Switch-mode power supplies
FRQQHFW3RZHU352+
FRQQHFW3RZHU
352+
A
% { \ | CB
Scheme
7HFKQLFDOGDWD
L (+)
N (–)
*HQHUDOWHFKQLFDOGDWD
Current limiting
Ambient temp. operating / storage temperature
Max. perm. air humidity (operation)
Degree of protection / Class of protection
Pollution degree
Insulation voltage input/output
MTBF according to IEC 61709
+
+
–
–
AC
DC
PE
13
14
DC OK
Data
Link
> 100 % Irated
-25…+70 °C -25 °C…+85 °C
95 % RH
IP 20 / I, with PE connection
2
4 kV I/O
2 kV I/earth 0.5 kV O/earth
CP T … 70/90 W
> 1.8 Mio. h
CP T … 140 W
> 1.2 Mio. h
CP T … 180/360/600 W > 0.9 Mio. h
16 V DC / 35 V DC / 63 V DC
yes, without diode module
metal, corrosion resistant
Thermal protection, autom. restart
Unlimited, autom. restart
Dual LED Operational: Green LED; Error: Red LED
Horizontal on TS 35 mounting rail, with 80 mm space at top and bottom.
Side by side mounting with 50 mm clearance.
7 mm
Protection against reverse voltages from the load
Parallel connection option
Housing version
Overload protection
Short circuit protection
Indication
Mounting position, installation notice
Stripping length (rated connection)
6LJQDOLQGLFDWLRQ
Power Good Signal
Trigger point
12 V Version 9…11 V DC
24 V Version 18...22 V DC
48 V Version 36...44 V DC
NO contact
30 V DC / 1.0 A max. for 12/24 V DC modules
48 V DC/ 0.5 A max. for 36/48 V DC modules
70 W
11 V DC ± 1 V DC / 20 mA max.
140 W
11 V DC ± 1 V DC / 40 mA max.
90 W
22 V DC ± 2 V DC / 10 mA max.
180/360/600 W 24 V DC
22 V DC± 2 V DC / 20 mA max.
180/360/600 W 48 V DC
44 V DC± 4 V DC / 15 mA max.
3RWHQWLDOIUHHÁRDWLQJVLJQDOFRQWDFW
Active output signal
0D[OLPLWLQJDYHUDJHRQVWDWHFXUUHQW>$@
Type\Temp.
1 ph 12 V / 6 A
1 ph 12 V / 12 A
1 ph 24 V / 3.8 A
1 ph 24 V / 7.5 A
1 ph 24 V / 15 A
1 ph 24 V / 25 A
1 ph 36 V / 16.5 A
1 ph 48 V / 2 A
1 ph 48 V / 4 A
1 ph 48 V / 7.5 A
1 ph 48 V / 12.5 A
1-2 ph 24 V / 7.5 A
1-2 ph 24 V / 15 A
1-2 ph 24 V / 25 A
40 °C
6.0
12.0
3.8
7.5
15.0
25.0
16.5
2.0
4.0
7.5
12.5
7.5
15.0
25.0
50 °C
5.7
9.5
3.1
6.3
12.5
22.5
15.0
1.6
3.3
6.3
11.3
6.3
12.5
22.5
60 °C
5.4
7.0
2.5
5.0
10.0
20.0
13.3
1.3
2.5
5.0
10.0
5.0
10.0
20.0
70 °C
4.5
3.7
1.7
3.3
6.7
13.3
9.0
0.8
1.7
3.3
7.5
3.3
6.7
13.3
(0&VKRFNYLEUDWLRQ
Noise emission acc. to EN55022
Noise immunity tests acc. to
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN610004-6 (conducted), EN61000-4-11 (Dips)
according to EN61000-3-2
3 axes, Sinus, 10…55 Hz, 1 g, 1 oct./min
3 axes, 15 g, half sinus, 11 ms
Limiting of mains voltage harmonic currents
Vibration IEC 60068-2-6
Shock IEC 60068-2-27
(OHFWULFDOVDIHW\DSSOLHGVWDQGDUGV
Electrical equipment of machines
Safety transformers for switched-mode power units
Machinery with electronic equipment
Safety extra low voltage
according to EN60204
according to EN61558-2-4
according to EN50178
SELV according to EN60950
CP T SNT...
