POWER TRANSFORMER
CHASSIS MOUNT :
TOROIDAL MEDICAL SERIES
VPM240-20800
Description:
The toroidal construction inherently reduces stray fields, increases efficiency and minimizes size
compared to traditional EI transformers. The addition of a Flux Band further reduces the
remaining stray fields. The shield between Primary and Secondary improves safety, reduces
common mode signals and minimizes leakage current. Built with a Class F (155°) insulation
system. A 140°C self-resetting thermal switch is included in the primary.
Electrical Specifications (@25C)
1. Maximum Power: 5000VA
2. Input Voltages: 240, 208VAC, 50/60Hz
3. Output Voltages: 120VAC @41.60A or 240VAC CT @ 20.80A
4. Voltage Regulation: 1.4% TYP from full load to no load
5. Temperature Rise: 50°C TYP
6. Hipot: 4000VAC, Primary to Secondary, Primary & Secondary to Shield & mounting surface
7. Efficiency: 95% TYP. @ full load
Photo for illustration only
RoHS
2011/65/EU
Agency File:
UL: File E122529, UL 60601-1/(R) 2012 Medical Electrical Equipment – Part 1 with 2 MOPP
CE: ES 60601-1 (IEC 60601-1:2005, MOD)
cUL: C22.2 No. 60601-1:14, Medical Electrical Equipment – Part 1
CB Certified.
OD
Max Dimensions: Inches (mm)
O.D.
HT.*
12.6(320)
5.8(148)
BOLT
Weight: 41Kg
FLAT
WASHER
Mounting:
Transformer is provided with one rubber pad, M12 x 140mm bolt, nut, spring and flat washer.
Inner diameter is potted with epoxy and a hole is drilled through epoxy for mounting bolt.
H
Connections:
Transformer is provided with 12” (305mm) long, 0.5” (12.7mm) stripped and tinned, stranded
UL 1015 lead wire. Primaries are 12AWG, Secondaries are 12AWG, and Shield is 18AWG.
The GRN/YEL shield lead is typically grounded. Do not lift transformer by leads!
SPRING
WASHER
Input Options:
208VAC: Input to Blue & Grey
240VAC: Input to Blue & Brown
Output Options:
120VAC: Output from Black & Red, jumper Black & Orange, jumper Red to Yellow
240VAC: Output from Black & Yellow, jumper Red & Orange
Primary and secondary windings are designed to be connected in series or parallel. Windings
are not intended to be used independently.
RoHS Compliance: Meets the requirements of 2015/863/EU, known as the RoHS 3 initiative.
* At printing, this document is considered “uncontrolled”. Contact Triad Magnetics’ website for current version
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
Publish Date: May 13, 2019
NUT
RUBBER
PAD