each power supply. The system is fully redundant and provides the output power even if one power supply has completely failed e.g. by short circuit on the output. In the event of either, one power supply failing or being disconnected, the second unit will automatically supply the full current to the load. The redundancy of the system is monitored and if lost, indicated by an alarm output. The inputs are hot swappable and can be loaded up to 15A each. 180–600 Watt Models Order code (includes terminal plugs) TSP–REM360 Input 2 x 24 VDC 2 x Control input Max Power per Input 2 x 360 W Output Voltage adjust 24 VDC (24 - 27 VDC) Output Power max. 360 W Function Diagram + DC IN 1 _ J1.2 J2.3 J2.4 J2.1 J2.2 Connector Positions Front view Output Load --++ Remote Link 2 Remote Link 1 + _ Bottom view Top view J1.1 TSP J3.1 J3.2 Remote Link 1 + DC IN 2 _ J1.4 Output Volt adjust J1.3 J4.1 TSP Remote Link 2 J4.2 REM Controller DC IN 1 DC IN 2 J5.1 J5.2 Redundancy ok Alarm Remote On/Off J5.3 J5.4 Alarm Remote On/Off -+-+ Specifications Operating temperature Electromagnetic compatibility Redundancy OK signal (Alarm) Remote link cable (0.5m) Remote On/Off Dimensions – 25°C...+70°C max. (–13°F...+158°F) derating above 40°C (104°F): 1.5%/K in correspondence to connected units (no internal switching device) trigger threshold at 18...22VDC, contact closed if one or both inputs failed 2 cables included with TSP-REM360 module by ext. contact: contact open = On, contact closed = Off see page 7 All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. http://www.tracopower.com Page 4 of 10 Industrial Power Supplies TSP-WR Series TSP–BFM24 Buffer Module The TSP-BFM24 Buffer Module will hold the output voltage of a 24VDC power supply after brown outs or voltage dips of up to ten full 50Hz cycles. During this buffer period no deterioration of the 24VDC output voltage will occur. For many applications this buffer module is an ideal and cost effective alternative to a battery based backup system. The buffer module consists of a large bank of capacitors. When the power supply is switched on, the buffer capacitors will be charged. This will take approximately 30 second and an opto-coupler signal is indicating the „READY“ condition. When a power fail occurs, the capacitor bank is discharged, maintaining the output of the buffer module at its nominal voltage. This condition is indicated by an „POWER FAIL“ signal. The hold up time is typically 200ms at 25A and 4 seconds t ypically at 1,2A. After 4 seconds the buffer device will switch off the output voltage. The operation modes of the module are indicated by a LED on the front panel also. The big advantage of this buffer solution is, that it is fully maintenance free and its storage capability does not deteriorate over the live time of the product. 180–600 Watt Models Order code (includes terminal plugs) TSP-BFM24 Function Diagram J2.2 Operating Voltage Range 24...28VDC Buffer Time 200ms typ. @ 25A max. 4.0 s max. @1.2A Connector Positions Output Power max. 600 W Inhibit J2.1 Discharge TSP Charge J1.1 J1.2 J1.3 J1.4 Volt adjust Load J2.4 Active J2.3 Voltage Detection Voltage Detection J2.6 J2.5 Ready Specifications Operating temperature Electromagnetic compatibility Buffer voltage Charging Status signals Inhibit Dimensions – 25°C...+70°C max. (–13°F...+158°F) derating above 40°C (104°F): 1.5%/K in correspondence to connected units (no internal switching device) adjustable, >1V below input voltage, min. 22VDC 0.6A max. / 30s max. Buffer Active , Buffer Ready (optocoupler output) and dual colour LED for status indication optocoupler input: 35V max.
TSP-WR 价格&库存

很抱歉,暂时无法提供与“TSP-WR”相匹配的价格&库存,您可以联系我们找货

免费人工找货