100
100
90
90
80
70
90 W
180 W
360 W
60
50
40
-25
40
50
Temperature [°C]
A.26
70 W
140 W
60
70
Output Power [% Pmax]
Output Power [% Pmax]
600 W
80
70
60
50
40
85 90 100 110 115
132
187
230 264
Input Voltage [V AC]
1460790000 – 2014/2015
connectPower
PRO-H
CP T SNT 70W 12V 6A
Switch-mode power supplies
connectPower PRO-H
CP T SNT 140W 12V 12A
A
L (+)
N (–)
+
–
AC
PE
DC
13
14
DC OK
Data
Link
L (+)
N (–)
PE
+
+
–
–
AC
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
1 A @ 230 V AC, 2 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
1.4 A @ 230 V AC, 2.5 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
12 V DC ± 1 %
12...14 V DC (adjustable via potentiometer on front)
100 mVSS @ 12 V DC, Inom
6 A @ 40 °C
6 A @ 40 °C, 5.4 A @ 60 °C, 4.5 A @ 70 °C
12 V DC ± 1 %
12...14 V DC (adjustable via potentiometer on front)
100 mVSS @ 12 V DC, Inom
12 A @ 40 °C
12 A @ 40 °C, 7 A @ 60 °C, 3.7 A @ 70 °C
typ. 82 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 35 / 110 mm
0.5 kg
typ. 85 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 54 / 110 mm
0.7 kg
BVATEX; CE; CSA; cULus; cURus; GOSTME25
BVATEX; CE; CSA; cULus; cURus; GOSTME25
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
2 (+ / -)
1 / 2.5
1 / 2.5
18 / 12
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
1 / 2.5
18 / 12
Ordering data
Type
CP T SNT 70W 12V 6A
Note
Qty.
1
Order No.
1105430000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Type
CP T SNT 140W 12V 12A
Qty.
1
Order No.
1105440000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
1460790000 – 2014/2015
A.27
Switch-mode power supplies
connectPower PRO-H
connectPower
PRO-H
CP T SNT 90W 24V 3.8A
CP T SNT 90W 24V 3.8A CL2
Class 2, UL 1310
A
L (+)
N (–)
PE
+
–
AC
DC
13
14
DC OK
Data
Link
L (+)
N (–)
+
–
AC
PE
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
1 A @ 230 V AC, 2.1 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
1 A @ 230 V AC, 2.1 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
3.8 A @ 40 °C
3.8 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
3.8 A @ 40 °C
3.8 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C
typ. 85 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 35 / 110 mm
0.5 kg
typ. 85 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 35 / 110 mm
0.5 kg
BVATEX; CE; CSA; cULus; cURus; GOSTME25
CE; cULus; GOSTME25
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
2 (+ / -)
1 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
2 (+ / -)
1 / 2.5
0.5 / 2.5
24 / 12
Ordering data
Type
CP T SNT 90W 24V 3,8A
Note
Qty.
1
Order No.
1105790000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Type
CP T SNT 90W 24V3,8ACL2
Qty.
1
Order No.
1194410000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
A.28
1460790000 – 2014/2015
connectPower
PRO-H
CP T SNT 180W 24V 7.5A
Switch-mode power supplies
connectPower PRO-H
CP T SNT 360W 24V 15A
A
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
L (+)
N (–)
PE
+
+
–
–
AC
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
1.4 A @ 230 V AC, 2.5 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
2.5 A @ 230 V AC, 5 A @ 115 V AC
6.3 A / < 25 A (230 V AC)
10…16 A, char. B, circuit breaker
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
7.5 A @ 40 °C
7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
15 A @ 40 °C
15 A @ 40 °C, 10 A @ 60 °C, 6.7 A @ 70 °C
typ. 88 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 54 / 110 mm
0.7 kg
typ. 87 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 80 / 110 mm
1.1 kg
BVATEX; CE; CSA; cULus; cURus; GOSTME25
BVATEX; CE; CSA; cULus; cURus; GOSTME25
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
1 / 2.5
18 / 12
Ordering data
Type
CP T SNT 180W 24V 7,5A
Note
Qty.
