Data sheet...
VSSC6 RS485 PA EX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Overvoltage coupling along the conductor path may
disturb or destroy sensitive signal inputs. It is important
to provide protection in the immediate vicinity of I&C
devices. Weidmüller's broad product range for the I&C
sector offers products in a 2-piece, pluggable design and
modular terminals for tension clamp or screw connection.
These products are suitable for both binary and analogue
signals. Weidmüller also offers other designs with
integrated components such as gas discharge tubes or
varistors. VARITECTOR stands for flexible and variable
surge protection by Weidmüller, tested according to
product standard IEC61643-21. The VARITECTOR
series can be used in applications according to IEC
61643-22 / VDE 0845-3 for classes C1, C2, C3 and
D1. The VARITECTOR SPC, SSC and MCZ OVP product
families optimally combine electrical and mechanical
properties. Size and easy handling play an important role.
This surge protection is suited for confined spaces in
industrical and process automation as well as in building
automation applications.
General ordering data
Order No.
Type
Version
GTIN (EAN)
Qty.
1065020000
VSSC6 RS485 PA EX
Surge protection for instrumentation and control
4032248830251
5 pc(s).
Creation date April 26, 2013 10:12:36 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes.
1
Data sheet...
VSSC6 RS485 PA EX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Depth
12.2 mm
81 mm
Height
Net weight
88.5 mm
49.2 g
5...96 %
-40 °C...+80 °C
Operating temperature
-40 °C...+70 °C
29
3,936 Years
MTTF
SFF
Isolating function
Optical function display
Segment
No
No
Instrumentation and
Control
Surge voltage category
94 V
12 V
35 V
Rated current
300 mA
Discharge current In (8/20µs) wire-wire 2.5 kA
Discharge current In (8/20µs) wire-PE
2.5 kA
Discharge current, max. (8/20 µs)
10 kA
Standards
IEC61643-21:2009, DIN
EN 60079-0.2009, DIN EN
60079-26:2007, DIN EN
61241-11:2006
Humidity
5...96 %
Lightning test current Iimp (10/350 µs)
0.5 kA
Residual voltage, UP typical
94 V
Overload - failure mode
Modus 2
Temperatures
Humidity
Storage temperature
Probability of failure
λges
-9
PFH in 1*10 per hour
SIL in compliance with IEC 61508
1.75
3
93.97 %
General data
Colour
Mounting rail
Protection degree
UL 94 flammability rating
Light Blue
TS 35
IP 20
V-0
Insulation coordination acc. to EN 50178
Pollution severity
2
III
Interference voltage
Protection level on output side Wire-PE
1kV/µs, typically
94 V
Protection level
Protection level, UP wire - PE
technical data
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Discharge current Imax (8/20µs) wirewire
Discharge current Imax (8/20µs) wire-PE
Protection level UP (typ.)
Colour
Requirements category acc. to IEC
61643-21
Volume resistance
Dielectric strength at FG against PE
5 kA
5 kA
≤ 1830 V
Light Blue
C2, C3, D1
1.8 Ω 10 %
≥ 500 V
Creation date April 26, 2013 10:12:36 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes.
2
Data sheet...
VSSC6 RS485 PA EX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Connection data
Clamping range, rated connection, min. 0.5 mm²
Wire connection cross section, stranded,
rated connection, min.
0.5 mm²
Tightening torque, min.
0.5 Nm
Clamping range, rated connection, max. 4 mm²
Wire connection cross section, stranded,
rated connection, max.
4 mm²
Tightening torque, max.
0.8 Nm
EX protection data
Input power, max. PI
Internal inductance, max. LI
0.75 W
0 µH
Temperature class T5/100°C (-40 ° C ...
+85 °C) li
300 mA
Internal capacitance, max. CI
Temperature class T4/135°C (-40°C ...
+120 °C) li
Temperature class T6/85 °C (-40 °C ...
+70 °C) li
1 nF
300 mA
300 mA
Further details of approvals
GOST certificate
GOST-Zertifikat
UL Zertifikat
ATEX Certificate
IEC Ex certificate
IECEX Zertifikat
EC000943
27-13-08-01
27-14-02-01
UNSPSC
eClass 5.1
eClass 7.1
30-21-19-21
27-13-08-01
27-13-08-05
Rated data UL
UL certificate
Ratings IECEx/ATEX
ATEX certificate
Classifications
ETIM 3.0
eClass 4.1
eClass 6.2
Approvals
Approvals
ROHS
Conform
Probability of failure
SIL PAPER
3-D model
SIL Paper
Downloads
Package insert
Declaration of Conformity
PDF
3-D model
Instruction sheet VSSC
K378_02_11.pdf
Type examination certificate
Creation date April 26, 2013 10:12:36 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes.
3
Data sheet...
VSSC6 RS485 PA EX
Drawings
Similar to illustration
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Circuit diagram
Creation date April 26, 2013 10:12:36 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes.
4
很抱歉,暂时无法提供与“1065020000”相匹配的价格&库存,您可以联系我们找货
免费人工找货