1
Order No.
1105810000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Type
CP T SNT 360W 24V 15A
Qty.
1
Order No.
1105820000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
1460790000 – 2014/2015
A.29
Switch-mode power supplies
connectPower PRO-H
connectPower
PRO-H
CP T SNT 600W 24V 25A
A
L (+)
N (–)
PE
+
+
–
–
AC
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
5 A @ 230 V AC, 10 A @ 115 V AC
12 A / < 30 A (230 V AC)
16…25 A, char. B, circuit breaker
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
25 A @ 40 °C
25 A @ 40 °C, 20 A @ 60 °C, 13.3 A @ 70 °C
typ. 89 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
125 / 165 / 125 mm
2.8 kg
BVATEX; CE; CSA; cULus; cURus; GOSTME25
mm²
mm²
Input
Screw connection
3 for L/N/PE
1/4
1/4
18 / 10
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
2.5 / 4
12 / 10
Ordering data
Type
CP T SNT 600W 24V 25A
Note
Qty.
1
Order No.
1105840000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
A.30
1460790000 – 2014/2015
connectPower
PRO-H
CP T SNT 90W 48V 2A
Switch-mode power supplies
connectPower PRO-H
CP T SNT 180W 48V 4A
A
L (+)
N (–)
+
–
AC
PE
DC
13
14
DC OK
Data
Link
L (+)
N (–)
PE
+
+
–
–
AC
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
1 A @ 230 V AC, 2.1 A @ 115 V AC
4 A / < 20 A (230 V AC)
6…16 A, char. B, circuit breaker
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
1.4 A @ 230 V AC, 2.5 A @ 115 V AC
4 A / < 25 A (230 V AC)
6…16 A, char. B, circuit breaker
48 V DC ± 1 %
48...56 V DC (adjustable via potentiometer on front)
100 mVSS @ 48 V DC, INenn
2 A @ 40 °C
2 A @ 40 °C, 1.3 A @ 60 °C, 0.8 A @ 70 °C
48 V DC ± 1 %
48...56 V DC (adjustable via potentiometer on front)
100 mVSS @ 48 V DC, INenn
4 A @ 40 °C
4 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C
typ. 87 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 35 / 110 mm
0.5 kg
typ. 90 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
110 / 54 / 110 mm
0.7 kg
BVATEX; CE; cULus; GOSTME25
BVATEX; CE; CSA; cULus; cURus; GOSTME25
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
2 (+ / -)
1 / 2.5
0.5 / 2.5
24 / 12
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
0.5 / 2.5
24 / 12
Ordering data
Type
CP T SNT 90W 48V 2A
Note
Qty.
1
Order No.
1194420000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Type
CP T SNT 180W 48V 4A
Qty.
1
Order No.
1105850000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
1460790000 – 2014/2015
A.31
Switch-mode power supplies
connectPower PRO-H
connectPower
PRO-H
CP T SNT 360W 48V 7.5A
CP T SNT 600W 48V 12.5A
A
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
2.5 A @ 230 V AC, 5 A @ 115 V AC
6.3 A / < 25 A (230 V AC)
10…16 A, char. B, circuit breaker
100…240 V AC (auto-select)
85…132 V AC, 187…264 V AC
47...63 Hz
5 A @ 230 V AC, 10 A @ 115 V AC
12 A / < 30 A (230 V AC)
16…25 A, char. B, circuit breaker
48 V DC ± 1 %
48...56 V DC (adjustable via potentiometer on front)
100 mVSS @ 48 V DC, INenn
7.5 A @ 40 °C
7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C
48 V DC ± 1 %
48...56 V DC (adjustable via potentiometer on front)
100 mVSS @ 48 V DC, INenn
12.5 A @ 40 °C
12.5 A @ 40 °C, 10 A @ 60 °C, 7.5 A @ 70 °C
typ. 89 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
125 / 80 / 125 mm
1.1 kg
typ. 91 % @ 230 V AC
min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC
yes, max. 5
125 / 165 / 125 mm
2.8 kg
BVATEX; CE; CSA; cULus; cURus; GOSTME25
BVATEX; CE; CSA; cULus; cURus; GOSTME25
Input
Screw connection
3 for L/N/PE
0.5 / 2.5
0.5 / 2.5
24 / 12
Input
Screw connection
3 for L/N/PE
1/4
1/4
18 / 10
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
1 / 2.5
18 / 12
Output
Screw connection
7 (+ / - / Signal)
1 / 2.5
2.5 / 4
12 / 10
Ordering data
Type
CP T SNT 360W 48V 7,5A
Note
Qty.
1
Order No.
1105860000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Type
CP T SNT 600W 48V 12,5A
Qty.
1
Order No.
1105870000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
A.32
1460790000 – 2014/2015
connectPower
PRO-H
CP T SNT2 180W 24V 7.5A
Switch-mode power supplies
connectPower PRO-H
CP T SNT2 360W 24V 15A
A
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
100…500 V AC (switchable)
85…132 V AC, 187…550 V AC
50 / 60 Hz
100…500 V AC (switchable)
85…132 V AC, 187…550 V AC
50 / 60 Hz
/ < 23 A @ 230 V AC
mm²
mm²
/ < 23 A @ 230 V AC
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
7.5 A @ 40 °C
7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
15 A @ 40 °C
15 A @ 40 °C, 6.7 A @ 70 °C, 10 A @ 60 °C
typ. 88 %
min. 20 ms
Yes
110 / 54 / 110 mm
0.7 kg
typ. 88 %
min. 20 ms
Yes
125 / 80 / 125 mm
1.1 kg
CE
CE
Input
Screw connection
3 for L/N/PE
1/4
1/4
18 / 10
Output
Screw connection
4 (++ / --)
2.5 / 4
2.5 / 4
12 / 10
Input
Screw connection
3 for L/N/PE
1/4
1/4
18 / 10
Output
Screw connection
4 (++ / --)
2.5 / 4
2.5 / 4
12 / 10
The device is suitable for single-phase and two-phase operation.
The device is suitable for single-phase and two-phase operation.
Type
CP T SNT2 180 W 24 V 7,5 A
Type
CP T SNT2 360 W 24 V 15 A
Ordering data
Note
Qty.
1
Order No.
1194480000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Qty.
1
Order No.
1194490000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
1460790000 – 2014/2015
A.33
Switch-mode power supplies
connectPower PRO-H
connectPower
PRO-H
CP T SNT2 600W 24V 25A
A
L (+)
N (–)
+
+
–
–
AC
PE
DC
13
14
DC OK
Data
Link
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
100…500 V AC (switchable)
85…132 V AC, 187…550 V AC
50 / 60 Hz
/ < 50 A @ 230 V AC
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
25 A @ 40 °C
25 A @ 40 °C, 20 A @ 40 °C, 13.3 A @ 70 °C
typ. 88 %
min. 20 ms
Yes
125 / 190 / 125 mm
3 kg
CE
mm²
mm²
Input
Screw connection
3 for L/N/PE
1/4
1/4
18 / 10
Output
Screw connection
5 (++ / ---)
2.5 / 4
2.5 / 4
12 / 10
The device is suitable for single-phase and two-phase operation.
Ordering data
Type
CP T SNT2 600 W 24 V 25 A
Note
Qty.
1
Order No.
1194310000
The internal varistor found in a switch-mode power supply does not replace the
necessary surge protection in a system.
Accessories
Note
A.34
1460790000 – 2014/2015
connectPower
PRO-H
CP T RM 10
Switch-mode power supplies
connectPower PRO-H
CP T RM 20
A
Input 1
Data
Link PS1
Data
Link PS2
Input 1
Control
Input 2
Remote
ON/OFF
Data
Link PS1
Output
Data
Link PS2
Output
Control
Input 2
DC OK
Remote
ON/OFF
DC OK
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
AC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continous output current @ 24 V DC
General data
Degree of efficiency
AC failure bridging time @ INom
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Note
mm²
mm²
24 V DC
24 V DC
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
15 A @ 40 °C
24 V DC ± 1 %
24...28 V DC (adjustable via potentiometer on front)
100 mVPP @ 24 V DC, Inenn
25 A @ 40 °C
110 / 35 / 110 mm
0.4 kg
110 / 54 / 110 mm
0.45 kg
CE; CSA; cURus; GOSTME25
CE; CSA; cURus; GOSTME25
Input
Output
Input
Output
4 (++--)
1/4
1/4
18 / 10
4 (++ / --)
2.5 / 4
2.5 / 4
12 / 10
4 (++--)
1/4
1/4
18 / 10
4 (++ / --)
2.5 / 4
2.5 / 4
12 / 10
Ordering data
Type
CP T RM 10
Qty.
1
Order No.
1105880000
Type
CP T RM 20
Qty.
1
Order No.
1105890000
Note
Accessories
Note
1460790000 – 2014/2015
A.35
Switch-mode power supplies
PRO H - Accessories
A
/DUJHVFUHZGULYHU
6PDOOVFUHZGULYHU
Type
SDIK PH1
SDIS 0.5X3.0X100
Blade type
Size/AF
1.00
B
a
b
0.5
3
c
80
100
Order No.
9008570000
9008380000
Markers
Type
SDIK PH2
SDIS 1.0X5.5X125
Blade type
Size/AF
2.00
B
a
b
1
5.5
c
100
125
Order No.
9008580000
9008410000
Qty.
50
Order No.
1162600000
End bracket
For DIN rail TS 35
Type
SM 18/9.5 K MC NE WS
A.36
Colour
white
Qty.
200
Order No.
1248580000
3RO\DPLGHZLWKÀEUHJODVVVFUHZDEOH
WEW 35/1 SW
Colour
black
Torque
1.2 Nm
1460790000 – 2014/2015
352+'LPHQVLRQDOGUDZLQJV
CP T RM 10
CP T RM 20
35.0 (1.38)
54.0
(4.33)
110.0 (4.33)
(2.13)
38.5
- - + +
Output
Inputs ON
DC 24 V / 25 A
Inputs ON
(4.33)
80.0 (3.15)
80.0
(3.15)
110.0
(4.33)
DC IN 1
5.0
(0.20)
5.0
25.0
(0.98)
CP T SNT 70 W / 90 W
(0.20)
5.0
- + - +
DC IN 2
25.0
14.5
(0.98)
(0.57)
CP T SNT 180 W / 140 W
110.0
54.0
(4.33)
110.0 (4.33)
(2.13)
38.5
(1.52)
(1.38)
38.5 (1.52)
110.0
DC IN 1 DC IN 2
(0.20)
A
24 27 V
24 – 27 V
35.0
38.5 (1.52)
(1.52)
110.0
DC OK
DC ON
Switch-mode power supplies
connectPower PRO-H
DC ON
DC OK
O/P ADJ.
PE N
L
L
5.0
(0.20)
25.0
14.5
(0.98)
(0.57)
S P
25.0
(0.98)
5.0
N
(0.20)
5.0
(0.20)
PE
80.0 (3.15)
110.0
80.0
(3.15)
110.0
(4.33)
(4.33)
O/P ADJ.
P/S
P S
Remote
P/S
Remote
1460790000 – 2014/2015
A.37
CP T SNT 360 W / 480 W
CP T SNT 600 W / 960 W
80.0 (3.15)
125.0
(4.92)
P/S
Remote
45.0 (1.77)
P S
DC OK
DC ON
O/P ADJ.
86.5 (3.41)
A
352+'LPHQVLRQDOGUDZLQJV
125.0 (4.92)
Switch-mode power supplies
connectPower PRO-H
PE N
25.0
25.0
(0.98)
(0.98)
L
123.0
21.0
(4.84)
(0.83)
165.0 (6.50)
45.0 (1.77)
17.0
(0.67)
25.0
(0.98)
(0.98)
125.0 (4.92)
5.0
(0.20)
(1.81)
25.0
DC OK
PE N
DC ON
O/P ADJ.
86.5 (3.41)
46.0
125.0 (4.92)
L
Remote
P S
P/S
A.38
1460790000 – 2014/2015